Haes ESENTO ESEN-8MAR Guide

Installation, Commissioning &
Operating Manual
MARINE APPROVED 8 - 12 ZONE CONVENTIONAL
CONTROL PANEL
Approved Document UI-ESEN12MAR-01 Issue 8.0
MED Ref: 0832/15

IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualied and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
This re alarm system requires periodic checks as specied in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this re alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specications at our discretion and without prior notice. E & O E.
IMPORTANT SAFETY NOTES
Haes Technologies Ltd, Unit 3 Horton Industrial Park, West Drayton, UB7 8JD
ATTENTION
Model Number MED Ref No.
Esento Marine 8 zone conventional panel ESEN-8MAR 0832-MED-1086
Esento Marine 12 zone conventional panel ESEN-12MAR 0832-MED-1086
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for re detection and re alarm systems for buildings.
Provided Options (with requirements):
Output to re alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for re detection and re alarm systems for buildings.
European Standard BS IEC60092-504 : 2001
Electrical installations in ships, special features, control and instrumentation.
European Standard BS IEC60533 : 1999
Electrical and electronic installations in ships, electromagnetic compatibility.

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
1
CONTENTS
Page
ABOUT THIS PANEL 2
PRODUCT OVERVIEW 2
CABINET DETAILS 3
CIRCUIT BOARDS 4
MAIN PCB TERMINALS 6
ZONE CARD TERMINALS 7
TECHNICAL SPECIFICATION 8
POWER SUPPLY MODULE 9
DESIGN CONSIDERATIONS 10
GENERAL DETECTION CIRCUIT SCHEMATIC 10
GENERAL SOUNDER CIRCUIT SCHEMATIC 11
INSTALLATION 12
SAFETY 12
ESD PRECAUTIONS 13
GENERAL 13
MOUNTING THE CABINET 13
MAINS CONNECTIONS 14
CONNECTING THE BATTERIES 15
SETUP & PROGRAMMING 16
NETWORK PANELS SETUP 16
LEVEL 3 ENGINEERING MODE 18
LEVEL 3 ENGINEERING OPTIONS INDEX 19
OPERATING 48
PANEL CONTROLS & INDICATIONS 48
DISABLE MODE 50
TEST MODE 51
FAULT DIAGNOSIS 52
FUNCTIONALITY DURING A SYSTEM FAULT 53
SERVICE & MAINTENANCE 54
DUTIES OF THE RESPONSIBLE PERSON 54
ROUTINE MAINTENANCE & TESTING 54
SCHEDULE OF TESTING LOG BOOK 56
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK 60
USER INSTRUCTIONS 63

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The Esento Marine 8 to 12 zone is a conventional control panel with integral power supply & space for
standby batteries.
Esento Marine panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm
Systems – Control & Indicating Equipment.
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
An eight button keypad is used to control the system and allow access to the function options. The three
main buttons, ‘RESOUND’ (red), ‘SILENCE’ (blue) and ‘RESET’ (green) being much larger and colour
coded to assist the end users.
Eight or twelve re zone circuits are provided plus four monitored sounder circuits. Fire & fault VFCO
relays, re & fault switched negative outputs, class change and an alert input are also included.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiesecent and alarm current details for standby battery calculations
Models Standby Current Alarm Current
ESEN-8MAR 139mA 220mA
ESEN-12MAR 182mA 267mA
TPCA04-S 4 zone ext card, standard 43mA 47mA
TPCA04-H 4 zone ext card, high spec 49mA 87mA
TPCA05 comms card 5.2mA N/A

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
3
ABOUT THIS PANEL
CABINET
60mm 85mm
310mm
455mm
300mm
450mm
Fire Detection System

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
4
ABOUT THIS PANEL
CIRCUIT BOARDS
Esento Marine 8-12 panels comprise of two main circuit boards plus optional ancillary boards
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3 4 5 6
ON
1 2 3 4 ENTER
RESOUND SILENCE RESET
TPCA01-X2MAR/X4MAR - Master PCB
TPCA03 - LED Display & Controls PCB

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
5
ABOUT THIS PANEL
ANCILLARY CIRCUIT BOARDS
+ - + - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1 2 3 4 5 6
1 2 3 4
ON
ADDRESS
+ - + - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
+ -- - + -
OPA OPB AUX SNDR A SNDR B
CNO
TPCA04-S - Std spec 4 zone extension card
TPCA05 - Comms PCB
TPCA04-H - High spec 4 zone extension card
• 4 x conventional zone circuits.
• Piggy backs on Main PCB for
connection to network & repeater
panels
• 6 programmable switch -ve outputs
• 4 x conventional zone circuits.
• 2 x switched -ve outputs
• 1 x Aux relay output
• 2 x monitored sounder circuits

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
6
ABOUT THIS PANEL
MAIN PCB TERMINALS
28v output fused @ 500mA
28v input for power supply
Temperature compensation voltage control link
Commmon re VFCO relay
unfused. Max 3A @ 30vdc
Commmon fault VFCO relay
maintained (fail safe)unfused.
Max 3A @ 30vdc
Programmable O/P
Programmable O/P
Alert (pulses sounders)
Precint/class change (activates sounders)
Switched -ve inputs
Switched -ve outputs
Max load 40mA
To 0 volts
Relay Coil
Conventional monitored
sounder circuits, fused @ 500mA
Conventional re zone circuits, fused @ 500mA
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3 4 5 6
ON

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
7
ABOUT THIS PANEL
ZONE CARD TERMINALS
+ -
+ -- - + -
+ - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
OPA OPB AUX SNDR A SNDR B
CNO
Conventionalre zone circuits,
fused @ 500mA
Relay Coil
Relay Coil
Programmable O/P
Programmable O/P
Programmable relay O/P unfused.
Max 3A @ 30vdc
28v
28v
Switched -ve outputs
Max load 40mA
Conventional monitored
sounder circuits, fused @ 500mA
Drawing shows the high spec version of the
zone extension PCB (TPCA04-H).
The std version does not contain the additional
outputs or sounder circuits shown at the
bottom.

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
8
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specication Inputs & Outputs - TPCA01-X2/X4 Main PCB
Terminal capacity 0.5mm2 to 2.5mm2solid or stranded wire.
PSU @ output Power supply voltage control line. For temperature compensation control.
PSU Input + - 28vdc supply input. Diode protected for
reversal and independent short circuit.
Max current 3 amps.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
28v+, 0v- power output 28vdc supply output for re alarm
accessory relays etc. Max continuous
use = 400mA.
Fused @ 500mA. Fuse = 500mA
resettable fuse.
Common re relay Fire relay contact. Clean C/O.
Max 3A @ 30vdc.
Unfused
Common fault relay Maintained fault relay contact. Clean C/O
Max 3A @ 30vdc.
Unfused
Outputs; FR, FLT Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28vdc. Non
latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6
zener diode.
SNDR 1 - 2 28vdc polarity reversal monitored
sounder outputs to re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Zone 1 - 4 Conventionally wired re alarm zone
circuits. 4K7 Ohm 5% 0.25W EOL
resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases tted
Electrical Specication Inputs & Outputs - TPCA04-S/H zone cards
Terminal capacity 0.5mm2 to 2.5mm2solid or stranded wire.
Zone A - D Conventionally wired re alarm zone
circuits. 4K7 Ohm 5% 0.25W EOL
resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases tted
Programmable outputs OP A & OP B Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Programmable relay ouput Fire relay contact. Clean C/O, C & N/O
Max 3A @ 30vdc.
Unfused
SNDR A - B 28vdc polarity reversal monitored
sounder outputs to re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 2.4A is not
exceeded.
Electrical Specication Inputs & Outputs - TPCA05 comms PCB
Comms A - B RS485 Repeater Comms, fused @ 20mA
28v Supply output Fused @ 500mA
Programmable outputs 1 - 6 Switched -ve outputs Overload voltage protected to 52vdc
Current limited 680R
Max load = 40mA

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
9
ABOUT THIS PANEL
General Specication
Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Cabling Fire resistant screened cable, minimum size 1mm2. Max cable length
1Km (20 Ohm), (max capacitance 1uF, max inductance 1 millihenry).
Temperature range -5 deg C to +55 deg C max RH 95%
Vibration IEC 60068-2-6 Test F
Inclination IEC 60092-501 22.5o
Number of conventional/Twin Wire detection circuits 2 - 12
Detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
POWER SUPPLY MODULE
Power Supply Specication
Mains supply 230vac +10% / -15% 50Hz max current
1.2A
Mains supply fuse 4 Amp (F4A 250V) Not accessible for servicing. Internal to
switch mode power unit
Internal power supply rating 3.0 Amps total including battery charging Maximum load shared between outputs
= 2.4A
Power supply output voltage 21.27 - 29.68vdc Tolerance +/- 0.1%
Max continuous load (ImaxA). Max
continuous load whilst battery charging
is not required (ImaxB).
ImaxA = 610mA ImaxB = ImaxA
Minimum current drawn by panel
(example)
4 Zone
I min = 90mA
12 Zone
I min = 188mA
Maximum ripple 1.0V p-p Supply and charger fault monitored
Min/max battery size and type 2 x 7.0Ah 12volt VRLA
Use Yuasa NP range batteries
Other equivalent batteries may be
used but have not been tested for the
purposes of EN54 approval.
Battery charging voltage 27.3 vdc nominal at 20 deg C Temperature compensated
Battery charging output current 3.0A PSU 1.34A
Current limited 4.7 Ohms
Battery high impedance fault (Batt Hi Z) Resistance = 1 Ohm or greater 1 hour reporting time
Max current drawn from batteries 3.15 Amps with main power source
disconnected. Battery fuse 3.15A LBC
20mm.
V+
V-
E
N
L
24v +ve output
O/P Voltage adjust
(default setting 27v4 at 20oC)
24v -ve output
Earth
Neutral
Live
Mains input
Temperature compensation input
from @ terminal on main PCB

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
10
DESIGN CONSIDERATIONS
GENERAL DETECTION CIRCUIT SCHEMATIC

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
11
DESIGN CONSIDERATIONS
GENERAL SOUNDER CIRCUIT SCHEMATIC
4K7 OHM
END OF LINE
RESISTOR
-
+
SNDR1
MOTORISED BELL
POLARISED
MOTORISED BELL
POLARISED
ELECTRONIC SOUNDER
POLARISED
ELECTRONIC SOUNDER
POLARISED
+VE
+VE
+VE
+VE
-VE
-VE
-VE
-VE

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
12
INSTALLATION
SAFETY
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
used. An article is not regarded as properly used if it is used “without regard to any relevant information or
advice” relating to its use made available by the supplier.
It is assumed that the system, of which this control panel is a part, has been designed by a competent re
alarm system designer in accordance with IMO FSS Code and with regard to BS EN 54 parts 2 and 4 in
the case of control equipment and power supplies. Design drawings should be provided to clearly show
the position of any eld devices and ancillary equipment.
This product should be installed, commissioned and maintained by, or under the supervision of, competent
persons according to good engineering practice and,
(i) Codes of Practice
(ii) Statutory requirements
(iii) Any instructions specically advised by the manufacturer
According to the provisions of the Code you are therefore requested to take such steps as are necessary to
ensure that any appropriate information about this product is made available by you to anyone concerned
with its use.
This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I
construction. As such it must be connected to a protective earthing conductor in the xed wiring of the
installation. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
to the protective earth will render the equipment unsafe.
This equipment must only be installed and maintained by a suitably skilled and technically
competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
These panels are designed to comply with the requirements of EN 54 part 2.
Installation of the panel should only be carried out by qualied personnel. The electronic components
within the panel can be damaged by static charge. Suitable precautions must be taken when handling
circuit boards. Never insert or remove boards or components, or connect cables, with the mains power
on or batteries connected.
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid
down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable EU Council
Directives

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
13
INSTALLATION
ESD PRECAUTION
GENERAL
MOUNTING THE CABINET
Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap,
suitably grounded, should be worn at all times when handling pcbs. These wrist straps are designed to
prevent the build up of static charges, not only within a persons body, but on many other materials.
ESD damage is not always evident immediately, faults can manifest themselves at anytime in the future.
All pcbs should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the
control panel.
Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely
to induce electrical interference. Earth links should be maintained on all system cables and grounded in
the control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be
segregated away from mains voltage.
• Any junction boxes used should be clearly labelled FIRE ALARM.
• Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
• Any coils or solenoids used in the system must be suppressed, to avoid damage to the control
equipment.
The panel is only suitable for mounting in dry control rooms or dry accomodation spaces. The site chosen
for the location of the panel should be clean, dry and not subject to shock or vibration. Damp, salt air or
environments where water ingress or extremes of temperature may affect the panel must be avoided. The
temperature should be in the range -5° to +55°C, and the relative humidity should not exceed 95%.
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to re-
connect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted
level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove
any knockouts and ensure the cabinet is clear of swarf etc prior to retting the PCB. Always ensure that if
a knockout is removed, the hole is lled with a good quality cable gland. Any unused knockouts must be
securely blanked off.
Knockouts should be removed with a sharp tap at the
rim of the knockout using a at 6mm broad bladed
screwdriver.
Use of excessive force will damage the enclosure
around the knockout.

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
14
INSTALLATION
Typical panel layout
Drawing shows typical internal layout of a 12 zone panel with two 7.0Ah, 12v batteries tted
MAINS CONNECTIONS
Do not connect the mains supply to the panel
until you are fully conversant with the layout
and features of the equipment.
A rating plate is attached to the power supply
module describing the nature of the supply
permitted.
The incoming mains supply should be brought
into the panel via one of the knockouts
provided.
A suitable cable gland must be used to secure
the outer sheath of the cable used. The earth
must rst be connected to the primary earth
stud (peg) marked with a symbol, using a
suitable ring crimp.
Sufcient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the
terminal block while leaving the earth connection intact.
V+
V-
E
N
L
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
Low voltage detection and sounder circuit wiringIncoming mains wiring
12V 7.0Ah VRLA BATTERY
12V 7.0Ah VRLA BATTERY
+ - + - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
+ - + - + - + -
ZONE A ZONE B ZONE C ZONE D
1 2 3 4
ON
D
C
B
A
TWIN
+ -- - + -
OPA OPB AUX SNDR A SNDR B
CNO
Filter

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
15
INSTALLATION
CONNECTING THE BATTERIES
BATTERY CHARGING VOLTAGE CHECKS
EARTH FAULT MONITORING
Batteries of even very small capacity are capable of delivering very high currents which can cause re or
injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB.
These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series using the
white jumper lead provided. See diagram.
To optimise the service life of the batteries, the battery
charger output voltage varies with temperature.
N.B.
In the event of mains failure, the battery charger circuit will
protect the batteries from full discharge by disconnecting
them when they reach below 19v. When the mains supply
is restored the batteries will be automatically reconnected.
+ve-ve
12v SLA Battery 12v SLA Battery
+ -
BATTERY
1 2 3
ON
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute
until the monitoring cylce has nished polling. This is normal. If the fault doesn’t clear after 1 minute, check
connections.
For on ship use:- battery retaining clamps must be tted.
The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20oC. This should not normally
require adjustment. Where battery problems are experienced, the following information should be
considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals,
due to intelligent battery controls.
b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries
disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11oC - 40oC.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the
battery voltage, should be 26.8v for a good battery or 22v for a at battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see
page 7), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be
disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 17), which will over
ride the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When
completed, switch off Access Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the
batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
The Marine panels are equipped with earth fault monitoring to the 28v supply rails. Any cable connected
to earth will cause an earth fault to be indicated. The earth fault LED is located internally next to the
program options switch on the main circuit board. If an earth fault exists a PSU Fault (and General Fault)
will be indicated externally. The internal LED will show continuously for earth faults on the -ve polarity
cables and pulse for +ve polarity cables. (Be aware sounder cables monitor in reverse). Identifying the
source of the earth fault requires systematically removing cables until the fault clears. There is a 30
second delay to the earth fault signal to avoid spurious faults due to noise.

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
16
SETUP & PROGRAMMING
NETWORK PANELS SETUP
The system can support up to 8 networked 8-12 zone control panels, 1 x Master and up to 7 x Slaves.
Comms PCB
To run a network, a Comms PCB (TPCA05) must be tted to each control panel.
The Comms PCB ts into the control panel on top of the main circuit board where the ribbon cable from
the display board comms is normally plugged.
To t the Comms PCB, power down the panel, un-plug the display board ribbon cable from the main circuit
board and plug the Comms PCB into the socket instead.
A socket is provided on the top of the Comms PCB to re-connect the display board ribbon cable.
Each panel to be included in the network is dened by setting switch 5 on the 6 way DIL switch located
on the main circuit board.
OFF = Stand Alone mode, ON = Network/Repeater mode.
With this switch in the ON position the panel will automatically recognise & operate the Comms PCB
(TPCA05).
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1 2 3 4 5 6
1 2 3 4
ON
ADDRESS
Disconnect display board ribbon cable
6 way DIL switch
Plug Comms PCB into the socket and
re-connect dispay board ribbon cable to
socket on top of Comms PCB
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
ON = Network/
Repeater mode
1 2 3 4 5 6
ON

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
17
SETUP & PROGRAMMING
Programming
The Master panel will need to be programmed for the number of network panels on the system. See panel
wide programming settings, code 2-1-2-3, option 10, (Set Number of Network Slave Panels on System).
Addressing
Each panel needs to have a unique address. The addressing is done using the 4 DIL switches on each of
the Comms PCBs using binary code values, see diagram below.
The addresses should be set in sequence from 1 - 8, rst slave panel = address 01, second slave panel =
address 02 etc.
The Master panel is dened by being address 00 (all switches off).
Network slave panels and/or repeater panels are designed to be wired in a fault tolerant (fail safe) loop
conguration, from comms A to B and back to the Master panel again (see drawing below). This enables
the network to still function if there is a break in the cables.
If replacing an older system where the existing cabling cannot be congured in a loop as above, it is
possible to change the panel settings to legacy, radial circuit comms monitoring.
See panel wide programming settings, code 2-1-2-3, option 6, (Change Network/Repeater Comms
Monitoring Type).
1 2 3 4
ON
ADD 01
1 2 3 4
ON
ADD 02
1 2 3 4
ON
ADD 03
1 2 3 4
ON
ADD 04
1 2 3 4
ON
ADD 05
1 2 3 4
ON
ADD 06
1 2 3 4
ON
ADD 07
SLAVE PANEL 1
SLAVE PANEL 5 SLAVE PANEL 6 SLAVE PANEL 7
1 2 3 4
ON
ADD 00
MASTER PANEL
SLAVE PANEL 2 SLAVE PANEL 3 SLAVE PANEL 4
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1 2 3 4 5 6
1 2 3 4
ON
ADDRESS
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1 2 3 4 5 6
1 2 3 4
ON
ADDRESS
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1 2 3 4 5 6
1 2 3 4
ON
ADDRESS
Fault Tolerant Loop Wiring
Master Panel Slave/Repeater Panel 1 Slave/Repeater Panel 2

Esento Marine 8-12 Installation, Commissioning & Operating Manual Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
18
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
1 2 3 4 5 6
ON
- + - + - + - + - + -
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
1 2 3 4 5 6
ON
A series of programmable engineering options are available. These
programming modes are initiated by entering a four digit code using
buttons 1 - 4 on the keypad followed by the ENTER button.
1 2 3 4 5 6
ON
P
RESOUND SILENCE RESET
ENTER
1 2 3 4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
To access Level 3 options, rst set switch 6 on the 7 way DIL switch located on the main PCB to the
‘ON’ position. Then activate the controls by turning the key switch or by entering the four digit code (see
Activate Controls in the OPERATING section).
Once the controls are active, the ‘Access Level’ indicator will pulse to signify that Level 3 access is active.
Programming throughout the panel is carried out in a sequence where the re LEDs indicate the options
to set and the fault LEDs indicate the status of these settings.
Generally button 1 is used to scroll the indications (button 3 can also be used to scroll backwards).
Pressing and holding button 1 for 3 seconds at any time will exit the programming mode completely.
N.B.
The panel will automatically save settings & drop out of programming modes if left idle for more than
approximately 30 seconds.
It is possible to review the settings within a programming mode without changing them. Steady Fire LEDs
indicate review mode. To edit a setting rst use button 1 to select the required option, pressing ENTER
enables editing of the option. Flashing re LEDs indicates edit mode and button 2 is used to change the
setting.
Pressing ENTER again will exit ‘edit’ mode back to ‘review’ mode.
Some programming modes are denoted with (EN54!). Where this symbol appears EN54 compliance may
be affected by this setting.
This manual suits for next models
2
Table of contents
Other Haes Control Panel manuals

Haes
Haes AOV Series Guide

Haes
Haes ELAN HS-5000 Series User manual

Haes
Haes MZAOV-1001 Guide

Haes
Haes FCPTEC-HS-4200 Guide

Haes
Haes ESPRIT-G Guide

Haes
Haes Esento Eclipse ECL-2 Guide

Haes
Haes AlarmSense PLUS User manual

Haes
Haes ESENTO MARINE Guide

Haes
Haes Excel-EN Guide

Haes
Haes FUSION 0832-CPD-1431 User manual
Popular Control Panel manuals by other brands

tau
tau D749MA installation guide

QOLSYS
QOLSYS IQ PANEL installation manual

Aprilaire
Aprilaire Zoned Comfort Control 6203 Safety & installation instructions

Context Plus
Context Plus CAST XFP Series user manual

Skov
Skov DOL 234 Panel Technical user guide

Calpeda
Calpeda QMLD 1D 12A-FA Original operating instructions