
Page
5
detectors that form a fire zone. One or more
smoke detectors can be connection to a detector
group. The smoke detectors in a group are
indicated with a star to the right of the menu. A
smoke detector can be assigned to more than
one detector group if required. When you close
the menu, a message tells you the number of
smoke detectors in this group. The external
input of the KSUB is always connected to
detector 1 for each KSUB. This means that
external fire alarm systems connected to a
KSUB can also be included in a particular
detector group. The fire alarm input of the
KSUA always takes precedence and can be
thought of as belonging to all detector groups.
The fan control is configured next. FAN 1 is
the same as Relay 1 in the description. Relay 1
is intended for the ventilation system. Relay 2
can be used for another ventilation system,
heater batteries or smoke extraction fans. An
important part of the configuration process is
defining what is to happen when a smoke
detector group is triggered. If a detector group
is considered to be critical, the entire system
must switch to fire mode, which means that the
ventilation system is stopped, all ventilation
dampers are closed, the evacuation dampers are
opened and a smoke extraction fan is started. In
a non-critical group, only the dampers within
the group are affected if a smoke detector is
triggered. Detector groups are defined as
critical in Stop/DetGrps in the menu.
The fan output of the KSUB can be used if
there are a number of small ventilation systems
in the installation, and you want them to be
controlled by the relevant detector group. The
output is hard coded so that detector group 1 is
connected to KSUB address 0. Detector group
2 is connected to KSUB address 1, etc. up to
detector group 12.
The KSUB fan relay output is dependent on the
Relay 1 configuration in the KSUA. If you
want the fans connected via the KSUB to stay
on during the damper exercises until the
relevant damper closes, set Stop/Test to OFF in
the Relay 1 menu. Other functions are also
dependent on the settings in the Relay 1 menu.
Inputs
Modbus / RJ45
The contact is standard for Modbus RTU and
contains outputs for +5V on pin 7 and 0V on
pin 8. A is on pin 5 and B is on pin 4. +5V can
be loaded with up to 100 mA resistive load.
The contact for Modbus over TCP/IP is on the
left side of the box. (TCP/IP is an optional
extra)
MBUS, SBUS
These are connections for Modbus and SBus
respectively. The SBus connection goes to the
slave units.
Forced opening
If the input is closed, the dampers will move to
the open position. All other functions are
disabled. It is possible to define whether the
fans will be on or off.
Alarm
This input is used to connect to a central fire
alarm system. If 9-10 is open the entire system
switches to critical mode. Ventilation systems,
etc. are stopped immediately, the dampers are
switched off and any smoke extraction fans are
started. Normally manual resets are necessary.
In menu 19 it could be changed to automatic
reset.
Night mode
The night mode input is activated when 11-12
is open. What happens next is that any heater
battery and the ventilation system are stopped
with the delays defined during configuration.
The open dampers are closed. If there are
evacuation dampers (pressure relief dampers),
they are not affected.
Outputs
Relay outputs
All relays are shown in the open position. FAN
1 is normally activated. The state of FAN 2
depends on the configuration.