Nortroll ComTroll 230 User manual

Page 1
ComTroll230
ComTroll 230T
ComTroll 230S
User Manual

Page 2
This document describes ComTroll 230, Remote Terminal Unit.
It also covers the –T and –S versions.
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30
CRU-200
COMMUNICATION
MODULE
SLC-200+
POWER MODULE
LOCALREMOTE
OFF
NORTROLL ASNORTROLL AS
REMOTE
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCAL
OFF
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCAL
OFF
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCAL
OFF
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCALREMOTE
OFF
REMOTE
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCAL
OFF
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCAL
OFF
CLOSE
OPEN
SERVICE
RESET
TX
RX
CLOSED
OPEN
SERVICE
NORTROLL AS
RTU-30i
LOCAL
OFF
Information in this document is subject to change without notice.
No parts of this documentation may be reproduced in any form by any means without the written permission
of Nortroll AS.
Copyright 2006 Nortroll AS. All rights reserved. All Nortroll products are trademarks or registered
trademarks of Nortroll AS. Other product names are trademarks or registered trademarks of their respective
holders.
2006 NORTROLL AS
P.O.Box 133
7601 Levanger
Norway
www.nortroll.no

Page 3
Contents
CONTENTS............................................................................................................................................. 3
COMTROLL 230, REMOTE TERMINAL UNIT........................................................................................... 4
COMMUNICATION.................................................................................................................................. 5
POWER SUPPLY ..................................................................................................................................... 6
CONNECTIONS ....................................................................................................................................... 6
Main backplane, 06310a ................................................................................................................. 6
Link Settings .................................................................................................................................... 7
J3 pin overview................................................................................................................................ 7
J7 Bridge overview .......................................................................................................................... 8
COMTROLL 230T .................................................................................................................................. 8
Installing the TSU-25....................................................................................................................... 8
COMTROLL 230S ................................................................................................................................ 10
Installing Modbus devices ............................................................................................................. 10

Page 4
ComTroll 230, Remote Terminal Unit
The ComTroll 230 is designed for a complete and modular functionality for monitoring and
control of primary and secondary functions in the distribution network.
The rack-mounted system can control and monitor a wide range of objects such as pole-
mounted sectionalizers, breakers, earthing switches, relay protection, fault indicators, tap-
changers and more through its serial, digital and analog interface.
The analog inputs can be connected to different sensors reading values for power frequency,
active/reactive power, bus-bar voltage, load current and more.
Based on the RTU-30 Controller unit, ComTroll 230 offers both local- and remote control of
the connected equipment.
ComTroll 230 can be connected to a wide range of transceivers for different communication
solutions:
Radio
Fibre optics
Power Line
Leased Lines
Ethernet
SLC-200+
CRU-200 RTU-30
RTU-30i RTU-30i
With the extensible backplane solution, ComTroll 230 can be supplied in a 10.5” single frame
rack where up to three RTU-30/RTU-30i cards can be fitted. It can also be supplied in a full
19” single frame rack with space for up to eight RTU-30/RTU-30i cards.
RTU-30 is acting as a master for the additional RTU-30i cards. One RTU-30 can communicate
with 14 RTU-30i cards on the I2C-bus.

Page 5
ComTroll 230 can be supplied as a –m version where the LED’s for status messages,
open/close button and the ModeSwitch (Remote/Off/Local) are removed.
Each RTU-30 /RTU-30i has dedicated OPEN and CLOSE outputs with accompanying open and
closed limit-switch inputs to ensure reliable operation.
Details about the RTU-30 /RTU-30i functions and options can be found in separate
document.
Communication
RTU
30
RTU
30i
RTU
30i
Communication
Channel
Transceiver
I C
2
The ComTroll 230 Remote Terminal Unit can communicate with the central unit /SCADA on
different communication media. The most commonly used is low power radio and fiber-
optics, but the flexible communication platform can utilize almost any media using a
specified Transceiver module for the actual media used.
CRU-200 is a module comprising a modem and radio. Nortroll offers both VHF and UHF
radios with respectively frequency range 140-172 MHz and 406-460 MHz.
The ComTroll 230 with radio communication can be used as a repeater for other Nortroll
devices in the network.
Where other communication media is used, the radio is not mounted in the CRU-200. The
transceiver will in these cases normally be mounted outside the rack.

Page 6
Power Supply
ComTroll 230 requires 12Vdc supply voltage with a battery backup. It can be solar charged in
configurations with up to three RTU cards. (With radio communication only).
SLC-200+ is the standard DC/DC regulator where external 12Vdc is available. This is also a
battery charger for the backup battery, both when external DC is connected and when a solar
panel is connected.
The SLC-200+ can be replaced with DC/DC-1, a regulator unit for input voltages between 18-
36 Vdc and 36-72 Vdc.
Connections
ComTroll 230 uses two different backplanes, 06310a and 06315a.
06310a covers the SLC-200+ (or DC-DC-1), the CRU-200 and one RTU-30 card.
Each additional RTU-30i card in a rack needs a separate backplane. The RTU-cards are tied
together on the Local Bus Bridge Cable, where also supply voltage is transferred to the next
unit.
NORTROLL AS
PCB 06310a
Ext.DC2
J6
Ext.DC1
J1
12V
J5
Battery
Backplane RTU26/RTU30
J9
SVDC
J2 J2 J8
TP-Net
J10
J3 J3
F2
F1 LowBatt
Ext.DC
Batt.
PCB 06315a
PCB 06315a
+
+
+
++
A ribbon cable connects between each RTU-30 and the RIM 1, Relay Interface Module. For
details about the RIM 1, please refer to separate documentation.
Main backplane, 06310a
J1: 12Vdc OUTPUT, from the SLC-200+. J1 can also be used as a 12Vdc input when the
SLC-200+ is not mounted.
J5: 12V battery input
J6: External DC input from solar panel or external DC source. Max voltage: 24Vdc
J9: DC input only used when DC/DC-1 regulator is mounted.
J10: Twisted Pair Bus. (TP/XF-78 or TP/FT-10)

Page 7
Link Settings
LowBatt
F1
Ext.DC
Batt.
F2
J8
J3 pin overview
Pin 1 is located in the upper left corner of J3.
F1: Connects the Low Battery signal from SLC-200+ to Digital Input 1 on the
NTM-20/25 Modem. Only used in repeaters. Default set open.
F2: Connects either External DC input or the Battery Input to the Analog
Input 4 on the first RTU-30 card. Battery voltage is monitored as the
default option. Ai_4 is setup to monitor voltages between 0V and 15Vdc.
F8: Activate / deactivate the termination of the twisted pair bus. Not
mounted as default.

Page 8
J7 Bridge overview
12 Vdc
GND
I2C
TP-Net
The backplane for additional RTU-30 cards have the same connectors and pin-out as the main
backplane.
ComTroll 230T
Installing the TSU-25
Before powering the TSU-25, connect the antenna to the connector located on the front
panel. The GPS antenna needs to be located with a good clear 360 degree view of the sky.
The ideal location for the antenna is a roof-top. However, in practice the TSU-25 antenna
All events in a substation can be precisely time tagged by the use of
GPS Time Synchronization Unit, TSU-25.
The TSU25 utilizes the accurate time signal broadcasts from the GPS
satellite network.
The TSU-25 has an integrated GPS receiver that constantly tracks up to
8 satellites simultaneously to provide a highly accurate time reference.
A software clock on the RTU-30t card will be calibrated every minute to
time-stamp events that occur in the digital and analog inputs. The time
information will be sent together with the alarm/message to the
SCADA.
Up to 7 RTU-30t cards can be calibrated from one TSU-25.
The RTU-30t has the same functions and I/O package as RTU-30 and
RTU-30i.

Page 9
generally works well on a window-ledge or positioned in a window or wall. As a rule of
thumb, the better the view the antenna has of the sky, the better the signal locks and a good
continuous uninterrupted time signal is provided.
TSU-25 can only be used together with RTU-30t. When more than one RTU-30t card is
installed in the same rack, a Router Module (RTR-10) must be installed.
Running LED (green):
LED flash once every 10 seconds as long as the TSU-25 is powered and the software runs OK.
Sync-LED (yellow):
The LED flashes every second when the GPS-unit is active.
Status-LED (red):
When the TSU-25 does not have a valid time, the Status LED will flash once a second.
Normal operating condition:
The TSU will activate the GPS every 660s (11min) or 2500s (42min) dependent upon the
measured temperature. When the interval expires the GPS will be activated and the Sync-LED
will start flashing. The LED flashes until the clock is updated.
Independent of this update, the TSU-25 sends out a time-sync message on the backplane
bus. The RTU-30T cards that are placed on the same bus will receive this accurate time
information and update the software clock that runs constantly on each individual RTU-30t
card.
This will give an accuracy of +/- 10ms on the time information sent from the RTU upon an
event.
Different types of antennas are
available. The default antenna is a
3.3V active antenna, but other types
of antennas can be used.’
IMPORTANT:
Do NOT change any antenna settings
without consulting NORTROLL AS
first.
Wrong setting can cause permanent
damage to the GPS unit and the TSU-
25.

Page 10
Faulty operating condition:
If the GPS receiver is not able to establish contact with the satellites, the TSU-25 will see that
the attempt to download accurate time information failed.
When the next sync period expires, the Status-LED will start flashing together with the Sync-
LED. The Status-LED will stop flashing when the satellite contact is established again.
If for some reason the contact cannot be restored, or the TSU-25 is unable to update the
software clock on the RTU-30t the time information sent will drift (note! worst case) +/-7 sec
every 24-hour period.
ComTroll 230S
ComTroll 230S is a gateway that resides on the ComTroll Network and connects to Modbus
devices over EIA-232 or EIA-485. The controller module RTU-30s supports up to 14 Modbus
devices on a multi-drop EIA-485 network.
The RTU-30s can be installed in a ComTroll 230 rack where other RTU-30 versions (RTU-
30/RTU-30i/RTU-30t) are installed, and support all media available in the ComTroll Network
System.
SERVICE
RESET
TX
RX
SERVICE
NORTROLL AS
RTU-30s
CRU-200
COMMUNICATION
MODULE
SLC-200+
POWER MODULE
NORTROLL ASNORTROLL AS
MODBUS
DEVICE
#1
MODBUS
DEVICE
#2
MODBUS
DEVICE
#247
Installing Modbus devices
For details about installation of Modbus devices, please contact NORTROLL AS.

Page 11
Ordering information
Product nr: 03-0230-01 ComTroll 230
Product nr: 03-0230-22 ComTroll 230S
Product nr: 03-0230-30 ComTroll 230T
Related products:
Product nr: 03-0030-01 RTU30
Product nr: 03-0030-03 RTU30i
Product nr: 03-0030-05 RTU30s
Product nr: 03-0030-07 RTU30t
Product nr: 03-0200-01 CRU-200 SPM (Radio and modem without router module)
Product nr: 03-0200-02 CRU-200 DC (Radio and modem with router module)
Product nr: 03-0030-50 RTU 30 Additional Modbus Object (AMO)
Product nr: 03-0030-15 RTU 30 add-on incl. Backplane RTU 30 add-on
Product nr: 03-0030-10 RTU 30 i add-on incl. Backplane RTU 30 add-on
Product no: 7211 Steel Outdoor Cabinet [500x500x300]
NORTROLL AS
Postboks 133
N-7601 Levanger
Norway
Phone: (+47) 7408 5500
Fax: (+47) 7408 5501
Email: n[email protected]
This manual suits for next models
2
Table of contents
Popular Controllers manuals by other brands

Tolomatic
Tolomatic ServoWeld CSW Installation operation & maintenance

Shuang Ri
Shuang Ri SR530F8 user manual

Alfalaval
Alfalaval ThinkTop Basic Installation instruction

KiWi Lighting
KiWi Lighting DMX300 Product specification

alphainnoTec
alphainnoTec Luxtronik operating manual

BECS
BECS BECSys5 Operation and maintenance manual

Kromschroeder
Kromschroeder TC technical information

i-MO
i-MO i3N Series user manual

Alphawave Photonics
Alphawave Photonics AWCL-300-6P Series user manual

Timeguard
Timeguard PDWM1500 Installation & operating instructions

FOS Technologies
FOS Technologies Designer 2048 user manual

Timeguard
Timeguard RTS113Q Quick start instructions