
PAGE 16 — DCA70SSIU4F 60 HZ GENERATOR DSE8610 MKII • OPERATION MANUAL — REV. #0 (08/11/22)
GENERATOR
This generator (Figure 4) is designed as a high-quality,
portable (requires a trailer for transport) power source for
telecom sites, lighting facilities, power tools, submersible
pumps and other industrial and construction machinery.
OPERATING CONTROL PANEL
The “Operating Panel” is provided with the following:
DSE8610 MKII Controller (Monitors)
• Alarms (low, fuel, high coolant temperature)
• Battery Charge
• Battery Voltage
• Fuel Level
• Coolant Temperature
• Engine Speed
• Engine Run Time
• Engine Fuel Temperature
• Engine Fuel Pressure
• Engine Inlet Pressure
• Oil Pressure
• DEF Level Gauge
• Generator Load
• Voltage Output
• DEF Tank Level
Panel Light/Panel Light Switch
Control Power Switch
USB Service Connection Port
Contactor Closed Lamp
Contactor Open Lamp
3-Pole, 200-Amp Main Circuit Breaker
CONTROL BOX
The “Control Panel” is provided with the following:
Current Transformers
Overcurrent Relay
Starter Relay
OUTPUT TERMINAL PANEL
The “Output Terminal Panel” is provided with the following:
Three 120/240V Output Receptacles (CS-6369), 50A
Three Auxiliary Circuit Breakers, 50A
Two 120V Output Receptacles (GFCI), 20A
Two GFCI Circuit Breakers, 20A
Five Output Terminal Lugs (3Ø power)
Engine Block Heater
Battery Charger (Option)
OPEN-DELTA EXCITATION SYSTEM
Each generator is equipped with the state-of-the-art
“Open-Delta” excitation system. The open-delta system
consists of an electrically independent winding wound among
stationary windings of the AC output section.
There are four connections of the open delta—A, B, C
and D. During steady-state loads, the power from the voltage
regulator is supplied from the parallel connections of A to B,
A to D, and C to D.These three phases of the voltage input to
the voltage regulator are then rectified and are the excitation
current for the exciter section.
When a heavy load such as a motor starting or a short circuit
occurs, the automatic voltage regulator (AVR) switches the
configuration of the open delta to the series connection of B
to C. This has the effect of adding the voltages of each phase
to provide higher excitation to the exciter section and thus
better voltage response during the application of heavy loads.
The connections of the AVR to the AC output windings are for
sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a “fixed ceiling” and responds
according to the demands of the required load.
ENGINE
This generator is powered by a 4-cylinder, 4-cycle,
water-cooled, direct injection, turbocharged, EGR, DOC,
SCR, Isuzu BR-4JJ1X diesel engine.This engine is designed
to meet every performance requirement for the generator.
Reference Table 2 for engine specifications.
In keeping with MQ Power’s policy of constantly improving
its products, the specifications quoted herein are subject to
change without prior notice.
MICROPROCESSOR CONTROL SYSTEM
The microprocessor controls the RPMs of the engine.When the
engine demand increases or decreases, the microprocessor
system regulates the frequency variation to ±0.25%.
EXTENSION CABLES
When electric power is to be provided to various tools or loads
at some distance from the generator, extension cords are
normally used. Cables should be sized to allow for distance
in length and amperage so that the voltage drop between the
generator and point of use (load) is held to a minimum. Use
the cable selection chart (Table 6) as a guide for selecting
the proper extension cable size.
GENERAL INFORMATION