NSC Sicherheitstechnik Solution F2 Specification sheet

NSC Sicherheitstechnik GmbH 1/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
Fire Control Panels “Solution F2”
Operating and Installation Manual
Issue: May 2011

NSC Sicherheitstechnik GmbH 2/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01

NSC Sicherheitstechnik GmbH 3/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
Content
1.
Description of Control Panel:........................................................................................................... 5
LED indications:.......................................................................................................................... 5
LC module indications:............................................................................................................... 6
Description of the push buttons:................................................................................................. 7
Configuration: ............................................................................................................................. 7
2.
Menus for the end user:................................................................................................................... 9
Description.................................................................................................................................. 9
General Main menu for end user................................................................................................ 9
Main menu „Switch on / switch off“............................................................................................. 9
Switching on/off: zones and single detectors........................................................................... 10
Switching on/off: Addressable detectors.................................................................................. 10
Switching on/off: OC-Outputs................................................................................................... 10
Switching on/off: 6 internal relays............................................................................................. 11
Switching on/off: 4 internal power outputs ............................................................................... 11
Switching on/off: sounders / strobes ........................................................................................ 11
Switching on/off: Alarm Transmission Device (TD).................................................................. 12
Switching on/off: Alarm transmission delay.............................................................................. 12
Switching on/off: Fire protection outputs.................................................................................. 12
Alarmcounter ............................................................................................................................ 12
Changing the end user access code........................................................................................ 13
Diagnosis Menu........................................................................................................................ 13
Event memory .......................................................................................................................... 13
Event memory: "Filter“.............................................................................................................. 13
Event memory: "Printing“.......................................................................................................... 14
Detector data............................................................................................................................ 14
Table of detectors..................................................................................................................... 14
Example of detector data: MCP ............................................................................................... 16
Example of detector data: Optical smoke detector .................................................................. 17
Only for Hochiki ESP............................................................................................................... 17
Only for Apollo Discovery......................................................................................................... 18
Only for Hochiki ESP............................................................................................................... 17
Example of „Zeropoint“ and „Firepoint“ display........................................................................ 17
Only for Apollo Discovery......................................................................................................... 18
Hardware modules: Overview .................................................................................................. 19
Internal Modules: Details.......................................................................................................... 19
Example of details of Hochiki ESP detector module................................................................ 19
Modem data.............................................................................................................................. 19
Display of FRP/LCD Panel....................................................................................................... 20
Example of details of a fire brigade repeater panel with fire brigade control panel ................. 20
Example of power supply voltages........................................................................................... 20
Example of power output voltages ........................................................................................... 20
Example of input voltages ........................................................................................................ 21
Example of displaying software version and Serial No............................................................ 21
3.
Menus for the installer:.................................................................................................................. 22
Access to the installer menu .................................................................................................... 23
General Main menu for installer ............................................................................................... 23
Main menu: Test functions ....................................................................................................... 24
Detector test (only for addressable detectors)......................................................................... 24
Menu "Manual Controlling“....................................................................................................... 25
Manual Control: internal OC Outputs....................................................................................... 25
Manual Control: 6 internal Relays............................................................................................ 25
Manual Control: 4 monitored Power Outputs........................................................................... 26
Manual Control: Output modules (loop) ................................................................................... 26
Menu „Simulation“ .................................................................................................................... 26
Menu „Revision“ ....................................................................................................................... 27

NSC Sicherheitstechnik GmbH 4/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
Settings 1 of FCP ..................................................................................................................... 27
To set date and time................................................................................................................. 27
Maintenance............................................................................................................................. 28
System settings........................................................................................................................ 28
Scanning RS485 devices ......................................................................................................... 29
Scan detectors.......................................................................................................................... 29
Delete Configuration................................................................................................................. 30
Delete Texts ............................................................................................................................. 30
Delete Events ........................................................................................................................... 30
Selecting the panel language................................................................................................... 30
Einstellungen 2 der BMZ.......................................................................................................... 30
Changing the installer access code.......................................................................................... 31
Configuring the interfaces ........................................................................................................ 31
Interface protocols.................................................................................................................... 31
Interface baudrates................................................................................................................... 31
Modem functions...................................................................................................................... 32
Power outputs: Thresholds....................................................................................................... 32
Loop parameters ...................................................................................................................... 32
Options ..................................................................................................................................... 33
ESPA 4.4.4 Settings................................................................................................................. 33
Modbus Einstellungen.............................................................................................................. 33
4.
Firmware Update........................................................................................................................... 34
For the flash update of the Solution F2 firmware you need the following items:...................... 34
Preparation............................................................................................................................... 34
Start of Bootloader & Flash Update Routine............................................................................ 34
Execute flash update................................................................................................................ 35
Errors and possible reasons..................................................................................................... 36
5.
Mounting instruction ...................................................................................................................... 38
6.
Commissioning of Solution F2....................................................................................................... 39
General..................................................................................................................................... 39
Checking the documentation.................................................................................................... 39
Checking the system components ........................................................................................... 39
Checking the wiring system...................................................................................................... 39
Measure cable resistance of loop wiring (without voltage)....................................................... 40
Measurement of the end of line resistors of the monitored power outputs (without voltage)... 40
Measurement of the end of line resistors of the monitored inputs (without voltage)................ 40
Checking the end of line resistor on the RS485 bus................................................................ 41
Commissioning of the power supply......................................................................................... 41
Scanning of internal an external components.......................................................................... 41
Detector modules ..................................................................................................................... 41
Serial devices ........................................................................................................................... 42
Addressable detectors/modules............................................................................................... 42
Checking of earth fault.............................................................................................................. 43
Measurement of loop voltage and current................................................................................ 43
Configure power outputs .......................................................................................................... 43
Configuration of the fire control system.................................................................................... 44
Functional tests ........................................................................................................................ 45
7.
Technical specifications :............................................................................................................... 46
8.
CE marking :.................................................................................................................................. 47
Attachment A : Menus for the end user
Attachment B : Menus for the installer

NSC Sicherheitstechnik GmbH 5/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
1. Description of Control Panel:
Picture of the control panel of the "Solution F2":
LED indications
Dynamic functions keys F1 – F4, Keypad and cursor push buttons
The functions are individually indicated
in the bottom line of the LC module
Field programmable push buttons S1 – S2
‘Prog’ : to select the main menu
‘ext. sounders off / on’
‘int. buzzer off“ / “LED test’
‘Reset’
LED indications:
LED : Description :
green LED "In Operation“ The Fire Control Panel (FCP) is in operation.
green LED "Delay“ Delay of transmission device signal to the fire brigade for
automatic detectors.
green LED "No Delay“ Indicates that the FCP is in normal operation mode. That
means the main alarm is NOT delayed and any alarm
activates the Fire Brigade immediately.
green LED "Service“ Indicates that the FCP is in „Service Mode“.
red LED "Main alarm“ Indicates that the FCP is in Alarm condition. See LC
module for detailed information. If an alarm transmission
device (TD) is connected to the panel the panel has tried
to activate the TD.
red LED "Internal alarm“ Indicates that the FCP is in Alarm condition. See LC
module for detailed information.
red LED "Fire Brigade alarmed“ Indicates that the FCP has activated the alarm
transmission device (TD) to the Fire Brigade and the TD

NSC Sicherheitstechnik GmbH 6/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
gave a response to confirm the activation. (Input
“TD response” in the wiring diagrams can be used for
this confirmation signal).
red LED "Call Fire Brigade“ Indicates that the FCP is in Main Alarm condition but the
alarm transmission device (TD) could not be activated.
So the Fire Brigade maybe has to be called by phone.
yellow LED "Fault“ Indicates that the FCP is in fault condition. At least one
device (detector, module), input, output or system
component is not in normal condition. See LC module for
detailed information.
yellow LED "System“ The FCP itself is in fault condition. That means that
maybe the main board (micro controller) does not
work well and the correct function of the FCP is not
guaranteed. Please check immediately by the
installation company.
yellow LED "Disabling“ Indicates that at least one device (detector, module),
input or output is disabled (switched off).
yellow LED "Transmission Device“ (TD) In case of flashing this LED (and yellow LED "Fault“ is
on) the TD is in fault condition.
In case this LED is on (and yellow LED "Disabled“ is on)
the TD is switched off.
yellow LED "Sounders“ In case of flashing this LED (and yellow LED "Fault“ is
on) one of the sounder outputs is in fault condition.
In case this LED is on (and yellow LED "Disabled“ is on)
one of the sounder outputs is switched off.
red LED "FPE activated“ One or more automatic controlling, configured to
switching function "switch like fire protection equipment“,
are active.
LC module indications:
The LC module is a graphics LCD which is automatically illuminated in the case of any event. That means
if an alarm message, a fault message, a disabled message or just if any push button is pressed the LC
module activated the illumination. Then detailed information is shown in the display. Either the LCD
shows the information in 8 lines of alpha numerical texts or in a graphics mode like bar charts or columns.
Usually the FCP shows the condition of the panel in the middle of the LC module. There is in big letter the
current status on a dark background. The following messages are possible :
IN OPERATION = normal condition
ALARM = the FCP is in alarm condition
T E S T ALARM = the FCP is in test alarm condition
FAULT = the FCP is in fault condition
SWITCH OFF = certain devices of the FCP are switched off
ACTIVATION = outputs are activated by automatic controllings
If the user enters one of the menus (by pressing the push button „Prog“) at the bottom line of the LC
module he sees the dynamic function keys F1 – F4. Sometimes all 4 keys are used, sometimes only

NSC Sicherheitstechnik GmbH 7/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
one or two. It depends on the menu. Here we do not describe the function keys in details. Therefore
please have a look into section 2.
Please note that : usually there are the following standard functions for
„F1“ = „cancel“ or „back“. Means to leave the current menu and jump into the menu above, and
„F4“ = „Enter“. Means to select (or confirm) the function which is marked in the LC module by a
black background.
Description of the push buttons:
The control panel of the FCP "Solution F2“ is a high-quality membrane keypad. An intelligent circuit
detects any pressing of the push buttons and confirms it by a beep.
Push button : Description :
By this push button the user leaves the normal operation display and enters the main
menu of the FCP. See the detailed description in section 2.
This push button deactivates (switch off) the external sounder outputs in case of an
alarm. This is a temporary deactivation because if another alarm comes in the
sounders will be activated again. It's also possible by this key to reactivate the
sounders manually.
This push button deactivates (switch off) the internal buzzer in case of an alarm or
fault message. This is a temporary deactivation because if another message comes in
the buzzer will be activated again.
In case of an alarm and delyed alarm transmission, the inspection time will be started.
If there is no alarm and no fault holding this push button activates an LED test.
This push button resets the FCP.
To reset a "key deposit alarm" message you have to enter the installer mode in main
menu. Afterwards the alarm can be reset it by this key.
Programmable function key (S1, S2). The setting could be done by the pC
configuration tool.
Use this push button in the menus to confirm your inputs line by line.
Use this push button in the menus to cancel your inputs.
Cursor control keypad.
Configuration:
The configuration of the fire control panel "Solution F2" has to be done generally by the PC configuration
software.
With Firmware release 1.00 and following the data communication between panel amd pc must be
enabled by user- or installercode. This requires as minimum release 6.0.0.0 of the configuration
software.
You need a standard USB cable USB-A to USB-B for connection between pc an panel.

NSC Sicherheitstechnik GmbH 8/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
Some essential settings also can be made directly through the keypad of the panel, i.e. setting of system
parameters or interface configuration. You have to type in the installer code to get access to the relating
menus (s. menu 20)

NSC Sicherheitstechnik GmbH 9/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
2. Menus for the end user:
The following description contains all the menus for the end user. If the push button „Prog" is
pressed it starts with the main menu.
Nr. LC-Display of Solution F2 Description
01
Main menu
1. Switch on/off
2. Alarm counter
3. End user code
4. Diagnosis
Cancel Installer Enter
General Main menu for end user
This menu appears immediately after pressing „Prog“.
The functions have the followings meanings :
1. To switch on / off detectors, input-/ output
modules, delay mode, zones and general
outputs Jump to Menu 02
2. Indication of the alarm counter. It is a 4 digit
number (1 – 9999) Menü 03
3. To change the end user code Jump to
Menu 04
4. To jump to the diagnosis menu Jump to
Menu 05
The push button "cancel“ (F1) leads to the normal
status indication of the FCP.
The push button Installer (F3) is to use for the
installer company only. It leads to the menus for
service and configuration.
The push button „Enter“ (F4) selects (activates)
the function which is marked by a black
background. Instead you can also select the
function by pressing the no. left in front of the
functions (here : 1 – 4).
02
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output
6. Alarm Trans.Dev.
3. Relay
7. Delay
4. Power Output
8. Fire Outputs
Cancel Enter
Main menu „Switch on / switch off“
1. Switching on/off of zones and detectors
Jump to Menu 02.1
2. Switching on/off of OC-Outputs Jump to
Menu 02.3
3. Switching on/off of Relays inside the FCP
Jump to Menu 02.4
4. Switching on/off of 3 monitored power
outputs Jump to Menu 02.5
5. Continuously switching on/off of sounders /
strobes (incl. loop sounders) Jump to
Menu 02.6
6. Switching on/off the alarm transmission
device (TD) Jump to Menu 02.7
7. To activate / deactivate the alarm delay for
the TD Jump to Menu 02.8
8. Temporary switching on/off the fire
protection outputs. This means all outputs
will be deactivated until this function is
canceled. The fire protection outputs CAN
NOT be switched off during alarm state.
Jump to Menu 02.9

NSC Sicherheitstechnik GmbH 10/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
02.1
Zones & detect.
Status
from zone : 5
programmed zone text
To zone :
Cancel On Off Detect.
Switching on/off: zones and single detectors
You can switch off single zones or several zones
simultaneously. This is done by using the “from …
to… “ function. Please type the zone number and
confirm by “OK”.
"Status“ means the current status of the zone (e.g.
normal, alarm, fault). To switch off the zone you have
to press "Off“ (F3) or for switching on the zone you
have to press "On“ (F2).
If only one zone shall be switched the line
"to zone“ can be missed and F2/F3 (on/off) can be
pressed immediately.
If single detectors shall be switched you have to type
“Detect.” (F4) after the zone has been confirmed (do
not use F2/F3 (on/off) in this case) Jump to Menu
02.2
02.2
Zone 0005 Status
from detector : 1 normal
evt. individual detector text
to detector : 3 normal
evt. individual detector text
Cancel On Off
Switching on/off: Addressable detectors
The first line of the LC module shows the zone where
the detectors are located (here : 5).
It is possible just to switch off only one detector as
well as several detectors. Please type the detector
number and confirm by “OK”.
"Status“ means the current status of the detector (e.g.
normal condition, alarm condition, fault condition). If a
individual detector text has been configured, this text
will be displayed right below the detector line after
pressing “OK”.
For switching off you have to press "Off“ (F3) or for
switching on you have to press "On“ (F2).
If only one detector shall be switched the line "to
detector“ can be missed and F2/F3 (on/off) can be
pressed immediately.
02.3
Switch on/off
from output : 001 normal
to output :
↓+1 ↑-1 Selection -> +10 <- -10
>001 Output 001 Main processor
002 Output 002 Main processor
003 Output 003 Main processor
Cancel On Off Enter
Switching on/off: OC-Outputs
Here the 8 OC-outputs on the main processor board
of the FCP "Solution F2” as well as the 9 OC-outputs
on the F2 io extension can be switched on/off.
Outputs 1 – 8 : OC- Outputs on main board
Outputs 9 – 17 : OC- Outputs on I/O extension
To switch on/off the outputs there are two possibilities
you can choose :
a)To type the output no. directly by the keypad and
confirming with "OK“. Please use the line “from
output” and “to output” for this.
b)Select the outputs by using the cursor keys
↓
and
↑
(means 1 line up or 1 line down) or the cursor
keys and (means 10 lines down or 10 lines
up) and confirm the output numbers with "Enter“
(F4) or “Ok”.
The actual "status“of the output (e.g. normal condition
or active) will be displayed behind the number.
After selecting the output / outputs you have to switch
them by pressing F3 („off“) or F2 („on“).

NSC Sicherheitstechnik GmbH 11/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
02.4
Switch on/off
from relay : 001 normal
to relay :
↓+1 ↑-1 Selection -> +10 <- -10
>001 Relay 001 Main processor
002 Relay 002 Main processor
003 Relay 003 Main processor
Cancel On Off Enter
Switching on/off: 6 internal relays
Here the 6 internal relays can be switched on/off.
Relay 1 – 3 : Relais on main board
Relay 4 – 6 : Relais on I/O extension
To switch on/off the relays there are two possibilities
you can choose :
a)To type the relay no. directly by the keypad and
confirming with "OK“. Please use the line “from
relay” and “to relay” for this.
b)Select the relays by using the cursor keys
↓
and
↑
(means 1 line up or 1 line down) or the cursor keys
and (means 10 lines down or 10 lines up)
and confirm the relay numbers with "Enter“ (F4) or
“OK”. Then press "Enter“ (F4) to confirm the
switching.
The actual „status“of the relay (e.g. normal condition
or active) will be displayed behind the number.
After selection the relay / relays you have to switch
them by pressing F3 ("off“) or F2 ("on“).
02.5
Switch on/off
from power output : 001 normal
to power output :
↓+1 ↑-1 Selection -> +10 <- -10
>001 Power Output 001 Main processor
002 Power Output 002 Main processor
003 Power Output 003 Main processor
Cancel On Off Enter
Switching on/off: 4 internal power outputs
Here the 4 internal power outputs can be switched
on/off.
Power output 1 – 2 : Power output on main board
Power output 3 – 4 : Power output on I/O extension
To switch on/off the relays there are two possibilities
you can choose :
a)To type the power output no. directly by the
keypad and confirming with "OK“. Please use the
line “from power output” and “to power output” for
this.
b)Select the power outputs by using the cursor keys
↓
and
↑
(means 1 line up or 1 line down) or the
cursor keys and (means 10 lines down or
10 lines up) and confirm the power output
numbers with "Enter“ (F4) or “OK”.
The actual "status“of the power output (e.g. normal
condition, fault or active) will be displayed behind the
number.
After selection the power output / power outputs you
have to switch them by pressing F3 ("off“) or F2
("on“).
02.6
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.
Dev.
3. Relay
7. Delay
4. Power Output 8. Fire Outputs
Cancel off
"External sounders/strobes" are all power outputs,
relays and outputs, which are configured to
switching function „on/off like sounders“.
Switching on/off: sounders / strobes
After selecting this function in the switch on/off main
menu you see at the bottom line of the LCD „off“
(F3) or „on“ (F2).
By pressing F3 all sounders / strobes will be switched
off continuously.
Pay attention :
By the function (F3) all sounders and strobes will
be switched off continuously. If another alarm

NSC Sicherheitstechnik GmbH 12/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
Also all loopsounders belong to the external
sounders.
comes in the sounders / strobes will not be
activated again until they are switched on again.
02.7
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.Dev.
3. Relay
7. Delay
4. Power Output 8. Fire Outputs
Cancel off
"Transmission devices" are all power outputs, relays
and outputs, which are configured to switching
function „on/off like transmission device“.
Switching on/off: Alarm Transmission Device
(TD)
After selecting this function in the switch on/off main
menu you see at the bottom line of the LCD "off“
(F3) or "on“ (F2).
By pressing F3 the Alarm transmission device will be
switched off continuously.
The current status of the TD will additionally
indicated by the yellow LED on the control panel.
02.8
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output
6. Alarm Trans.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel on
Switching on/off: Alarm transmission delay
Here the delay of the alarm transmission device of the
FCP „Solution F2” can be switched on/off.
After selecting this function you see at the bottom line
of the LCD "off“ (F3) or "on“ (F2). “On” means to
activate the delay (Day Mode)
The current status of the delay will be additionally
indicated by the green LEDs (Delay, No Delay) on
the control panel.
When the delay is activated there is an additional
indication in the LC module (“Delay activated”)
Pay attention :
To switch on the delay of the alarm transmission
device is only possible if “Response time” and
“Inspection time” are configured. This can only be
done by the installer company.
02.9
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output
6. Alarm Trans.Dev.
3. Relay
7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: Fire protection outputs
This function disables all outputs which have been
configured to "switch on/off like fire protection
outputs".
This disablement only is possible in case of no
alarm.
After selecting this function you see at the bottom line
of the LCD "off“ (F3) or "on“ (F2).
Pay attention :
By the function (F3) all fire outputs will be switched
off continuously. If an alarm comes in no output will
be activated.
03
Alarmcounter
FCP - Alarm : 0025
Testalarm : 0011
cancel
Alarmcounter
It is a 4 digit number (1 – 9999).
Testalarms (Detector test/revision) will be displayed
by a seperate counter.

NSC Sicherheitstechnik GmbH 13/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
04
End user
old access code : 0000
new access code : 3528
new access code : 3528
Cancel
Changing the end user access code
First you have to type the old access code, then you
have to type two times the new access code.
Every line has to be confirmed with „OK“.
Example left side : old access code 0000 is replaced
by new access code 3528.
05
Diagnosis
1. Event memory 5
. Power Outputs
2. Detector data 6. Inputs
3. Internal Modules 7. FCP data
4. Voltages
Cancel Enter
Diagnosis Menu
1. To display the event memory on the LCD.
The youngest message will be displayed
first. Jump to Menu 06
2. To analyse the zones and detector data. A
list of all zones with detectors will be
displayed. You can investigate in the
details Jump to Menu 07
3. A list with possible types of internal
modules (PCBs) will be displayed Jump
to Menu 08
4. A list will be displayed with real time
measurements of power supply voltage
and earth fault voltages. You can check
power supply and earth fault messages here
Example in Picture 09
5. A list will be displayed with real time
measurements of the monitored power
outputs. You can check fault messages
here Example in Picture 10
6. A list will be displayed with real time
measurements of the all monitored inputs.
You can check fault messages here
Example in Picture 11
7. To display FCP Software version and
Serial no. Example in Picture 12
06
Event memory
Message 0001 of 0391
Fault
Power output 001 wire break
08-07-2007 18:25:22
Cancel Filter print
Event memory
The last message (the youngest) is shown first in the
upper area of the LC module. In the last but one line
of the LCD data and time of the message are shown.
This is the time when the event has appeared.
You can scroll with the cursor keys up and down the
messages :
↓and ↑: 1 line up or 1 line down
und : 10 lines down or 10 lines up
By pressing F2 („Filter“) Jump to Menu 06.1
By pressing F3 („print“) Jump to Menu 06.2
06.1
Filter
1. Alarm x 5. Off -
2. Pre alarm x 6. Activation -
3. Test alarm -
4. Fault -
Cancel on
Event memory: "Filter“
The FCP Solution F2 saves all messages in its event
memory.
This filter functions allows displaying only certain kind
of messages in the LC module (e.g. only alarm
messages).
There are 6 different kinds of messages, which can
be displayed in the LC module. If a message is
marked with "x“ this message will be displayed. If it is

NSC Sicherheitstechnik GmbH 14/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
marked with "-" this message will not be displayed.
You can switch from "x“ to "-“ by push button F3
(“off”) and from “-“ to “x” by push button F2 (“on”).
The example on the left side shows only alarm and
pre alarm messages but all other kind of message
are hidden.
06.2
Event memory
from message :
to message :
Cancel print
Event memory: "Printing“
Please type the number of messages and confirm
every line by "OK“: The last (youngest) message is
message no. 1 and the oldest one is message no.
1034.
After selecting the messages press F4 ("print“) for
printing.
The print goes out through the interface which is
selected by menu "Settings 2“ -> "2. Interfaces“ ->
"Protocol" -> "Printer".
07
Zone | existing | config.
> 0001 | 010 | 010
0002 | 010 | 010
0003 |
011 | 107
0004 | 003 | 127
0005 | 010 | 010
0006 | 021 | 117
Cancel Segment Details
Segment | existing | Current
> 01 |
024 | 008,4mA
02 | 031 | 010,9mA
| |
| |
| |
| |
Cancel Zone Details
Detector data
Here the zones which contain at least one detector
are listed line by line (left column).
The middle column shows the number of detectors
which were found during last loop scanning.
The right column "config.“ shows the number of
detectors which were configured by configuration
software.
Ideally the numbers in the middle and right
columns should be identical.
By pressing key F3 "Segment", the display will
change to a list of segments with number of
connected devices and current on each segment.
Please select with the cursor keys the zone/segment
which should be investigated more detailed and press
„Details“ (F4) Jump to Menu 07.1
07.1
Zone 0003 Detect. 002/010
No. |Type |Seg.|Add|Status
001|Conv. mo. CHQ_MZ|01:o|001|Normal
>002|Flashl.
CHQ_AB|01:o|002|Normal
003|Ion. det.
AIE_E |01:o|003|Normal
004|opt. det. ALG_E |01:o|004|Normal
005|Conv. mo.
CHQ_Z |01:o|005|Normal
Cancel existing Details
Table of detectors
The first line of the LC module shows zone and
number of the detector which is marked by ">“ in the
left column of the display area. Here in this example it
is zone 0003 and detector 002 of 10 detectors in
this zone at all.
The second column shows all configured detectors of
this zone by name (abbreviated), doesn’t matter if
they are connected to the panel or not. If you want to
see only the connected detectors of this zone press
"existing“ (F2).
In this case the bottom line changes and "config.“ is
written above F2. Additionally the number of
detectors in line 1 will change, if there is a difference
between connected and configured detectors for this
zone.
Pressing F2 again will show all configured detectors
again.
One detector is shown per line. The grey line have the
following meanings :

NSC Sicherheitstechnik GmbH 15/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
No. :Detector number within the displayed zone
Type : Kind of detector, e.g. optical, MCP etc. This
information is automatically transmitted by the
detectors to the FCP.
The meanings of the abbreviations are :
1. Hochiki ESP
opt. det. ALG-E
opt. det. ALG-EN Optical smoke detector
Ion. det. AIE-E Ionisation smoke detect.
Heat det. ATG-E Heat detector
Multisen. ACA-E Multisensor
Multisen. ACB-E Multisensor Heat
MCP. CHQ-CP
MCP HCP-E Manual Call Point
Sound.mo. CHQ-BS Base Sounder
Sound.mo. YBO-BS Base Sounder
Sound.mo. YBO-BSB Base Sounder / Beacon
Sound.mo. CHQ-WS Wall Sounder
Sound.mo. CHQ-WS2 Wall Sounder
Sound.mo. CHQ-WSB Wall Sounder / Beacon
Sound.mo. CHQ-DSC 2 ch. Sounder output
module
Input mo. CHQ-SIM 1 ch. Input module
Input mo. CHQ-DIM 2 ch. Input module
Conv. mo.CHQ-SIM 1 ch. conventional Zone
monitor
Conv. mo.CHQ-DZM 2 ch. conventional Zone
monitor
I/O mo. CHQ_MRC Mians Relay Switching
module
I/O mo. CHQ-DRC 2 Relaiy Input-/output
module
I/O mo. CHQ-FIO 8 ch. Input-/output
module
I/O mo. NT-FIO monitoring module for
separate NSC powe
supplys
Flashl. CHQ-AB Addressable strobe
Remote CHQ-ARI Addressable remote ind.
Add.Base YCA_3H2 Addressable base
Add.Base YCA_5H2 Addressable base
Outp-Mod. CHQ-POM Power Output Module
Outp-Mod. YBO-POM Power Output Base
STRATOS ASD loop module of Startos
Aspirating Smoke
Detector
2. Apollo Discovery/XP95/Xplorer
opt. det. DISCOV. Optical smoke detector
Ion. det. DISCOV. Ionisation smoke detect.
CO detect.DISCOV. Co detector
Heat det. DISCOV. Heat detector
Multisen. DISCOV. Multisensor
CO/Heat DISCOV. Multisensor CO / Heat
MCP DISCOV. Manual Call Point
opt. det. XP95 Optical smoke detector
Ion. Det. XP95 Ionisation smoke detect.
Heat det. XP95 Heat detector
H.Thermo. XP95 Heat detector high
temperatur
Multisen. XP95 Multisensor

NSC Sicherheitstechnik GmbH 16/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
MCP XP95 Manual Call Point
Sounderm. XP95 Sounder output module
Inp.mod. XP95 Input module
Zone mod. XP95 Conventional module
Inp/Outp. XP95 Input-/output module
Flame det. XP95 Flame detector
Beam XP95 Beam detector
Ref.Beam XP95 Beam detector with
reflector
opt. det. XPlorer Optical smoke detector
Heat det. XPlorer Heat detector
H.Thermo. XPlorer Heat detector high
temperatur
opt. det. S90 Optical smoke detector
Ion. det. S90 Ionisation smoke detect.
Heat det. S90 Heat detector
MCP S90 Manual Call Point
Inp.mod. S90 Input module
Inp/Outp. S90 Input-/output module
Sounderm. S90 Sounder output module
Seg. : Segment = Section of addresses with a
maximum of 254 Hochiki detectors,
modules / base sounders and a maximum
of 126 Apollo detectors, modules.
The segments are partitioned according this list :
•Loop 1 Main board: Segment 1
•Loop 2 Loop extension: Segment 2
o
: This is a symbol for a loop.
-
: This is a symbol for a stub line.
Adr. : Detector address (physical address stored
in the detector)
Status : Current status of the detector (e.g. normal
condition, alarm condition, fault condition,
disabled condition)
By pressing F4 („Details“) it is possible to display
more details of the detectors. That means analogue
values, dust contamination, input bits and so on.
.
Jump to Picture 07.2 for Manual Call Points
Jump to Picture 07.3 for optical smoke detector
07.2
0001/001 MCP CHQ-CP
Configured detector text
1 2 3 4 5 6 7 8
Inputs |0| | | | | | | |
Outputs |0| | | | | | | |
Fault : missing
Cancel
Example of detector data: MCP
The input bits display the status of the alarm contact
of the MCP or - in case of input modules - the status
of the input bits of the module (high / low).
The “Output” bits show – in case of output modules –
which outputs are active or in fault condition.
Following status are possible:
•0 = inactive
•1 = active
•x = reset
•= open curcuit
•S = short curcuit
•U = undefined
The last but one line shows any additional fault
information if the detector/module is not in normal
condition (here: fault because detector is missing).

NSC Sicherheitstechnik GmbH 17/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
Leaving the menu by pressing F1 ("Cancel“).
07.3
Hochiki ESP
0002/001 opt. det. ALG-
E
Configured detector text
A-Value ████████ 0,8%/m
Pre alarm███████████████ 2,7%/m
Alarm
█████████████████ 3,4%/m
Cancel Calib. Details
Apollo
0002/001 o
pt. det. XP95
Configured detector text
A-Value █████ 025
Pre alarm ██████████ 045
Alarm ████████████ 055
Cancel Compens.
Details
For detector series "XP95", "Xplorer" and "S90"
there is an automatic threshold compensation
implemented. If the analogue value for optical
smoke detectors or ionisation smoke detectors is
higher than 40 or lower than 9 for several hours, the
panel will display a pollution fault message.
Example of detector data: Optical smoke
detector
The FCP displays the current values of the detector
as horizontal bar charts. The meanings of the bars
are :
•Analogue value (measured in detector
chamber)
•Pre alarm threshold
•Alarm threshold
The percentage values on the right relates to the bar
charts.
The Pre alarm/alarm threshold depend on
a) the detector sensitivity which can be
adjusted
b) the mode if the detector is a multi sensor
Only for Hochiki ESP
The push button „Calib“ration (F3) can be used to
calibrate an optical smoke detector or a multi sensor
manually. This will be done by the panel usually
automatically once a day (see Settings -> System
settings -> Parameter 12). That means usually this is
not necessary to do manually except :
1. after replacing a detector and if the fault
message "Calibration fault" appears.
2. if after the daily automatic calibration the
fault message "Calibration fault" appears.
The manual calibration process needs about 20 sec.
If in the second case the fault message does not
disappear the detector has to be replaced.
The push button „Details“ (F4) shows the result of
the last calibration of the detector Jump to Picture
07.4
.
Only for Apollo
By pressing „Compens.“ation (F3) an automatic
smoke detector (Optical, Multi) can be readjusted
manually. This should be done, if a polluted detector
will be changed by a new one. By compensating the
detector the drift value (Discovery) or the alarm
threshold (XP95, XPlorer) will be reset. Without
manual compensation the FCP will adjust these
values automatically but this process may last several
hours..
The push button „Details“ (F4) shows more
information for Apollo Discovery detectorsJump to
Picture 07.4.
07.4
Only for Hochiki ESP
0002/001 opt. det. ALG-
E
029 094 156 232
| | | |
______|______ ______|_____
Zeropoint Firepoint
Only for Hochiki ESP
Example of „Zeropoint“ and „Firepoint“
display
Zeropoint = quiescent analogue value
(9-109 depending on detector type)

NSC Sicherheitstechnik GmbH 18/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
61 190
Cancel
0002/001 Multisen ALG-
E
029 094 156 232
| | | |
______|______ ______|_____
Zeropoint Firepoint
61 190
Cancel
0002/001 Ion det. ACA-
E
008 110 138 246
| | | |
______|______ ______|_____
Zeropoint Firepoint
61 190
Cancel
Only for Apollo Discovery
0002/001 opt. det. DISCOV.
Date of manufact. : 04/05
Pollution : 16
Sensitivity : 3
Last revision : -
Det.LED flash at poll. : 0
cancel
Firepoint = testalarm threshold
(139-246 depending on detector type)
Out of these two values the actual smoke density and
the alarm thresholds will be calculated. (s. picture
28).
By calibrating the detector the smoke density will be
set to 0 and the alarmthresholds will be readjusted.
The zeropoint represents the pollution of the detector.
In the bar charts on the left hand the limits and the
standard values for the different detector types are
demonstrated.
A pollution fault will be generated automatically
at the following smoke densities::
opt. det. ALG-
E
+- 1,1 %/m
Multisen ALG-
E
+- 1,1 %/m
Ion det. ACA-
E
+- 0,17%/m
Only for Apollo Discovery
The Apollo "Discovery" series has the ability to store
data in the flash memory of the detector itself. These
data remains in memory even if the detector will be
removed from the base. The reading and transmitting
of the data will last about 1-2 seconds.Therefore you
have a short delay before first value will be displayed.
The following data is aavailable:
- date of manufacture of the detector in format
MM/JJ
- pollution in the range 0-31.
•16 = clean air value
•<=3 and 31 = pollution fault
•0 = fault with analogue value 4
- sensitivity 1-5
- date of last revision in format MM/JJ. If no revision
alarm has been activated for this detector a "-".will
be displayed.
- detector LED at polling
•1 = LED flashes, if detector is polled.
•0 = LED off, if detector is polled
this function can be set by system-parameter 8

NSC Sicherheitstechnik GmbH 19/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
08
Hardware modules
1. Loop module HOCHIKI ESP : 01
2. Loop module Apollo XP/DISCOV
: 00
3. Input-/output extension : 00
↓
4. RS 485 Extension
Cancel Details
Cursor key „↓“ show more :
5. Modem : 00
7. RS 485 Devices : 00
Hardware modules: Overview
Here all possible types of internal modules are listed
and behind them you can see how many numbers of
modules are installed in the FCP (here: only loop
module Hochiki ESP).
These types of modules are possible (depending on
software version) :
Loop module supporting Hochiki ESP
detectors
Loop module supporting Apollo
XP95/Discovery detectors
Input- / Output extension
RS485 extension
Telephone modem for software configuration
Connected RS485 Devices
Please select with the cursor keys the module which
should be investigated more detailed and press
„Details“ (F4) Jump to 08.1
08.1
Hardware
modules
01/02
>01 Detector module
HOCHIKI ESP
02 Detector module
HOCHIKI ESP
Cancel Details
Internal Modules: Details
Here only the really existing modules will be
displayed.
Detector module 1 represents the loop on the main
board, Detector module 2 the loop extension PCB..
Please select with the cursor keys the module which
should be investigated more detailed and press
„Details“ (F4) Jump to 08.2
08.2
Detector
modul HOCHIKI ESP
Segment : 1
Loop: Yes , Normal
ML 1: ON U = 34,9 V
ML 2: OFF U = 34,9 V
Current Seg. 1 = 038,2 mA [100mA]
R+/- (015,7/014,1) = 029,8 ohm[999ohm]
Cancel
Example of details of Hochiki ESP detector
module
Display of the loop state: Recognition as Loop
or Spurs, open- or shortcircuit faults, state of
line 1 anfd line 2 outputs.
Furthermore voltage and resistor values of the
loop will be shown.
08.3
Modem
Call accept off
Cancel hang up
Modem data
If a telephone modem has been installed on the main
board, this menu displays the following information :
Line 2: Product code
Line 3: Firmware version
Line 4: Modem version
Line 5: Country code (FD=Europe)
Line 6: Version of "Data pump"
In line 7 the actual modem status will be displayed.
The modem only accepts an incoming call, if the
automatic call acceptance has been activated in the
installer menu Menü 39 or the system parameter
"ccAll accept after restart" is activated.
Possible messages are:
•Call acceptance on
•Call acceptance off
•RING (of other modem)

NSC Sicherheitstechnik GmbH 20/47 2011 / 04 / 26
Eckendorfer Str. 125 c Installation Manual Solution F2 20110509.doc
33609 Bielefeld Version S031A01.01
•CONNECT 33600 (Connection to other modem
established)
•NO CARRIER (Connection terminated)
You can cancel a connection by pressing F3 „hang
up“.
08.4
Internal Modules 01/63
>01 FRP with FBC A B
02 Remote LCD Panel A
03 Remote LCD Panel A
04 FRP A B
05 -
06 -
Cancel Details
Display of FRP/LCD Panel
Different protocol can be set to each serial interface
of the FCP. (s. menu 38.1).
On all interfaces set to "FRP protocol" connected
devices will be scanned. The address range for these
devices is 1-63.
The device types will be shown as text.
Folowing devices are available:
FRP
FRP with FBC
Remote LCD Panel
LED Panel
PC Managementsystem
By characters "A" and "B" will be signalised, on which
channels a device has been connected.
For further informations please press „Details“ (F4)
jump to menu 8.5
08.5
FRP with FBC
Softwareversion : S150A01.01
24V 1 : OK
24V 2 : Fault
FBC : OK
Checksum : OK
Restart : OK
zurück
Example of details of a fire brigade repeater
panel with fire brigade control panel
In case of a fault of a RS485 device this menu
gives a hint about fault reason. In this example
24V supply voltage on input 2 of the FRP is
missing.
09
Voltages
Charging voltage nominal: 27,66 V
Charging voltage actual : 27,57 V
Battery voltage : 27,48 V
Earth fault voltage : 1,42 V
Ri-Battery : 00,55 Ohm
Cancel
Example of power supply voltages
The charging voltage should be in between 27,3V and
27,6V (20°C). This should be checked by voltage
meter.
The earth fault voltage normally has a value between
9 V and 17,5V. In case of an earth fault you can see
here, i fit is an earth fault against plus oder minus
potential.
Mit F1 ("zurück") Rücksprung aus dem Menü.
10
Power outputs
No.: Vot. Th.SC R-Act. Th.OC(Cal.)
1 : 2,42V 0741< 1008 <1108 (1008)Ohm
2 : 2,39V 0734< 1000 <1095 (0995)Ohm
3 : 4,70V 0838< 1958 >1383 (1283)Ohm
4 : 0,02V 0975>0008 <1475 (1375)Ohm
cancel
Example of power output voltages
The voltage and the measured resistance for each
power output will be displayed, furthermore the
thresolds for open- and shortcircuit.
The samploe on the left side shows an open circuit
for line 3 and an short circuit for line 4.
Leaving the menu by pressing F1 („Cancel“).
Table of contents
Other NSC Sicherheitstechnik Control Panel manuals