manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Murphy
  6. •
  7. Security Sensor
  8. •
  9. Murphy Earth Leakage Detector Units ELD2 User manual

Murphy Earth Leakage Detector Units ELD2 User manual

ELD series
EARTH LEAKAGE DETECTOR UNITS
A range of versatile and economical earth leakage
detection relays. Each unit is housed in a robust, glass
filled nylon case: an aperture in the casing allows the
installation cabling to be passed through the integral
core balance transformer.
The electronic circuitry combines a stable amplification
of the transformer output with an ability to give high
sensitivity and fast operating speeds. Detection of an
earth fault results in the energisation and latching of the
unit's SPCO relay. The unit is reset by momentarily
removing the auxiliary supply.
Protection from excessive fault current and supply
transients are fitted as standard, as is filtering to allow use
with chopped waveform and variable drive applications.
A 'test' facility is supplied in the form of a button, either
pre-fitted into the unit's front facia or connected remotely.
Electrical connection on standard units is by a colour coded,
6 way flying lead, with terminal blocks available as an
option. Each unit may be mounted on a front panel or back-
plate using two 3mm threaded inserts; an optional mounting
assembly (part no. EMA) is also available for front access
back-plate mounting.
Standard units include:
ELD2 Basic unit, with 20mS typical trip time.
Fast response to earth leakage faults.
ELD4 As ELD2, but with longer trip delays, 80mS
to 5 secs. Prevents nuisance tripping in motor
protection circuits and allows time discrimination
in distribution networks.
ELD5 As ELD4, but with an adjustable trip delay.
Available in various time ranges up to 2 seconds.
With options:–
'VS' Adjustable trip current (via front facia potentiometer.)
'HT' High temperature specification (to +60°C ambient).
'TB' Screw terminal connectors instead of flying leads.
'RC' Special calibration and 1m wiring for use with
remote CTs (for RTCs of >125mA).
Variations on our standard units and options are also
available: please call with your requirements.
When ordering, please specify:–
a) Product type number (ELD2, ELD5, etc.)
b) Auxiliary supply voltage
c) Trip current (fixed, or variable range for VS option)
d) System frequency (50, 60 or 400 Hz.)
e) Trip delay time (fixed or variable, according to model)
f) Additional options, if required.
Accessories:–
EMA Mounting assembly for ELD series.
Remote CTs A range of remote core balance/current
transformers, enabling specially
calibrated ELD units to be used with
larger cables. Available in a range of
sizes, with or without a magnetic screen
(see sheet M060101 for full details).
The Generator Controls Division of
R
M060501
Issue 4, revised 09/98
Catalogue section 75
Since 1939
Frank W. Murphy Manufacturer
PO Box 470248, Tulsa, Oklahoma 74147, USA
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146
email: [email protected]
web: http://www.fwmurphy.com
Frank W. Murphy Southern Division
PO Box 1819, Rosenberg, Texas 77471, USA
Tel: + 1 281 342 0297 Fax: + 1 281 341 6006
email: [email protected]
Frank W. Murphy Ltd.
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Tel: + 44 1722 410055 Fax + 44 1722 410088
Pour service en Français, tél: + 44 1722 410697
email: [email protected]
web: http://www.fwmurphy.co.uk
Murphek Pty. Ltd.
1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
email: [email protected]
Murphy Switch of California
PO Box 900788, Palmdale, California 93590, USA
Tel: + 1 805 272 4700 Fax: + 1 805 947 7570
email: [email protected]
web: http://www.murphyswitch.com
Murphy de Mexico S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí,S.L.P.México 78384
Tel: + 52 48 206264 Fax: + 52 48 206336
email: [email protected]
Frank W. Murphy Pte, Ltd.
No. 2 Tuas South Street 2, Sprintecs Building
02-01/02, Singapore 637895
Tel: + 65 863 1398 Fax: + 65 863 0208
email: [email protected]
Frank W. Murphy Ltd. en France
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89
Direct usine Tel: + 44 1722 410697
email: [email protected]
Dimensions (mm)
31
4
3
25
25
EMA
ELD
162
136
176
148
59
Connection (standard unit)
RED
L1
External
Test
Button
BLUE
BLACK
L2 or N
Test
ELD
GREEN
WHITE
YELLOW
Product Specification
Power supply:
operating voltages (ranges)
(all for 50/60Hz.) 110V AC (100 – 120 V)
230 V AC (200 – 250 V)
415 V AC (380 – 440 V)
power consumption < 100mA
Control:
trip levels fixed and variable, 10mA to 30A
trip point accuracy to BS4293
Relay output: (ratings for resistive load)
SPCO contacts, rated
3A @ 250V AC/30V DC,
1A @ 440V AC
Physical:
operating temperature standard unit: –25 to +40°C
'HT' spec.: –25 to +60°C
weight (with EMA) approx. 330 g

This manual suits for next models

6

Popular Security Sensor manuals by other brands

Apogee SF-110 owner's manual

Apogee

Apogee SF-110 owner's manual

EMS FireCell FCX-170-001 installation guide

EMS

EMS FireCell FCX-170-001 installation guide

STEINEL PROFESSIONAL US 360 operating instructions

STEINEL PROFESSIONAL

STEINEL PROFESSIONAL US 360 operating instructions

MICRO-EPSILON optoNCDT1800 instruction manual

MICRO-EPSILON

MICRO-EPSILON optoNCDT1800 instruction manual

Alula RE359 manual

Alula

Alula RE359 manual

Metasys 5451 manual

Metasys

Metasys 5451 manual

FORTEZA FM-60(24)-BT user manual

FORTEZA

FORTEZA FM-60(24)-BT user manual

hager WE050 User instructions

hager

hager WE050 User instructions

SEBSON IR_OUT_E manual

SEBSON

SEBSON IR_OUT_E manual

TAKACHIO MPL-H11S manual

TAKACHIO

TAKACHIO MPL-H11S manual

Hitachi SOR-NEC Installation and operation manual

Hitachi

Hitachi SOR-NEC Installation and operation manual

GROTHE McGuard professional Series manual

GROTHE

GROTHE McGuard professional Series manual

Sundstrom SR 540 EX Instructions for use

Sundstrom

Sundstrom SR 540 EX Instructions for use

Maxkin PIR-600PLUS user manual

Maxkin

Maxkin PIR-600PLUS user manual

Visonic Quatro+ installation instructions

Visonic

Visonic Quatro+ installation instructions

Sperian Miller EN 353.1 manual

Sperian

Sperian Miller EN 353.1 manual

TS-market LORNET-36 user manual

TS-market

TS-market LORNET-36 user manual

DoCash mini IR user manual

DoCash

DoCash mini IR user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.