NT KN303 User manual

( )KN303
USER MANUAL
TEMPERATUTE
CONTROLLER
Neuron Tech
1 2 3 4 5 6 7 8 9 10 11 12 13
16 17 18 19 20 21 22 23 24 25 26 27 28
POWER
DC 8V4
+ -
T/X T/X+ -
AUTO
MAN

CONTENTS
● ---------------------Caution for Safety 2
----------------------8. Example of Wring 10
7. Operation and Setting 8-------------------
6. Name of Each Part 8----------------------
5. Output Operating Diagram 7----------------
4. Feat res 7u -----------------------------
3. Connection Diagram -------- 6------------
2. External Dimension and Panel Cutting Size 5----
1. Specifications 4------------------------
● --------KN 303 TEMPERATURE CONTROLLER 4
-1-

Caution for Safety
WARNING
1.power
1) use it within rated voltage in order to protect equipment and prevent and
prevent trouble.
2) ln order to prevent electric shock and equipment damage when installing
equipment check wiring after finishing wiring and than input power.
3) use standard wiring and terminal for connecting power .this can cause
electric shock and fire.
2.caution for operation
1) lf abnormality of this equipment is related to serious accident, it is
recommended to install protection device in addition.
2) Do not use this equipment in the gas (This is not explosion-proof structure).
If this equipment is exposed to gas do not operate power switch and
so on but operate ane it when it is sage after venting the space.
3) Do not use in the place with chemical materials, There is danger of electric
leakage and electric shock.
4) Do not touch or loosen terminal when there is applied lt can cause electric
shock or mal -operation.
5) Do not touch the product when there is water around or when body is wet.
There is danger of electric shock.
6) Do not install the equipment in the place where children can touch the
equipment.
3. Caution for wiring and maintenance
1) Perform wiring for this equipment exactly into relevant number as show in
the instruction manual or terminal instruction. (Tighten terminal bolt firmly)
mal-wiring can cause equipment damage, mal- operation of fire .
2) Perform repair or assembling after turning off external power switch and
interrupting external circuit power. It can cause electric shock or trouble.
3) Never disassemble reform or repair equipment lt cause electric shock fire
product damage mal-operation or trouble.
Caution for safety, aims at securing safety of user and preventing accident
or danger in advance by using it safely ,so read and follow it well.
Caution matters are divided into ‘warning’ and ‘caution’ whose meanings
are as follows
Violating instruction may cause injury product
damage or material loss.
CAUTION
WARNING Violating instruction may cause serious damage or
death
- 2 -

-3-
CAUTION
1.caution for attachment and wiring
1) Fix the equipment firmly with the fixing device (included during shipment
below and above the equipment when attaching equipment.
2) lf there is severe induction noise in the power ,it is recommended to us
insulation transformer and noise removal circuit.
3) Twisted wiring of power line is effective for noise
4) lf water enters receive checking by all means.
5) Use lead wire which has low resistance is non-combustible.
6) Use output and input signal lines by separation them by all means. Use
shield wire for input signal wire and be away from load or high voltage.
7) Use sensor of non-grounding type.
2.Caution for handling
1) when operation output relay frequently by connecting load without
allowance in rating, relay life can be shorter rating so use it by adding
to outside. *Electric life of relay --About 100.000 times (under rated load)
2) Make each setting exactly and check abnormality in input and output,
3) lf sensor is single or short it is displayed “---”.
turn off voltage by all means when replacing sensor at this time .
It can cause trouble and mal -operation
4) Do not drop this product nor give shock this product. It can cause trouble
or mal-operation
5) Do not wipe the product with organic
solvent lt can cause damage in appearance .
6) Avoid use in the following condition.
: ln the place where surrounding temperature and humidity exceed the
temperature and humidity scope in usage condition.
: ln the place exposed to combustible gas or corrosive gas.
: ln the place where there is much oil water steam iron or salt.
: ln the place which is not waterproof structure exposed to outside water
or rain.
: ln the place directly exposed to direct sunshine.
: ln the place where freezing phenomenon takes due to severe
change of temperature and humidity.
relay
4) Replace sensor after turning off power by all means. Lt can cause electric
shock.
Fire product damage mal-operation or trouble.
5) The components of this equipment have life period and include year -passing
components There is 1 year of guarantee period from purchasing date.
However. Trouble due to customer mistake and natural disaster is excluded.

KN303 DIGITAL TEMPERATURE CONTROLLER
1.Specification
DIMENSION
INPUT MEASURING CYCLE
INPUT
AMBIENT TEMPERATURE & HUMIDITY
MEASURING RANGE
TEMPERATURE INDICATION
OUTPUT CONTACTS CAPACITY
DATA STORAGE
ANALOG OUTPUT
COMMUNICATION
POWER SUPPLY
POWER
CONSUMPTION
DIELECTRIC STRENGTH
INSULATION
RESISTANCE
WEIGHT
100m SEC
+/- ℃(0.5 Full Scale)
- ℃50~250
1℃
10 YEARS
DC 4~20mA (RANGE:0~200 Load Resistance Max 600℃) Ω
SERIAL RS-485 MODBUS RTU (OPTION: RS-232)
(INPUT/OUTPUT ISOLATION)
(INPUT/OUTPUT ISOLATION)
TRIP, ALARM,FAN, FAULT
AC 250V 5A(Resistance Load)
FREE VOLTAGE
DC 48V
7 VA
AC 2000V FOR 1MIN
DC 500V 100M ohm MINIMUM
750g
DC 30V 5A(Resistance Load)
RELAY CONTACT
3 INPUT Pt100 3WIRE(DIN IEC 751)Ω-
OPERATION (-20 TO 60 10 TO 90% RH)℃ /
ACCURACY
115(W)X90.5(H)X72(D)mm
-4-
Free voltage
( DC 48V )
3 sensor input(Pt100Ω)
Program type function
(Setting value)
Temp, max storage function for each channel
Data storage function
Fan auto / manual function
Operation setting function for each channel(run/stop)
caution:”stop”seleced channel is not displayed.
Test function for each input channel
Scan time setting function(2~10 sec)
Outputs delay time setting function
Fan ( 0.1~6.0 sec)
Alarm, Trip ( 0.5~10.0 sec)
Channels scanning
SCAN : ch1-2-3 scanning( 2~9 sec)
AUTO :automatic hottest scanning
MAN :manual function
POWER
AUTO
MAN

2.External Dimension and Mounting
◎External Dimension 단위 :mm
-5-
115mm
96mm
90.5mm
72mm
70.5mm
90.5mm
9mm
115mm
104mm
96mm
72mm
(En50022)
MOUNTING
FOR DIN RAIL
POWER
AUTO
MAN

3. DiagramConnection
◎Connection Diagram
-6-
POWER
NOTE: When the unit is powered the fault relay 12-13 closed
and it opens again in case of fault condition

-7-
4.Features
5. utput Operating DiagramO
OUTPUT SPECIFICATIONS( setting temp)△:
ALARM,TRIP
FAN OUT
FAN ON
ALARM,TRIP ON
FAN OFF
Power input is free voltage (DC 48V) and it is stably
operated even at bad condition such as outside power change,surge etc
Temperature of transformer is measured and displayed and
alarm output (alarm, trip) and fan is controlled according to
temperature.
Temp max function -lt is possible to check the highest
temperature of transformer during operation up to now.
Data storage function memorizes T .MAX value and each control
temperature setting values.(Semieternal) T.MAX value is stored
even after turning power it is reset during operation
Each setting value is also stored after turning off power unless
setting value is changed during operation
.
.
Fan out function -lt is possible to control outside fan by
comparing fan on and fan off setting values and measured
temperature.

(3)Temp. Max
DISPLAY LED
(2)MAN MODE
DISPLAY LED
(1)AUTO MODE
DISPLAY LED
(5)PROGRAM MODE
DISPLAY LED
(4)FAN MANUAL OUTPUT
DISPLAY LED
(6)T MAX CHECK SWITCH.
(7)RESET WITCHS
(8)FAN MANUL ON/OFF SWITCH
(9) ROGRAM M ODE/SETTING SWITCHP
(15)FAN AUTO OUTPUT
DISPLAY LED
(16)ALARM OUTPUT
DISPLAY LED
(17)TRIP OUTPUT
DISPLAY LED
(13)CHANNEL DISPLAY
(18)TEMP&SETTING DISPLAY
(10)DOWN SWITCH
(11)UP SWITCH
(12)MODE/TEST SWITCH
(14)FAULT OUTPUT
DISPLAY LED
6. ame of Each PartN
7. Operating and Setting
FUNCTIONS
OPERATION
KEYS
(3)T.MAX: Monitoring unit shows the highest temperature recorded
by the sensor and the last reset
(4)FAN : AN is automatically controlled by fan on and fan off
setting value
F
(16)ALARM:When the measurement temperature is over ALARM
setting value, ALARM ON
(17)TRIP :When the measurement temperature is over TRIP
setting value, TRIP ON
(8)T.MAX : T.MAX value check key mode only)(SCAN,AUTO,MAN
(8)FAN MAN: FAN peration the button which the ON/OFF
operation with a manual operation.
o
(9)PRG/ENT:
Program setting function key
PROGRAM MODE(“PRG/ENT”key 3 seconds pressing)
(10)DOWN: hen Program setting value change DOWN.W
(11)UP : When Program setting value change UP.
(9)RESET: RESET(In T.MAX MODE)->The current T.MAX
record again
(“RESET” key 3 seconds pressing)
value delete and
- 8 -
AUTO
MAN
(1)AUTO : Control device automatically displays the highest
temperature channel
(2)MAN :Channel temperature manual reading through cursor keys
(12)MODE/TEST: DISPLAY MODE SCAN,AUTO,MAN change key
TEST MODE ey
"MODE/TEST” key 3 seconds pressing)
( )
k
(

PRG ON
PRG ON
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
PRG
ENT
After power supply
The display shows the measurement temperature
Pressing key 3 seconds
*Anywhere in the program by pressing key 3 seconds
or key operation is not longer than 30 seconds
in the measurement mode is changed.
PRG ON led turns on
PRG ON led turns off
" "F onan Setting display
Return to first display
*Measurement mode
" "F oFan f Setting display
"AL Sarm on etting” display
"Tr Sip on etting” display
“ Communication ID setting displayC Idom "
" "FAN ON Setting value changes
" "FAN OFF Setting value changes
" "ALARM ON Setting value changes
" "TRIP ON Setting value changes
" "COM ID Setting ID value changes
Save the changed setting value
Save the changed setting value
Save the changed setting value
Save the changed setting value
Save the changed setting value
Setting manual
-9-
AUTO
MAN

POWER SOURCE
(USER SUPPLY)
1 AC 100~240V
50~60Hz
¢
POWER SOURCE
(USER SUPPLY)
MCCB
MCCB
MC
MC
UVW
R
RS
T
T
3
3
1
12
R1
R1 S1
T1
T1
◎In case of Phase
◎In case of Three Phase
1
2
1
2
5
6
7
8
9
10
11
12
13
5
6
7
8
9
3
4
3
4
10.
11
12
13
16
17
18
19
20
21
22
23
24
25
26
27
28
16
17
18
19
20
21
22
23
24
25
26
27
28
8.Example of Wiring
- 10 -

Neuron Tech
A 303 ,875-1Maesonggosaek-Ro, Gwonseon-Gu,
Suwon-City, Gyeonggi-Do, Korea, 441-230
TEL : +82-31-227-4504 / FAX : +82-31-298-1962
www.neurontech.kr
Table of contents
Popular Controllers manuals by other brands

Johnson Controls
Johnson Controls A28 Series Installation Sheets Manual

Norac
Norac UC4.5 Operator's manual

HEROSE
HEROSE 4186 Series Original Operating and Installation Instructions

Penn
Penn P216 Product bulletin

Ag Leader
Ag Leader OnTrac3 MDU-G4 installation manual

Synapse
Synapse DIM10-087-06 install guide

Allen-Bradley
Allen-Bradley PowerFlex 4M user manual

Resol
Resol DeltaSol SLT Manual for the specialised craftsman

Festo
Festo CPX-E-CEC EP Series Translation of the original instructions

Toshiba
Toshiba LC531 Series instruction manual

Danfoss
Danfoss DEVIreg Multi Installation and user guide

Danfoss
Danfoss AMI 120 NL-1 operating guide