1
ARLINGTON PRO DROP BLADE LED EXIT SIGN LUMINAIRE INSTRUCTIONS
Issue 06 21st December 2021
THANK YOU for buying this product. To help ensure it gives complete satisfaction, please install it according to these
instructions and then pass the instructions to the appropriate person for retention and future reference.
SAFETY This is a mains voltage powered luminaire. It is designed to be installed by suitably qualified personnel only
and in accordance with the applicable building and electrical regulations. Before installation or maintenance, the
electrical supply to the luminaire must be isolated.
INSTALLATION SUPPORT If installation advice or accessories are required, please contact us at the above address. When
reporting a suspected fault or seeking installation support the problem is likely to be resolved more quickly if you have full product
details to-hand, as well as details of when and where it was purchased.
LUMINAIRE INSTALLATION
1. The luminaire is suitable for wall or ceiling mounting. If
mounting on the ceiling, leave the main body of the luminaire
in its current position. If wall mounting, rotate the main body
through 90 degrees (see diagram).
2. Unscrew the small screw located on one end of the luminaire
body.
3. Using a small flat head screwdriver (in identified position),
gently lever the base plate away from the main luminaire
body.
4. Prepare the fixing surface (ceiling or wall) at the fixing
centres shown in the diagram.
5. Drill through the central cable entry point provided on the
base plate.
6. Pass the mains supply cable through the cable entry hole,
offer the base plate up to the fixing surface & secure in
position. Ensure the fixing method is capable of holding the
weight of the luminaire. Screws & rawl plugs are provided.
7. Route the mains supply cable to the terminal block in the base plate & terminate, ensuring correct polarity is observed. A
cable clamp is provided to restrain the cable.
NOTE! THIS LUMINAIRE MUST BE EARTHED NOTE! THIS LUMINAIRE NEEDS A PERMANENT LIVE SUPPLY
8. Connect the battery pack to the 2-pole connector on the main PCB & write the “installed date” in allocated position.
9. Offer the main fitting body to the base plate, locate the notch at one end & rotate to fully cover the base plate.
10. Secure in position using the small screw.
11. Connect the power supply & check the green LED charge indicator illuminates.
12. The batteries should be allowed to charge, uninterrupted for at least 24 hours before carrying out a full discharge test to
check they are charging correctly & the rated emergency duration is being achieved.
13. The operating temperature range of the luminaire is 0⁰C - +40⁰C.
ALTERNATIVE LEGEND PANELS (SUPPLIED SEPARATELY)
This product comes as standard with the Euro “Running Man legend with the DOWN arrow”. Alternative direction Running Man
legends & the ISO Running Man Through Door legends are also available from NVC – Please contact your local supplier.
To change legends:
1. Carefully pop apart the two clear plastic rivets located towards the bottom corners of the blade. Keep them safe.
2. Slide out the current legend panel.
3. Slide the top edge of the new legend panel into the head unit. Repeat for both sides.
4. Align the holes of the legends with the holes in the blade & secure using the two clear plastic rivets.
ALTERNATIVE MOUNTING OPTIONS (SUPPLIED SEPARATELY)
As standard this product suits either ceiling or wall mounting. There are further options via alternative mounting accessories
available from NVC. This includes:
Recessed mount kit
Side wall mount kit
Wire suspension kit
Please contact your local supplier