Obvius AcquiSuite Ally 12 User manual

Revision C (12/18)
AcquiSuite™
Ally 12 & 48
Advanced Multi-Circuit Meter
Install Guide

Revision C (12/18)
2
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Turn off all power supplying equipment before working on or inside the equipment.
•Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
•This equipment must only be installed and serviced by qualified electrical personnel.
•Read, understand and follow the instructions before installing this product.
•Product may use multiple voltage/power sources. Be sure all sources of power have been disconnected
before servicing.
•Use a properly rated voltage sensing device to confirm power is off.
•DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
•Only install this product on insulated conductors.
•Failure to follow these instructions will result in death or serious injury.
CAUTION
This product is not intended for life or safety applications.
•Do not install this product in hazardous or classified locations.
•The installer is responsible for conformance to all applicable codes.
•Mount this product inside a suitable fire and electrical enclosure.
A qualified person is one who has skills and knowledge related to the construction and operation of this
electrical equipment, and the installation, and has received safety training to recognize and avoid the hazards
involved. NEC2011 Article 100 No responsibility is assumed by Leviton for any consequences arising out of the
use of this material.
DO NOT EXCEED 346V Line to Neutral or 600 volts Line to Line. This meter is equipped to monitor loads
up to 346V L-N. Exceeding this voltage will cause damage to the meter and danger to the user. Always
use a Potential Transformer (PT) for voltages in excess of 346V L-N or 600 volts line to line. The VerifEye™ is a
600 Volt Over Voltage Category III device.
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control
conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the correct
use of ventilation, thermal properties of the equipment, and the relationship
with the environment.
Installation category: CAT II or CAT III
Provide a disconnect device to disconnect the meter from the supply source. Place this device in close
proximity to the equipment, and within easy reach of the operator, and mark it as the disconnecting device.
The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be
suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide
overcurrent protection and disconnecting device for supply conductors with approved current limiting devices
suitable for protecting the wiring. If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the device may be impaired.
For the complete safety information for this product, see the full user guide.

Revision C (12/18)
3
Technical Specifications
Specification
Description
Service Types
Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire
(Delta)
Voltage Channels
90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III.
Two independent voltage reference inputs
Current Channels
48 channels, 0.525 VAC max, 333 mV CTs, 0-4,000+Amps depending on current
transducer
Maximum Current Input
150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A
with RōCoil CTs.
Measurement Type
True RMS using high-speed digital signal processing (DSP) with continuous sampling
Line Frequency
50-60 Hz
Power
From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max
Use of 12 volt auxiliary output requires 100 VAC minimum input voltage.
AC Protection
0.5A Fuse 200kA interrupt capacity
Power Out
Unregulated 12VDC output, 200 mA, self-resetting fuse
Waveform Sampling
1.8 kHz
Parameter Update Rate
1 second
Measurements
Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received)
kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered)
kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD,
Theta, Frequency. All parameters for each phase and system total.
Accuracy
0.2% ANSI C12.20-2010 Class 0.2
Resolution
Values reported in IEEE-754 single precision floating point format (32 bit).
Indicators
4-line display, tri-color backlight (PhaseChek™)
Pulse Input
AMC12 –4 inputs, AMC48 –2 inputs
Alarm Output
Voltage Phase Loss Alarm (SPDT Relay - 30 VDC) ( only)
Communication
Hardware
RS-485, Ethernet, & USB (for configuration only)
Supported Protocols
Modbus RTU or BACnet Master Slave Token Passing protocol (MS/TP)
Modbus (using SunSpec IEEE-754 single precision floating point model)
BACnet MS/TP
Modbus TCP
BACnet IP
Max Communication
Length (RS485)
1200 meters total cable length, with Data Range of 100K bits/second or less
RS-485 Loading
1/8 unit

Revision C (12/18)
4
Communication Rate
(baud)
Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200
BACnet: 9600 (Default), 19200, 38400, 76800
Data Bits
8
Parity
None, Even, Odd
Stop Bit
2, 1
Termination
None provided
Mechanical
Wire Connections
12-22 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated
Mounting
Enclosure or Panel Mount
High Voltage Cover
IP40 (embedded version)
Operating Temperature
-20 to + 60⁰C (-4 to 140⁰F)
Humidity
5% to 95% non-condensing
Enclosure
ABS Plastic, 94-V0 flammability rating, connections sized for 1–inch EMT conduit
Dimensions
(L) 33.7cm x (W) 25.2cm x (H) 8.0 cm (13.3” x 10” x 3.1”) (no enclosure version)
(L) 24.7cm x (W) 25.2cm x (H) 8.0 cm (9.8” x 10” x 3.1”) (no enclosure version)
PCBA Dimensions
(L) 21.6cm x (W) 21.6.0cm x (H) 6.4 cm (8.5” x 8.5” x 2.5”)
Obvius Ally Configuration Console™ Minimum System Requirements
Operating System
Windows® 7. Windows® 8, Windows® 10
Communications Port
USB or Ethernet connectivity
Safety
FCC Compliance
This device has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in
a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at user’s own expense.
Serial/Ethernet Meters
The following are UL Recognized:
AMC12-B-y-z, -P-y-z, AMC48-B-y-z, -P-y-z
The following are UL Listed: AMC12-C-y-z, AMC48-C-y-z
Conforms to UL Std 61010-1, 3rd Edition, UL 61010-2-30:2010
Certified to CSA Std C22.2 No. 61010-1, 3rd Edition

Revision C (12/18)
5
Mechanical Specifications & Mounting
Series AMC48 - Enclosure
Series AMC12 - Enclosure

Revision C (12/18)
6
Series AMC48 –Enclosure Drill Pattern
Series AMC12 –Enclosure Drill Pattern

Revision C (12/18)
7
Series AMC48 –Mounting Plate Template

Revision C (12/18)
8
The following section illustrates the 12 channel model. The mounting components are slightly
different, but follow the same procedure.
STEP 1) Remove top cover screws (4x) and high voltage cover screws (2x) –provided
STEP 2) Locate, mark, and drill wall mounting points (2x–6x—customer supplied)
The plastic enclosure itself can be used as a template for marking the drill locations on the
wall.
If the meter is not available for use as a drill template, a drawing indicating the spacing between
mounting holes can be found in the appendix. The centerline holes are intended for fastening
to wall studs. If hollow wall fasteners are used, the outer 4 mounting points are recommended.
#8 Fastener

Revision C (12/18)
9
STEP 3) Mount conduit fittings, conduits, and blanking plugs
STEP 4) Connect voltage leads

Revision C (12/18)
10
STEP 5) Attach high voltage cover
STEP 6) Connect CT and Communications Wiring
Connecting Voltage
Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter through a dedicated
disconnect or circuit breaker. A voltage lead of 14 AWG THHN Minimum 600VAC rating (or
equivalent) is required.
IMPORTANT: Verify the circuit breaker is marked as the disconnect
breaker for the meter.
IP30
TOUCH SAFE (with internal cover installed)

Revision C (12/18)
11
Wiring the AcquiSuite™Ally Meter in a 3-wire, Split ɸService Panel
High voltage MAY BE PRESENT. Risk of electric shock. Life
threatening voltages may be present. Qualified personnel only.
Illustrating the intended wiring configuration for each of the Service Types
available in the Service drop-down list under “Meter Setup”
EXAMPLE LOADS:
Single Phase L1-N or L2-N 110 VAC: Lighting, Appliance, Living Zone
Single Phase L1–L2 220 VAC: Water Heater, Clothes Dryer, Equipment with no neutral wire.
Split Phase L1–L2 220 VAC: Service Entrance, Equipment with neutral wire.
3-Wire, 1 Phase used
On MAINS
L1-N, L2-N
(RōCoils Shown)
Single Phase
110 VAC Plug Loads
L1-N or L2-N
Single Phase
220 VAC Plug Load
L1-L2
Meter is powered
from L1 to L2 on
the V Input 1
terminal
(Label as Disconnect))
Connect the
Neutral wire to
V INPUT 1 (N) on
the meter
3-Wire, 1 Phase
Split Load
L1-N, L2-N

Revision C (12/18)
12
Wiring the AcquiSuite™ Ally Meter in a 4-wire, 3 ɸService Panel
Illustrating the intended wiring configuration for each of the Service Types
available in the Service drop-down list under “Meter Setup”
Note: The AcquiSuite™Ally Meter Series uses the “Neutral” Terminal as a
voltage reference. For systems without a neutral conductor, Leviton
suggests connecting a ground wire to this terminal. If the neutral terminal
is left open, L-L measurements will be accurate, but L-N measurements
may not be symmetric. If a ground wire is connected to the Neutral
terminal, <2mA will flow into the ground wire.
Single Phase
Branch Loads
L1-N
Connect the
Neutral wire
or Ground wire to
V INPUT 1 (N) on
the meter
Meter Power
Connect all phases
to the V INPUT 1
terminal
(Label as Disconnect)
3-Wire, 3 ɸ
DELTA load
(No possibility of
Neutral Current)
L1-N, L2-N(est), L3-N
3 Wire, 3 ɸused
On MAINS
L1-N, L2-N, L3-N
(Rogowski Coils Shown)
4 Wire, 3 ɸ
WYE load
(Neutral Current)
L1-N, L2-N, L3-N

Revision C (12/18)
13
Wiring the CTs to the AcquiSuite™ Ally Meter
The image below is the counterpart to the service panel illustration and indicates how to
connect CTs to the input terminals on the AcquiSuite™ Ally, for each service type. For service
types that are not specifically listed, it is recommended to choose “single phase” service and
configure each channel individually. Three phase loads are illustrated on the left and split phase
loads on the right as an example only. Elements are fully interchangeable on the meter.
•Current and voltage inputs must be installed ‘in phase’ for accurate readings (e.g. CT1
on Line 1, CT2 on Line 2) Orientation is critical: Ensure that all CTs are properly oriented
with the line and load, as marked. Failure to install CTs in the correct orientation and on
the correct phase will lead to inaccurate meter readings.

Revision C (12/18)
14

Revision C (12/18)
15
Communication Verification
Verification includes confirmation of BOTH the physical interface settings
(Serial or Ethernet) and the protocol (Modbus or BACnet) settings.
The LCD User interface can be used to quickly confirm the settings required for each
combination of interface and protocol. The interface is intuitive and groups together commonly
associated registers. The complete interface is presented in Appendix A as a navigational map.
Arrows indicate how to move from one menu display to the next. A Reverse Contrast entry in
the documentation indicates the active menu item in a list which corresponds to a blinking
character in the physical LCD. The ENTER button is used to select a property and up / down
buttons are used to select among the values supported by the meter. Note that changes to the
meter configuration are limited to the communication interface using the LCD. If additional
changes (such as CT type) are required they must be made using a software interface.
Example LCD Navigation
AcquiSuite™ Ally Configuration Console / Web Application
If your AcquiSuite™ Ally model does not include the LCD user interface or if you prefer to verify
the installation using software, then verification is facilitated through the AcquiSuite™ Ally

Revision C (12/18)
16
Configuration Console PC application or the Web App which shares a common design. Refer to
the section on Configuration Details in the full user manual, or the AcquiSuite™ Ally Web App.
Pulse Inputs
Ally ACM12 meters are equipped with 4 pulse inputs and Ally ACM48 meters (hardware version
I) are equipped with 2 pulse inputs. Pulse counting supports accumulation of consumption data
from any external meter using a dry contact (Form A Relay) or open collector outputs. The
AcquiSuite Ally pulse inputs are compatible with “low speed” meters. The pulse duration must
exceed 50mS in both the logic low and high state allowing for a maximum input frequency of 10
Hz.
Pulse scaling, resetting and accumulated values are accessed through registers and are “system”
in scope. Refer to the register list, Obvius Ally Configuration Console, or videos for more
information.
Typical Pulse Sequence
>50 mec
>50 mec
Other manuals for AcquiSuite Ally 12
1
This manual suits for next models
1
Table of contents
Other Obvius Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Rigol
Rigol RSA5000 Series Performance Verification Guide

AMALGAMATED INSTRUMENT
AMALGAMATED INSTRUMENT PM5 Optional Output Addendum

Velleman
Velleman DVM856 user manual

Siemens
Siemens SIREMOBIL Compact Installation and setting instructions

Endress+Hauser
Endress+Hauser Liquiline CM44P Brief operating instructions

Emerson
Emerson Lumity IC100D EVO Quick reference guide