oke-2020TH user manual V19-9 en.PDF
Required Temp./ Humid. Setup process
Master mode Setup process
1. Press SET button (5 sec)
for requested Humid./
Temp.
2. Humid. or Temp.
➢Humid. Set range : 0 ∽ 99.9%
➢Temp. range : -55.0 ∽ 99.9C
1. Press Up / Down button
for requested set Humid./
Temp.
1. Press SET button during
5 seconds (or wait 10
seconds) to save new
value and then return to
normal function display
1. Press shortly SET button
For Humid. Or Temp.
till display “OK” and then the
value will auto save.
➢Operationrange : -55℃~99.9℃ / 0%~100%
➢External size (mm) : 76(W) x 34(H) x 75(D)
➢Cutting size (mm) :70(W) x 30(H)
➢Delay time : 0 ~ 9 MIN (1min/unit)
➢Correct Current Humidity. : -9.9~+9.9℃ (0.1℃/units) / -
9.9~+9.9% (0.1%/units)
➢Input sensor : NTC (5KΩ 25℃) / HIH-4000(5V)
sensor
➢Sensor accuracy : Temp1% / Humidity 2 %
➢Power supply : 100~240VAC 50/60Hz (free Volt)
➢Power Consumption : Aver. 5VA ↓
➢Ambient temp./ Humidity : 0℃~50℃/ 80% ↓
➢Output : 2 relay ON/OFF (250VAC2A) (R1: Temp, R2:
Humidity)
➢Output deviation : 0.0℃~9.0℃ (0.1℃/units) / 0.0~9.0%
(0.1%/units)
1. Press SET button during 5 seconds for requested Humid. or Temp.
2. Press Up / Down button for requested set Humid. or Temp
3. Press SET button shortly to switch required function
4. Press SET button during 5 seconds (or after 10 seconds) Master mode will save with new value saving
automatically and return to normal function mode..
➢Set the Highest value for Required Temp./Humid.
➢When change the required value, it should be lower than HSP
➢Set the Lowest value for Required Temp./Humid.
➢When change the required value, it should be higher than LSP
➢When set the function, just Output display lamp will be blinking
without any operation during the set delay-time.
➢When ended the set delay-time, Output display lamp will be blink
and then start the real Output “ON”
➢( ♠Pease refer the below graph for the Output Delay-time Value)
❖Output control graph for the Output
Deviation Value Chart
➢When - Set Temp.: 0C/ delay-time : 0 min /
Deviation : 5.0C / mode: C(cooling)
➢Output control ON/OFF graph for the Temp.
Output Deviation Value
❖Output control graph for the Output
Delay-time Value Chart
➢When –Set delay-time : 0 min
➢When –Set delay-time : 2 min
Output OFF Output ON
Output OFF Output ON
Delay
Time
❖Specification Details
➢When set the function, the required Output will ON/OFF depend on
the Deviation value
➢When equal current Temp./Humid. With required value, the Output
will OFF and when there are any deviation value, Output will ON
➢( ♠Pease refer the below graph for the Output Deviation Value)
➢When there are any different in between the current Temp./Humid.
and the required values, function will allow to correct the values
discretionally.
➢Just correct the different Temp./humid. Values in between with
current and required values
➢Set the Output mode (Temp./Humid.) function
➢When if set as C(D) mode, the Output will be ON when the current
Temp.(Humid.) is higher than the required Temp.(Humid.) value
➢When if set as H(H) mode, the Output will be ON when the current
Temp.(Humid.) is lower than required Temp.(Humid.) value
5. Press SET button during 5 seconds, and then new values will be saved
6. Or after 10 seconds, new values will be saved automatically
7. Return to normal function mode display