Nordtronic INDUSTRIA IP65 Series User manual

1
52
INSTALLATION & MAINTENANCE MANUAL
TRLEDxx
IP
65
230V
50Hz
52111014, 52121014, 52131014 07-2018
Find the updated manual on our website - www.nordtronic.com
With reservation for typing errors
Nordtronic A/S | Flade Engvej 4 | DK - 9900 Frederikshavn | Denmark
CVR: 29808708 | Tel: +45 70209531 | www.nordtronic.com
Monteringsvejledning / Installation instructions
INDUSTRIA IP65
220 -240
VAC
14W
23W
29W
4000
Kelvin
1530
2650
3650
Lumen
CRI>80 100%
100%
RoHS

Vigtig information
Armaturet skal monteres af en autoriseret
el-installatør. Kontrollér at mærkningen på
armaturet stemmer overens med den anvend-
te spænding, samt installationsmåde og
-område. Husk altid at afbryde for gruppe-
afbryderen inden montering af armaturet.
Overskrid aldrig armaturets max. wattage
mærkning.
Vær opmærksom på, at lyskilden sidder
korrekt i fatningen. Anvend altid kabler af
en type, der er godkendt til fast installation
efter Stærkstrømsbekendtgørelsens krav og
gældende SIK-meddelelser.
Monteringsvejledning
Kontrollér at armaturet er godkendt til det
aktuelle sted, hvor det skal monteres.
Bemærk: Hvis dette armatur bruges sam-
men med eksterne PIR eller sensorer, bedes
du venligst forespørge hos producenten
af sensorer, at de er kompatible med LED
armaturer.
Vigtigt: Hvis armaturet monteres udenfor, skal
ledningskablet tilsluttes til en egnet IP-klassi-
ficeret forbindelsesboks.
• Brug monteringsbeslaget som skabelon,
og lav huller til montering af armaturet, som
anvist på fig. 1.
• Løsne klipsene på begge sider af armaturet
(se fig. 2).
• Fjern glasset.
• Fjern dækpladen ved at klemme sammen
på de to klipse (se fig. 3).
• Tilslut armaturet efter anvisning på figur 4
• Monter dækpladen, tjek at alle klemmer er
fastgjort korrekt, og herefter påsæt glasset
igen.
• Armaturet er forberedt til videresløjfning,
og opretholder IP65 ved brug af medføl-
gende forskruninger.
Important information
The lighting fixure must be installed by an
authorised electrician. Check that the label
on the product matches the utilised voltage
and also check the method of installation
and area. Always remember to switch off the
main power prior to installation of the lighting
fixture. Never exceed the wattage label on
the product.
Installation instructions
Note: If this luminaire is being used in con-
junction with external PIR or sensors, please
confirm with the manufacturer of the sensors
that they are compatible with LED luminaires
• Provide power to the required point of
installation.
• Important: Subject to the surface founda-
tion material, ensure the correct fixings are
used. If installed outside, the mains cable
should be connected into a suitable IP
rated junction box
• Referring to Fig 1, using the mounting
brackets as a template, mark the location
of the fixing holes. Drill the fixing holes
ensuring not to infringe with any joists, gas/
water pipes, or electrical cables that may
be hidden behind the surface.
• Unfasten clips on either side of the fitting
(see Fig 2).
• Remove the diffuser.
• Remove the gear tray by pinching the clips
at the two locations (see Fig 3)
• When using as a singular fitting, feed cable
through a compression gland (included) at
the end of the fitting.
• Connect the Live (brown), Neutral (blue)
and Earth (yellow and green) via the 3-way
terminal connector (see Fig 4).
• Replace the gear tray and diffuser ensuring
all clips are fastened correctly.
• Switch on power supply and check for
correct operation
Note: This fitting can be linked to another
fitting by using the same 3-way terminal con-
nector in Fig 4 and has knock-outs at both
ends of the fitting which can be drilled using
a 20mm holesaw. The IP65 rating will be
maintained when a 20mm compression gland
(supplied) is used in the drilled hole.
Monteringsvejledning / Installation instructions

L (mm) L (ft) A1 (mm)
Industria IP65 14W 653 mm 2 390 mm
Industria IP65 23W 1263 mm 4 900 mm
Industria IP65 29W 1563 mm 5 1000 mm
Fig 1
2
These instructions should be read carefully and retained after installation by the end user for
future reference and maintenance.
These instructions should be used to aid installation of the following products:
TRLED12 / TRLED14 / TRLED15 / TRLED16 / TRLED22 / TRLED24 / TRLED25 / TRLED26
GENERAL INSTRUCTIONS
SAFETY
INSTALLATION
• Installation of this luminaire should only be carried out by a qualified electrician or competent
person to the latest Building and current IEE Wiring Regulations (BS7671)
• Please isolate mains prior to installation/maintenance
• Check the total load on the circuit (including when this luminaire and LED load is fitted) does not
exceed the rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress of Protection) rating of this product when deciding the location for
installation
• This product is Class I and must be earthed
• This product is IP65 rated
• This product is non-dimmable
Note: Outdoor electrical installations should be protected by an earth leakage circuit breaker such as
a residual current device (RCD)
Note: If this luminaire is being used in conjunction with external PIR or sensors, please confirm with
the manufacturer of the sensors that they are compatible with LED luminaires
• Provide power to the required point of installation
• Important: Subject to the surface foundation material, ensure the correct fixings are used. If
installed outside, the mains cable should be connected into a suitable IP rated junction box
• Referring to Fig 1, using the mounting brackets as a template, mark the location of the fixing holes.
Drill the fixing holes ensuring not to infringe with any joists, gas/water pipes, or electrical cables
that may be hidden behind the surface
TRLEDxx
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for future reference and
maintenance.
These instructions should be used to aid installation of the following products:
TRLED12 / TRLED14 / TRLED15 / TRLED16 / TRLED22 / TRLED24 / TRLED25 / TRLED26
SAFETY
•Installation of this luminaire should only be carried out by a qualified electrician or competent person to the
latest Building and current IEE Wiring Regulations (BS7671)
•Please isolate mains prior to installation/maintenance
•Check the total load on the circuit (including when this luminaire and LED load is fitted) does not exceed the
rating of the circuit cable, fuse or circuit breaker
•Please note the IP (Ingress of Protection) rating of this product when deciding the location for installation
•This product is Class I and must be earthed
•This product is IP65 rated
•This product is non-dimmable
Note: Outdoor electrical installations should be protected by an earth leakage circuit breaker such as a residual current
device (RCD)
INSTALLATION
Note: If this luminaire is being used in conjunction with external PIR or sensors, please confirm with the manufacturer of
the sensors that they are compatible with LED luminaires
•Provide power to the required point of installation
•Important: Subject to the surface foundation material, ensure the correct fixings are used if installed outside, the
mains cable should be connected into a suitable IP rated junction box
•Referring to Fig 1, using the mounting brackets as a template, mark the location of the fixing holes. Drill the fixing
holes ensuring not to infringe with any joists, gas/water pipes, or electrical cables that may be hidden behind the
surface
Fig 1
L (mm)
L (ft)
A1 (mm)
TRLED12 / 22
1263
2
390
TRLED14 / 24
1563
4
900
TRLED15 / 25
1828
5
1000
TRLED16 / 26
1263
6
1000
Fig 1
Fig 2
Fig 3
Fig 4
Løsen klipsene på begge sider af armaturet
Unfasten clips on both sides
• Unfasten clips on either side of the fitting (see Fig 2)
• Remove the diffuser
• Remove the gear tray by pinching the clips at the two locations (see Fig 3)
• When using as a singular fitting, feed cable through a compression gland (included) at the end of
the fitting
• Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal
connector (see Fig 4)
• Replace the gear tray and diffuser ensuring all clips are fastened correctly
• Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4
and has knock-outs at both ends of the fitting which can be drilled using a 20mm holesaw. The IP65
rating will be maintained when a 20mm compression gland (supplied) is used in the drilled hole.
3
Fig 2
Fig 3
Fig 4
L (mm) L (ft) A1 (mm)
TRLED12 / 22 653mm 2 390
TRLED14 / 24 1263mm 4 900
TRLED15 / 25 1563mm 5 1000
TRLED16 / 26 1828mm 6 1000
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
• Unfasten clips on either side of the fitting (see Fig 2)
• Remove the diffuser
• Remove the gear tray by pinching the clips at the two locations (see Fig 3)
• When using as a singular fitting, feed cable through a compression gland (included) at the end of
the fitting
• Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal
connector (see Fig 4)
• Replace the gear tray and diffuser ensuring all clips are fastened correctly
• Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4
and has knock-outs at both ends of the fitting which can be drilled using a 20mm holesaw. The IP65
rating will be maintained when a 20mm compression gland (supplied) is used in the drilled hole.
3
Fig 2
Fig 3
Fig 4
L (mm) L (ft) A1 (mm)
TRLED12 / 22 653mm 2 390
TRLED14 / 24 1263mm 4 900
TRLED15 / 25 1563mm 5 1000
TRLED16 / 26 1828mm 6 1000
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
• Unfasten clips on either side of the fitting (see Fig 2)
• Remove the diffuser
• Remove the gear tray by pinching the clips at the two locations (see Fig 3)
• When using as a singular fitting, feed cable through a compression gland (included) at the end of
the fitting
• Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal
connector (see Fig 4)
• Replace the gear tray and diffuser ensuring all clips are fastened correctly
• Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4
and has knock-outs at both ends of the fitting which can be drilled using a 20mm holesaw. The IP65
rating will be maintained when a 20mm compression gland (supplied) is used in the drilled hole.
3
Fig 2
Fig 3
Fig 4
L (mm) L (ft) A1 (mm)
TRLED12 / 22 653mm 2 390
TRLED14 / 24 1263mm 4 900
TRLED15 / 25 1563mm 5 1000
TRLED16 / 26 1828mm 6 1000
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
•Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
•Remove the diffuser
•Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
•When using as a singular fitting, feed cable through a compression gland (included) at the end of the fitting
•Connect the Live (brown), Neutral (blue) and Earth (yellow and green) via the 3-way terminal connector (see Fig
4)
Fig 4
•Replace the gear tray and diffuser ensuring all clips are fastened correctly
•Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the same 3-way terminal connector in Fig 4 and has knock-outs at
both ends of the fitting which can be drilled using a 20mm holesaw. The IP65 rating will be maintained when a 20mm
compression gland (not provided) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance testing.
Irreparable damage will occur if this instruction is not followed.
GENERAL
Pinch at these points
Neutral (blue)
N
L
Live (brown)
E
Earth (green/yellow)
Fase (brun)
Live (brown
Jord (grøn og gul)
Earth (green and yellow)
Nul (blå)
Neutral (blue)
Klem her
Pinch at these points

Nordtronic A/S | Flade Engvej 4 | DK - 9900 Frederikshavn | Denmark
CVR: 29808708 | Tel: +45 70209531 | www.nordtronic.com
This manual suits for next models
3
Popular Lantern manuals by other brands

Lumascape
Lumascape LS482 Important Instructions for Installation

Hess
Hess CENTO A Installation and operating instructions

ML Accessories
ML Accessories Knightsbridge OL01B Installation & maintenance manual

Lighting Technologies
Lighting Technologies KRK Series manual

olympia electronics
olympia electronics GR-8/leds installation instructions

Maxim
Maxim Dover 56094 quick start guide