Olimpia electronics BSR-6160 User manual

BSR-6160
Page 1 from 4
GENERAL
The user have to read carefully the following instructions, in order to be properly informed and keep them
for future use.
The BSR-6160 is an analogue addressable heat detector which integrates the function of rate-of-rise
heat detection and it can work with any fire panel supports Olympia A Protocol. It can be adjusted to detect
multiple levels of heat offering flexibility and rich functionality. Also, it integrates a short circuit isolation
circuit which is automatically activated and disconnects the defective node from the remaining loop,
allowing it to be located by the panel.
The detector sends to the main panel an analogue value which depends on the heat. The value is 100 at
o o
57 C and increases proportionally to 120 at 90 C. When a sudden increase in temperature is detected the
detector sends the value of 121.
By default the panel is set to sound an alarm when the temperature is 57 C. The user can change this
setting from the panel for each detector and define any level of temperature between the lower and the
upper limits, specifying the sensitivity of the system depending on the requirements of each site. Also, the
user can select A1R or A1S working mode through the panel.
They are composed by two parts. A plastic base which is placed on the ceiling and the main body of the
o
detector which fits on the plastic base with a simple rotation to the right. The detectors have a 360 visible
led and a remote led driver which are light up constantly in case of detection of fire, till cancelled from the
panel. Also, they are staying lit even if the sirens are silenced from the panel, so the detector which
detected the alarm is visible. They are turned off only when a reset command is given from the panel. The
indicator led blinks every 10 sec indicating the connection status with the main panel.
o
Analogue addressable rate-of-rise heat detector
with integrated isolator
Thank you for your trust in our products
Olympia Electronics - European manufacturer
TEMPERATURE SENSITIVITY
INDICATORS
OUTPUT
MAXIMUM LOOP CURRENT (Ic max, -L in/out)
MAXIMUM SWITCH CURRENT (Is max, -L in/out)
MAXIMUM SERIES RESISTANCE (Zc max, -L in-out)
MAXIMUM LEAKAGE CURRENT
IN ISOLATION MODE (I max, -L in/out)L
ISOLATION VOLTAGE (Vso min-max)
RECONNECT VOLTAGE (Vsc min-max)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
1A
5A
IP42
EN 54-5 EN 54-17,
100mΩ
Adjustable from 57 to 90 in 1.5 steps oC
10.7 - 12.7
9.3 - 10.6
Up to 95%
ο
-40 to 70 C
ABS/PC
145 gr.
103 (d) x 48 (h) mm
2 years
Remote LED driver
Alarm LED
25mA pulses (6ms duration every 2sec)
90μΑ
11-30V DC
2.5mA (with activated LED)
TECHNICAL CHARACTERISTICS
MAIN VOLTAGE
STANDBY CONSUMPTION
ALARM CONSUMPTION
CLASS A1R/A1S
Olympia A ProtocolCOMMUNICATION PROTOCOL
921616000_09_002

SETTING THE ADDRESS
Each detector must have a unique address, with which it is recognised from the panel. It is forbidden for
two devices in the same loop to have the same address. To set it up you can use the function of changing
address point as described in the user manual of the panel.
.
-
- Automatic fault diagnosis.
- Adjustable temperature alarm level for maximum flexibility.
- 360
UID:
In every device there is a double sticker with the UID (Unique Identifier) number. This number is
INSTALLATION
The detectors should be placed in the ceiling in visible points without side obstacles, away from places
that are barely ventilated or with strong air currents and water vapor. Each detector covers an area of 50
2
m while the distance between two detectors should not be more than 15m. Also, they must be placed at
least 50 cm away from fluorescent lamps. Cable diameter should be from . to .
MAINTENANCE & FUNCTIONAL TESTING
The detector has fault diagnosis function, which automatically informs you when detector replacement is
required. This function combined with periodic manual testing ensure maximum security level. It is
suggested to carry out a test every 6 months or after a change in the position of the sensor. A key element
of its proper function is the air to be able to freely circulate inside it. So be careful not to block the openings
of the outer cover. Before the manual testing procedure it is suggested to enable the special “walk in test”
mode from the panel.
CAUTION !!
After installation the device must not be covered with dust or be painted or anything else happen that will
block the air to get to the sensor. Special attention must be given during the installation and the use of the
device, since the user assumes full responsibility for proper operation afterwards.
0 5 2 5mm
Additional features of the device :
ooptically visible LED.
Integration of dynamic algorithms for noise and false alarm rejection.
Page 2 from 4 921616000_09_002

1. Remove the detector from its base rotating to the left till the side marks are aligned.
2. Fasten the base with the supplied mounting materials (point 5).
3. Connect the power cables (minding the correct polarity) according to the requirements of the
installation (Figure 1, 2).
4. Place the detector carefully so that the side marks are on the same position and rotate the detector
clockwise until it locks. Power the device and after 3-5 seconds it is ready for operation.
CONNECTION
1. + IN/OUT: Connect to (+L) of the loop.
2. - IN: Connect to (-L) of the loop.
3. - OUT: Connect to (-L) of the loop.
4. - R : External LED connection.
5. : Connected to the cable’s shield (when shield is used).
Mounting base
Figure 1
55
R
+
-R
Installation process
2
Connection
with exterrnal
LED
U
T
/O
N
I
+
N
- I
T
U
- O
Page 3 from 4
e
n
i
t
n
s
g
a
f
d
t
e
n
t
a
e
c
m
h
1
Indicating
LED
Side marks
Figure 2
Loop
Loop
-R
U
T
/O
N
I
+
N
- I
T
U
- O
Loop Loop
-R
-R
-R
-R
-R
+L -L +L -L
CN2
U
T
/O
N
I
+
N
- I
T
U
- O
U
T
/O
N
I
+
N
- I
T
U
- O
U
T
/O
N
I
+
N
- I
T
U
- O
U
T
/O
N
I
+
N
- I
T
U
- O
U
T
/O
N
I
+
N
- I
T
U
- O
PE
IN OUT
921616000_09_002

Page 4 from 4
WARRANTY
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty
is specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which
accompanies each product. This warranty ceases to exist if the buyer does not follow the technical
instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods
provided or has any repairs or re-setting done by a third party, unless Olympia Electronics has fully
agreed to them in writing. Products that have been damaged can be returned to the premises of our
company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.