Omniguard 760 series Service manual

760 SERIES OPTICAL
FLAME DETECTORS
Installation and operating
service manual

2
©Firey AB (Oktober 2016)
Table of contents
Description ...........................................................................3
Theory of operation ...................................................................5
Specications .........................................................................6
Applications ..........................................................................7
Installation............................................................................7
Electronics ............................................................................7
Maintenance and troubleshooting....................................................11
Service and Repair ...................................................................12
Warranty.............................................................................12
Part Number Key .....................................................................13
Wiring Diagram ......................................................................13
CAUTION!
Electrostatic Discharge:
A discharge of static electricity from an ungrounded source, including the human body,
may damage the electronic circuitry of the Omniguard® Series 760 Flame Detectors. Use
one or more of the following methods when handling or installing electrostatic sensitive
parts:
• A wrist strap connected by a ground cord to an earth ground source
• Heel straps, toe straps, or boot straps at standing workstations
• Conductive eld service tools
• A portable eld service kit with a static-dissipating work mat

3
©Firey AB (Oktober 2016)
Description
The Omniguard® 760 ame detector is an optically based,
self-contained, microprocessor controlled, multi-spectrum
infrared (IR5) ame detector. The 760 ame detector utilizes
the patented Fire Event Analysis (FEA)™ discrimination
technology. This ame detector is compatible with most alarm
panels without the need for a controller. All electronics are
housed within a copper-free aluminum, high temperature,
TGIC-Polyester coated enclosure with a ¾-14NPT or M20-1.5
conduit entry.
The Model 760 ame detector is suitable for use in Class I,
Division 1, Groups B, C and D (explosion-proof) areas. The
housings are Type 4X, dust-tight and watertight. The detectors
are approved for both indoor and outdoor installations.
Standard features
• Microprocessor Based.
• User adjustable time delays.
• User adjustable latching or non-latching re relay.
• User adjustable sensitivity.
• User adjustable NO or NC relay outputs.
• LED indication: re (red), normal (green ashing), fault (amber).
• Transient voltage (surge) protection.
• RS485 addressable user interface using MODBUS RTU.
• Terminal block accepts 22 to 12 AWG wire.
• 0 to 20 mA output.
• Relay contacts rated at 2 Amps @ 30 VDC.
Approval:
• FM
• SIL 2
• CSA
• Russian Fire Certicate
• IECEx
• ATEX
• EMC
• LVD
• CSFM
Fire Detection Performance
The Model 760 ame detector is designed to function properly
when operated under the conditions outlined in the“re detetion
performance”, “false alarm immunity”and “re detection in the
presence of false alarm sources” sections of this manual. Exposing
a 760 detector to any IR sources within the specied eld of view at
distances less than 3.5 feet may cause the detector to either false
alarm or alter the detector’s abiltiy to meet other stated performance
parameters during the exposure.
Note: All performance tests listed below were performed outdoors
and were third party certied for performance. The “*“ indicates a pre-
burn condition.
Normal Sensitivity:
• 1 ft2n-Heptane re at 75 ft in < 1 sec.
• 1 ft2gasoline re at 75 ft in < 1 sec.
• 1 ft2Isopropyl Alcohol re at 75 ft in < 1 sec.
• 1 ft2Propane re at 75 ft in < 1 sec.
• ½ lb of oce paper re at 75 ft in < 1 sec.*
• 0.75 inch diameter orice with a ow rate of 1.5 SCFM hydrogen
plume at 50 ft < 1 sec.
• 1 ft2Diesel re at 75 ft in < 1 sec.*
Enhanced Setting:
• 1 ft2n-Heptane re at 100 ft in < 1 sec.
• 1 ft2gasoline re at 100 ft in < 1 sec.
• 1 ft2Isopropyl Alcohol re at 100 ft in < 1sec.
• 1 ft2Propane re at 100 ft in < 1 sec.
• ½ lb of oce paper re at 100 ft in < 1 sec.*
• 1 ft2Diesel re at 75 ft in < 1 sec.*
Long Distance Setting:
• 1 ft2n-Heptane re at 200 ft in < 1 sec.*
• 1 ft2gasoline re at 200 ft in < 1 sec.
• 1 ft2Propane re at 200 ft in < 1 sec.
• 4 ft2JP5 re at 200 ft in < 5 sec.*
• 4 ft2Diesel re at 200 ft in < 5 sec.*
Note: Detector response times and distances can be inuenced by
wind, smoke and viewing angle. Consult Firey AB applications
engineers for specic details.

4
©Firey AB (Oktober 2016)
False Alarm Immunity
All tests were performed outdoors and third party certied for no
response at the recommended distances. These distances should be
used as a guide when installing the detectors.
Normal Sensitivity:
• Sunlight
• 1500 Watt ribbon heater at 5 ft.
• 100 Watt incandescent bulb in a work-light xture at 3.5 ft.
• 500 Watt quartz halogen lighting xture at 4 ft.
• 40 Watt uorescent bulb at 4 ft.
• Welding at 20 ft.
Enhanced Sensitivity:
• Sunlight
• 1500 Watt ribbon heater at 7 ft.
• 100 Watt incandescent bulb in a work-light xture at 5 ft.
• 500 Watt quartz halogen lighting xture at 4 ft.
• 40 Watt uorescent bulb at 4 ft.
• Welding at 20 ft.
Long Distance Sensitivity:
• Sunlight
• 1500 Watt ribbon heater at 10 ft. (unmodulated)
• 1500 Watt ribbon heater at 20 ft. (modulated)
• 100 Watt incandescent bulb in a work-light xture at 10 ft.
• 500 Watt quartz halogen lighting xture at 5 ft.
• 40 Watt uorescent bulb at 4 ft.
• Welding at 40 ft.
Note: Unless otherwise specied the method of testing for sunlight
was both direct and indirect and for the other sources was both
modulated and unmodulated.
Fire Detection Performance in the Presence of False Alarm
Sources
All tests were performed outside and third party certied for response
to a 1 ft2Propane re at 75 ft for the Normal setting, at 100 ft for the
Enhanced setting and at 200 ft for the Long Distance setting with the
false alarm sources at the recommended distances. In all cases the
detector response was less then 1 second. These distances should be
used as a guide when installing the detectors.
Normal Sensitivity:
• Sunlight
• 1500 Watt ribbon heater at 5 ft.
• 100 Watt incandescent bulb in a work-light xture at 3.5 ft.
• 500 Watt quartz halogen lighting xture at 4 ft.
• 40 Watt uorescent bulb at 4 ft.
• Welding at 20 ft.
Enhanced Sensitivity:
• Sunlight
• 1500 Watt ribbon heater at 10 ft.
• 100 Watt incandescent bulb in a work-light xture at 5 ft.
• 500 Watt quartz halogen lighting xture at 4 ft.
• 40 Watt uorescent bulb at 4 ft.
• Welding at 20 ft.
Long Distance Sensitivity:
• Sunlight
• 1500 Watt ribbon heater at 20 ft.
• 100 Watt incandescent bulb in a work-light xture at 10 ft.
• 500 Watt quartz halogen lighting xture at 5 ft.
• 40 Watt uorescent bulb at 4 ft.
• Welding at 40 ft.
Note: Unless otherwise specied the method of testing for
sunlight was both direct and indirect and for the other sources was
unmodulated only.
(Fig 1) Field of View for JP-5
(Fig 2) Field of View for Diesel
(Fig 3) Field of View for all other Tested Fuels

5
©Firey AB (Oktober 2016)
Theory of operation
The Omniguard® 760 ame detector is a multi-spectrum, infrared
sensing, re detector. The principle of operation is based on the
patented Fire Event Analysis (FEA) detection algorithm proven to be
both successful and reliable since its inception in 1984. The newly
developed 760 Flame Detector utilizes the fundamental concept of the
original FEA scheme while incorporating improvements aorded by
advances in microprocessor technology.
Sensors located behind two separate windows sample 5
separate wavelength regions within the infrared (IR) portion of
the electromagnetic spectrum. These sensors are continuously
interrogated to ensure the proper operation of the re detector.
The re channel senses radiation in two discrete regions of the IR,
which are common to the CO2and H2O emission bands generated as
by-products in conjunction with most combustion processes. The non-
re channel senses radiant energy in three additional discrete regions
of the IR, which are exclusive of those associated with the re channel.
The outputs from these sensors, combined with a sophisticated
algorithm, results in a highly reliable means with which to detect res
fueled by both hydrocarbon and certain non-hydrocarbon materials
while maintaining a high degree of false alarm immunity.
The automatic self-test feature of the Model 760 ame detector veries
the proper function of the electronics, sensors and optical surfaces.
This self-interrogation process is implemented a minimum of four
times per hour, thereby providing vital re detection reliability. This
is accomplished by channeling the calibrated output of an internally
mounted incandescent lamp, through optical light guides, to both
re detector windows and nally the sensors. Failure of this process
will generate a fault indication. Upon receipt of a fault, an inspection
process is required in order to determine whether the windows have
become contaminated to a level that is likely to impair the detector’s
ability to adequately sense res.
A self-test fault condition will result when a sensor’s response has
degraded signicantly over that established during the original factory
calibration of the re detector. Alternatively, in the event of a self-test
fault where windows are found to be free of lms, the fault will be an
indication that another part of the detector has failed.
The 760 ame detector has three sensitivity settings: Normal,
Enhanced and Long Distance. For performance attributes associated
with these settings please refer to section for User Selectable Interface
(USI) Options.
Note: Reference Figure 4 for appropriate sensor wavelength regions to
be used in Zeta calculations per NFPA 72 edition 2002 or later.
(Fig 4) Typical Hydrocarbon Fire Spectrum (Wavelengths in Micrometers)

6
©Firey AB (Oktober 2016)
Specications
Environmental
• Suitable for use in hazardous locations:
Class I, Division 1, Groups B, C & D
Class II, Division 1, Groups E, F & G
Type 4X rated.
• European Rating –
ll 2 G/D Exd IIB + H2 T5 Gb for gas
Ex tb IIIC T100°C Db IP66 for dust
• Operating Temperature: -40°F to 194°F (-40°C to 85°C)
• Storage Temperature: -40°F to 212°F (-40°C to 100°C)
• Humidity: 0 to 95% relative humidity at 140°F (60°C)
• Shock: Mil-Std-810E Method 516.4 Procedure I, Figure 516.4-4, 20
G’s, 11ms
• Vibration: Mil-Std-810E Category 10, Method 514.4 Test Procedure
1, Test Condition I-3.4.9, Figure 514.4-17. Modied 20 to 500 HZ. 20
minute sweep to 3 Hrs Max per Axis in all three Axes.
Electical Interface
• Nominal voltage input – 24 Vdc (20 Min/30 Max).
• Maximum allowable ripple voltage – 240 mV
• Maximum Current Draw (@ 30Vdc):
Standby Alarm Manual Test Auto Test
80 mA 100 mA 160 mA 160 mA
• Relay Contact rating:
2 Amps @ 30 Vdc (Resistive)
Note: The detector contains two relays:
(1) Fire, (1) Fault
• Current Loop Output (0 to 20 mA) (For details see Table 2)
• RS485 Half-duplex, Addressable, User Interface
Baud Rate 9600 bits per second
1 start bit, 8 data bits and 2 stop bits.
• Maximum Power consumption (@ 30 Vdc)
Standby Alarm Manual Test Auto Test
2.40 W 3.00 W 4.80 W 4.80 W
Mechanical Specication
(Figure 5 Shows Nominal Dimensions)
Depth: 4.9 inches [124.97 mm](Max)
Height: 4.8 inches [122.43 mm](Max)
Width: 5.5 inches [140.21 mm](Max)
Weights: (installed)
Aluminum Housing 5 lbs (2.4 kg)
Stainless Steel 13 lbs (6.3 kg)
Shipping weight:
Aluminum Housing 6 lbs (2.8 kg)
Stainless Steel 14 lbs (6.7 kg)
Optional Accessories
Swivel Mount - 20856(1) (Used with aluminum enclosure)
70991(2) (Used with stainless steel enclosure)
Air Shield Kit - 19796
Rain Shield - 23546
Portable test unit Model 545
(Fig 5) Mechanical Dimensions
(Fig 6) Swivel mount installation

(Fig 5) Mechanical Dimensions
Applications
The Model 760 ame detector is designed for re detection
applications where sudden res from hydrocarbon and specied non-
hydrocarbon fuels, may occur. This detector is not recommended for
detection of smoldering materials.
The following is a partial list of materials which when burned, can emit
infrared radiation in the wavelengths common to the detection bands
of the 760. Response times and detection distances will vary. Contact
a Firey AB applications engineer for assistance:
Hydrocarbon:
• Petroleum based materials such as liquid fuels, solvents, gases, or
solid compounds
• Wood products
Non-Hydrocarbon:
• Hydrogen, silane, hydrazine
The rugged, weatherproof construction and the operating
temperature range of the detectors will accommodate a variety of
indoor and outdoor applications.
All installations should comply with local re codes and regulations.
Do not proceed with the installation if you do not understand the
installation procedure or operation of the detectors. Firey AB
applications engineers are available to assist you.
Installation
To ensure trouble-free operation and reliable re protection, follow
these installation guidelines:
1. Locate the Detector(s) in an area where they will have an
unobstructed view of the area to be protected. The detector(s) must
be accessible for periodic cleaning. Failure to maintain clean sensor
windows and self-test optics will impair the performance of the
detector.
2. Separate the base from the housing by removing the four M8 X
1.25 cap screws. This will require a 6mm hex key. Store the housing
assembly, containing the electronics, in a clean and dry environment
while installing the base.
3. Mount the detector base to a previously installed swivel mount
or other appropriate support structure so that the detector has an
unobstructed view of the area to be protected. Position the base such
that the conduit opening faces down. It will be necessary to seal the
conduit within 18 inches of the re detector enclosure. This will insure
that water and airborne moisture do not enter the detector housing
through the conduit. Provide conduit drains as necessary to prevent
moisture from collecting inside the conduit.
4. Determine the critical areas where res are most likely to occur. Use
these areas as focal points for aiming the detectors. The detectors
have a conical eld-of-vision as shown earlier in Figures 1 and 2.
The type of fuel and the size of the re will determine the range of
detection. Aim the detector at a point equal to or below horizontal so
that water, dust and dirt will not accumulate on the optical surfaces
of the detector. As a general rule, mount the detector so that it will
view the base of the area to be protected. The aiming of the detectors
becomes increasingly critical the greater the detection distance
becomes. There should be few if any obstructions between the
detector and the area to be protected.
5. Complete the installation by wiring the detector according to the
wiring diagram located inside the rear cover. Before assembling the
detector housing to the base, verify that the terminal block assembly is
plugged in all the way and is located at the top. Insure that the wires
are arranged so as not to interfere with the main electronics module.
If a Torque wrench is available, it is recommended that the four cap
screws be tightened to a value of 35 to 40 in-lbs. (3.95 to 4.52 NM).
Note: The electronics module contains no re-useable parts. It should
never be removed from the housing assembly. This will result in the
voiding of the warranty.
6. Use a 20 to 30 Vdc regulated and ltered power supply, with a ripple
not exceeding 1 percent. The detectors should be protected from
induced and transient voltages as well as radio frequency interference
(RFI). To ensure compliance to CE requirements, a dedicated conduit is
highly recommended for the detector wiring. Connect every detector
base to earth ground via an independent wire. Earth ground and
-24 VDC RTN should be isolated and not connected anywhere in the
installation.
Electronics
User Selectable Factory Settings
The electronic module has been factory congured to provide the user
with the following:
Time Delay: 3 Seconds (re)
35 Seconds (Warning)
Sensitivity: Normal
Relays: Fire: Normally Open, Latching.
Fault: Normally Open, Non-latching (Relay is failsafe,
it closes upon application of power to
detector and will clear after a successful test).
Optical Self-Test: Automatic
0 to 20 mA: “OFF”
RS485: “OFF” MODBUS RTU
User Selectable Interface (USI) Options
Refer to Figure 8 for locations of User Selectable Interface Options.
Figure 7 provides the user with a quick reference of switch setting
options for the various models. The text following these gures
describes in more detail the function of each switch setting.
SPST dip switch (S1) located on rear I/O board
Option O On
Automatic & Manual Test Activated 1, 2
No Test Feature 1, 2
Manual Test Only 2 1
Automatic Test Only* 1 2
Sensitivity — Long Distance 3, 4
— Enhanced 3 4
— Normal 4 3
— (Reserved) 3, 4
Warning Alarm5 5
No Warning Alarm* 5
Fire Output Latching* 6
Fire Output Non-latching 6
0 to 20 mA 7
No 0 to 20 mA* 7
RS485 MODBUS RTU 8
No RS485 MODBUS RTU* 8
Program 9
No Program* 9
*Denotes factory settings for auto test units only
(Fig 7) Switch Options For the User Selectable Interface
7©Firey AB (Oktober 2016)

8
©Firey AB (Oktober 2016)
(Fig 8) User Selectable Options
Fire Time Delay
The re outputs can be congured to delay for up to 25 seconds
before annunciation of a re. If the re were to extinguish anytime
prior to the end of the set delay time, the detector would not declare
a re. The factory setting for this delay time is 3 seconds. To adjust
the re delay time, use Potentiometer (Pot) R49. Turning the Pot
counterclockwise (CCW) will decrease the time delay. One turn equals
approximately 1.25 seconds.
Warning
Switch position 5 is used to enable the Warning Output. If switch
position 5 is “ON”, this option is activated. If switch position 5 is
“OFF”, this option is not activated. This option will alert the user to
the presence of elevated levels of IR within the eld-of-view of either
sensor.
Warning Time Delay
The warning outputs can be congured to delay for up to 60 seconds
before annunciating the presence of elevated IR levels. If the warning
signal disappears prior to the end of the set time delay, then the
detector would not allow the outputs to toggle“ON”. The factory
setting is 35 seconds. To adjust the warning time delay, use Pot R48.
Turning the Pot CCW will decrease the time delay. One turn equals
approximately three seconds.
Note: Always reset power to the detector after adjusting the pots. The
detector will not recognize any new setting unless it is reset.
Sensitivity Levels
(Table 1): Switch positions 3 and 4 adjust the sensitivity to four
dierent levels. The “Long Distance”setting is the most sensitive
to infrared radiation and the most susceptible to false alarms. The
“Normal” setting is the factory setting and is recommended for
most applications. The following are the settings for the two switch
positions:
Table 1: Sensitivity Settings
Sensitivity Level Position 3 Position 4
Long Distance O O
Enhanced O On
Normal On O
(Reserved) On On
Note: The “Reserved” setting will provide the same level as the
“Normal” setting.
Relay Adjustments
There are two relays and conguration option jumpers, JP1 and JP2,
located on the exposed surface of the printed circuit board (PCB) in the
housing assembly. Using these jumpers, the relays may be congured
as normally open or closed. The factory will ship the detectors with
the following settings.
Relay Adjustments
There are two relays and conguration option jumpers, JP1 and JP2,
located on the exposed surface of the printed circuit board (PCB) in the
housing assembly. Using these jumpers, the relays may be congured
as normally open or closed. The factory will ship the detectors with
the following settings.
1.) Fire relay (K2) – normally open:
-will close when there is a re continuously present beyond the
re time delay setting.
-will close when manual test is activated beyond the length of
time for the re delay time setting.
Note: The red light emitting diode (LED) will illuminate when
relay closes.
2.) Fault relay (K1) – normally open:
-will close within 8 seconds when power is applied.
-will open when power is lost or fuse F1(located on the PCB)
opens.
-will open when detector fails automatic test.
-will open when detector fails manual test.
-will open when switch 7 is on and no loop is present.
Note: The amber LED will be illuminated when relay opens,
unless there is a loss of power.
Note: Any adjustments to the user options listed above should
be done with the power“OFF”. The detectors will not recognize
any changes until the microprocessor is reset. Removing the
power allows a reset to occur.
Caution: Upon applying power, insure that the detector
remains on for at least 8 seconds to allow for complete
initialization to take place.
Fire Outputs Latching or Non-Latching
Switch position 6 selects the latching or non-latching Fire Outputs
option. To select latching, the switch position 6 must be toggled“ON”.
Upon detecting a re, the Fire Outputs signal will remain engaged as
long as power remains“ON” or until the detector is reset through the
RS485 User Interface (UI). If you select non-latching by toggling switch
position 6 to “OFF”, the Fire Outputs signal will disengage after a re is
extinguished.
Optical Self-Test
The Model 760 ame detector makes use of a self contained “through-
the-lens” optical clarity-checking feature. The factory setting is for
automatic test only, switch position 1 is“OFF”and switch position 2
is “ON”. (See Figure 6 for location of the switches and Figure 5 that
describe the switch settings for the user selectable interface.) If the
addition of the manual test feature is desired, then toggle switch
position 1 to “ON”. If only the manual test feature is needed, then
toggle the switch position 1“ON”and switch position 2 “OFF”. If no
optical testing is preferred then ensure that both of these switches are
“OFF”.
0 to 20 mA Output
Switch position 7 selects the 0 to 20 mA output option. If this output is
utilized, then switch position 7 must be“ON”. Otherwise, if this output
is not used, switch position 7 must be kept“OFF”or it will cause the
Fault Outputs to turn “ON”. Table 2 illustrates the order of priority.

9
©Firey AB (Oktober 2016)
Table 2: Milliamp Logic Chart
Priority State Load Current mA
1 Fire 20 ± 0.2
2 Fire IR Warning 16 ± 0.2
3 Ref IR Warning 15 ± 0.2
4 Fire Relay Coil Fault 3 ± 0.2
5 Calibration not complete /
EEPROM Corrupted Fault
2 ± 0.2
6 Exceedance Fault 1.5 ± 0.2
7 Block Fault 2.5 ± 0.2
8 Self-Test Fault 1 ± 0.2
9 Current Loop Fault 0 ± 0.2
10 Normal 4 ± 0.2
RS485 MODBUS RTU
The Series 760 Flame Detector is equipped with a two wire, half-
duplex, serial communication interface which supports the MODBUS
RTU protocol. The RS485 MODBUS RTU will allow up to 31 detectors
to be networked to a controller (i.e., customized re panel or personal
computer). The network controller will perform the master duties.
Due to the network being in half-duplex mode, it will only allow one
transmitter to be broadcasting on the network at one time.
The RS485 MODBUS RTU Option
The RS485 MODBUS RTU is enabled when switch 8 is in the “ON”
position. The Flame Detector has to be programmed to a unique
detector number from 1 through 247. The detector number will give
the Flame Detector an address on the network.
Programming the Detector Address Number
This option is activated when switch position 9 is toggled“ON”. The
option is deactivated when the switch is in the “OFF”position. This
option provides the user with a method of programming the unit
number into the non-volatile memory of the microprocessor.
To program the detector address number, rst remove power from
the detector. Then toggle the program option“ON” and use the
remaining eight switches on the User Selectable Interface (USI) to set
the detector address number.
In program mode, the USI becomes a binary programmer as illustrated
in Table 3. When a switch is toggled“ON”, it will equal the binary
weighted number. These binary weighted numbers are added
together when a multiple number of switches are switched“ON” (i.e.,
if SW2 and SW3 were toggled“ON”, then the detector number would
equal a 6)
Table 3: Binary Weight for Switch States “ON”
SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
1 2 4 8 16 32 64 128
When power is applied to the detector, the detector will sense that it is
in program mode and read the eight switch positions. From the switch
setting, it will determine the detector number. Once the number
has been determined, the detector will enter it into the non-volatile
memory of the microprocessor. Next, the amber LED will ash “ON”a
certain number of times equaling the detector address number in the
following manner: the detector will ash the hundreds digit, pause 2
seconds, ash the tens digit, pause 2 seconds, and then ash the ones
digit. Then it will hold the amber LED “ON”constantly for about 10
seconds. Next, the detector will repeat this sequence. This process will
continue for up to 5 minutes.
Once you are sure that the proper number is programmed, then shut
the power“OFF”and reset the USI options to suit your application.
Reference the section on the USI if you are not sure which option is
best for your application or call a Vibro-Meter, Inc application engineer.
Note: In the case that the program option switch is left“ON”and the
detector is installed on network, the detector will go through the same
process as explained previously, but after 5 minutes the detector will
reset and use the last USI setting that it had prior to going into the
program mode.
MODBUS RTU Protocol
A typical MODBUS message or Application Data Unit (ADU), which
is also referred to as a MODBUS RTU Message Frame, as illustrated in
Table 4 consists of a Slave Address byte, a Protocol Data Unit and two
CRC error checking bytes in accordance with the MODBUS standard.
A Slave Address of 0 is used when a message is directed to “ALL” Slave
Devices (MODBUS Broadcast Mode). A Slave address of 1 to 247 is
used when directing a message to a single Slave Device (MODBUS
Unicast Mode).
Table 4: MODBUS Application Data Unit Format
Slave Address Protocol Data Unit CRC Low CRC High
The Protocol Data Unit (PDU) shown in Table 5 consists of a function
code byte and a data eld. The data eld supported by this application
may be empty (no bytes) or it may contain up to two address and two
data bytes.
Table 5: MODBUS Protocol Data Unit Format
Function
Code
Address
High
Address
Low
Data
High
Data
Low
MODBUS RTU Supported Commands
In normal operating mode, the Flame Detector will receive and
respond to the following MODBUS commands listed in Table 6.
Table 6: PDU Supported MODBUS Commands
Supported Commands Function
codes
Addr
high
Addr
low
Data
high
Data
low
Fire & Fault relay status 0x01 0x00 0x00 0x00 0x08
USI Status 0x02 0x00 0x01 0x00 0x08
Fire Delay (EEPROM) 0x03 0x00 0x02 0x00 0x01
Warning Delay
(EEPROM)
0x03 0x00 0x03 0x00 0x01
Fire Occurrences 0x03 0x00 0x04 0x00 0x01
Fault Occurrences 0x03 0x00 0x05 0x00 0x01
Fire Delay (Measured) 0x03 0x00 0x06 0x00 0x01
Warning Delay
(Measured)
0x03 0x00 0x07 0x00 0x01
MODBUS ID# 0x06 0x00 0x08 0x00 0x00
to
0xFF
Clear Fire Occurrences 0x06 0x00 0x09 0x00 0x00
Clear Fault
Occurrences
0x06 0x00 0x0A 0x00 0x00
Software Reset 0x06 0x00 0x0C 0x00 0x06

10
©Firey AB (Oktober 2016)
MODBUS RTU Response
Based on the commands from Table 6, the read functions from the
Flame Detector are functions 1, 2, 3 and 7. In response to these
commands the Flame Detector will follow the PDU format illustrated
in Table 7. For function 6, the Flame Detector will simply echo the
received PDU to acknowledge that the specied command was
performed.
Note: The second PDU byte contains either the number of data bytes
that follow or, in the case of the Exception Status Word, Variable Data
as supplied by the main micro-controller.
Table 7: PDU Formats for Transmission of MODBUS Read Results
Read
Command
Function
Code
See
Note
Variable
Data
Variable
Data
Fire & Fault
relay status
0x 01 0x01 See Table
8
Not Used
USI Status 0x 02 0x01 See Table
9
Not Used
Fire Delay
(EEPROM)
0x 03 0x02 See Table
10
See Table
11
Warning Delay
(EEPROM)
0x 03 0x02 See Table
10
See Table
11
Fire
Occurrences
0x 03 0x02 Hi Byte Lo Byte
Fault
Occurrences
0x 03 0x02 Hi Byte Lo Byte
Fire Delay
(Measured)
0x 03 0x02 See Table
10
See Table
11
Warning Delay
(Measured)
0x03 0x02 See Table
10
See Table
11
Exception
Status Word
0x 07 See Table
12
Not Used Not Used
As illustrated in Table 8, if the relay is energized, the corresponding bit
will be set (1, high). If the relay is de-energized, the corresponding bit
will be cleared (0, low).
Table 8: MODBUS Function 0x01 Read Coil Response
Bit 7:2 Bit 1 Bit 0
Always 0 (Cleared) Fault Relay Status Fire Relay Status
As depicted in Table 9, if the option is active, the corresponding bit will
be set. If the option is not active, the corresponding bit will be cleared.
Table 9: USI Status Bit Denition
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3:2 Bit 1 Bit 0
RS-485
ENQ
0 to
20 mA
Output
Fire
Output
Latch-
ing
War-
ning
Indica-
tion
Sensiti-
vity
Manual
Test
Auto-
matic
Test
Table 10: Byte Denition for Delay Time Whole Number
Bit 7:4 Bit 3:0
BCD of 10’s digit BCD of 1’s digit
Table 11: Byte Denition for Delay Time Decimal
Bit 7:4 Bit 3:0
BCD of tenth’s digit Always cleared
Note: An example using Table 10 and 11; if the delay time is 25.3
seconds, the two bytes transmitted would be 0x25 and 0x30.
As shown in Table 12, the status word has seven alarm bits and one
valid transmission bit. When bits 0 through 6 are at a logic zero, the
alarms are “OFF”. When bits 0 through 6 are at a logic one, the alarms
are “ON”. Bit 7 is always“ON”. If bits 4 through 7 are set to logic one
then the relay coil is open. If bits 3 through 7 are set to logic one then
the non-volatile memory has been corrupted.
If the bits 1, 3 through 7 are all set to a logic one then the re channel
is in exceedance due to saturation either from excessive heating
or cooling. If bits 2, 3 through 7 are all set to a logic one, then the
reference channel is in exceedance due to saturation either from
excessive heating or cooling. If bits 1, 4 and 7 are all set to a logic one,
then the re window is being blocked or the sensor is producing an
illogical signal level as compared to the reference channel. If bits 2, 5
through 7 are set to a logic one, then the reference channel window
is being blocked or the sensor is producing an illogical signal level as
compared to the re channel.
Table 12: Status Word Denition
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Always
On
Manual
Test
Fault
Auto
Test
Ref IR
Fault
Auto
Test
Fire IR
Fault
Milli-
amp
Fault
Ref IR
Warn-
ing
Fire IR
Warn-
ing
Fire
MODBUS RTU Exception Handling
An exception is an error detected by the Flame Detector. If an error
should occur from the received command, the Flame Detector will
respond with a PDU in the form of Table 13.
Table 13: PDU Format for MODBUS Exception Reporting
Exception Function Code Exception Code
(0x80 + MODBUS Function Code) See Table 14
When assembling the PDU to annunciate an error, the Flame Detector
will calculate an Exception Function Code equal to 0x80 plus the
received MODBUS Function Code, i.e. if the MODBUS function was
0x03, the Exception Function Code is 0x83. Table 14 contains the
supported Exception Codes that will be returned depending on the
type of error detected.
Table 14: Supported Exception Codes
Exception Exception
Code
Reporting
Priority
Illegal function requested 0x01 1
Illegal address specied 0x02 2
Illegal data specied 0x03 3
Fire Detector Request
failure
0x04 4

11
©Firey AB (Oktober 2016)
Maintenance and troubleshooting
Note: It is recommended that when cleaning or servicing the Flame
Detector, that any suppression or alarm systems be disabled.
Omniguard® 760 Series Flame Detector is designed for years of
trouble-free operation with minimal attention. Periodic cleaning of
the optical surfaces is essential, however, for maintaining reliable re
protection. The frequency of required cleaning will be determined
by the environmental conditions in and around the installation. The
detectors should be regularly inspected for a build-up of dust or other
contaminants on the optical surfaces.
The detection specications presented in this manual are predicated
on performance with clean sensor windows. Contaminants such as
dust, oil and paint will reduce sensitivity. Severe contamination on the
light guides or sensor windows will cause a failure of the self-test. A
detector that fails self-test due to dirty optical surfaces may be capable
of detecting re, but its eectiveness will be limited to 30 to 50% of its
specied range.
Cleaning Procedure:
Locate the following optical surfaces: (Figure 9)
1. Fire IR Window
2. Fire Light Guide End
3. Reference IR Window
4. Reference Light Guide End
Clean the optical surfaces with a cotton swab wetted with commercial
liquid glass cleaner, ammonia, methanol, or isopropyl alcohol.
Rinse with clean water and dry with lens quality cloth. Repeat with
methanol if needed to remove smudges.
Caution: Wiping with excessive force or inappropriate materials may
scratch the optical surfaces and impair performance.
Troubleshooting:
*WARNING* Do not attempt to repair a detector. Study these
troubleshooting guidelines and review the referenced sections of the
manual prior to performing maintenance on the re detection system.
New Installations:
When the detectors are in operational mode, a green LED will be
visible for one second approximately every ten seconds. If any or
all the detectors fail to operate, check the system wiring and power
supply. Tight, reliable wiring connections are essential, as are low-
resistance connections from every detector housing to earth ground.
Measure the voltage between terminals 8 and 10 at the detector
locations to verify that the supply voltage is within range.
Note: Voltage at detectors installed farthest from power source will be
lower than the no-load supply voltage due to line losses. Maximum
load condition occurs during manual test.
The Omniguard® 760 Series Flame Detectors employ sensitive and
sophisticated electronic circuitry. Power line transients or excessive
power supply ripple may therefore cause erratic or intermittent
operation. DC-powered detectors function best with ripple-free
(less than 1 percent) supply voltage; power supply ltering may be
necessary to improve performance. In areas that are unprotected from
shielding and have the potential for conducted RFI/EMI directly into
the power lines, it is highly recommended to use a Corcom Filter P/N
15DCB6F or equivalent on the power lines.
Note: For reliable operation, the instantaneous supply voltage at the
input to any detector must not fall below 20 Vdc or exceed 30 Vdc.
Failure To Alarm:
Upon detection of re, the re outputs will activate and the red LED,
visible through the LED window, will turn “ON”.
If during testing a detector fails to alarm, inspect the sensor windows
for cleanliness. Clean sensor windows are essential for eective
optical re detection. Clean all the optical surfaces per the cleaning
procedures previously described and retest the detector.
Should the detector continue to be inoperative, check the supply
voltage and all associated wiring. Incorrect power supply voltage or
loose connections will cause marginal or intermittent performance.
Alarm Condition – No Fire Present:
A detector in alarm condition when no re is present may be caused
by an inadvertent actuation of the manual test. The Series 760
Flame Detectors feature a manually initiated self-test feature of the
optical and electronic systems. If the light guides are continuously
illuminated, check the manual test wiring and the test switch for
broken, loose, or intermittent connections. Repair or tighten any faulty
connections. If the light guides are not illuminated, then contact your
Firey AB representative.
Condence Condition:
The Model 760 Flame Detectors are equipped with a fault relay to
annunciate a change in the operational status of the detector. When
power is applied to the detector, the fault relay will energize within 8
seconds under normal environmental conditions. A loss of power will
cause the relay to de-energize.
If the fault relay output fails to change state within 8 seconds after
power-up and the amber LED fails to illuminate, then there may be no
power reaching the detector’s electronic module. Check the supply
voltage, the condition of the fuse located at F1 on the PCB and the
wiring to terminals 8 and 10. Also, inspect the wiring to the fault relay
terminals 6 and 7 and the jumper JP1 that sets the fault relay option.
Note: Model 760 Flame Detectors are equipped with a 0 to 20 mA
option. A loss of power will result in a constant 0 mA output.
If the fault relay output continues to be inoperative, isolate the relay
contacts by disconnecting the external wiring to the fault relay
terminals. Connect an Ohmmeter across the fault relay terminals and
monitor for an actuation of the relay. Repair the external wiring if
necessary.
Fault Condition:
Note: During environmental conditions that cause a large thermal
transient such as moving a detector from inside a warm building to
outside in the cold, the detector will be inoperable until it stabilizes
to the new thermal condition. The fault relay will remain o and the
Amber LED will ash at a 2 Hz rate due to the exceedance until the
detector acclimates to the environment. This will be an indication of an
Exceedance Fault.
Model 760 Flame Detectors are equipped with a 0 to 20 mA output.
When the 0 to 20 mA option is not used, make sure that the 0 to 20
mA option is “OFF”on the USI. If the 0 to 20 mA option is “ON”and at
any time the driveline opens or the current sense is not at the proper
level, it will cause the activation of the fault outputs. Check the
wire terminal 15 and insure that a good signal ground is present at
terminal 10 or 11. To insure that the 0 to 20 mA option causes the fault
(Fig 9) Optical Surfaces

12
©Firey AB (Oktober 2016)
condition, toggle the option on the USI“OFF”and reset the detector by
toggling the power o then on. If the fault condition continues to be
activated, then the problem is in a dierent section.
Note: If the Model 760 is placed near a grey body source with the
equivalence of the object being at a minimum temperature of 150°F
(65°C) from a distance of 22 in. [55.9 cm] and if one of the IR sensor
window is blocked while the other one remains unblocked then the
Amber LED will ash at the rate of 4 Hz until the blockage is removed
from the window’s viewing area. This will be an indication of a Block
Fault
Model 760 Flame Detectors are equipped with automatic self-test
in addition to the manual test. Approximately every 15 minutes
the automatic self-test is actuated, and for a brief time interval, the
optics and electronics are checked for functionality. A failure of
the automatic self-test is annunciated by the activation of the Fault
Outputs. If a detector goes into a fault condition, the optical surfaces
should be checked for cleanliness. Clean sensor windows and light
guide ends are necessary for the detector(s) to pass self-test.
After the optical surfaces have been inspected and cleaned, reset
the detector. If the detector is wired for manual test, perform the
manual test. The typical response time should be to approximately 0.6
seconds beyond the actual re output time delay.
*WARNING* During Manual Test, the re outputs will be actuated.
Always disable re suppression and alarm systems before testing.
If the detector continues to go into a fault condition following a
cleaning of the optical surfaces, check the supply voltage and wiring
at terminals 8 or 9 and 10 or 11. Look for loose or intermittent
connections.
During normal operation, the fault outputs will change state on
power-up. The output will return to its original state if power to the
detector is removed. If the fault output is intermittent or erratic, check
the supply voltage and wiring to terminals 8 or 9 and 10 or 11. Inspect
the fault relay wiring on the detectors. Repair or tighten any loose
connections.
If the Warning option is “ON”, the fault relay will be ashing at a 1 Hz
rate whenever a fault conditions exists.
Manual Test Failure:
*WARNING* This will activate the re outputs. Always disable
extinguishing circuits before testing.
A manual test is activated by connecting the test circuit terminal 12 to
the plus terminal of the detector’s input power supply (terminal 8 or 9).
During manual test, the optical and electronic systems of detector are
checked. Upon successful completion of the test, the re outputs will
be activated. Also, the red LED inside the detector, visible through the
LED window, will turn “ON”. The typical response time is 0.6 seconds
beyond the actual re output time delay. If the detector fails to
respond to a manual test, check to see if the USI manual test option is
“ON”(switch position 1).
If the detector fails manual test and activates the fault outputs or if
the response time is longer than expected, the optical surfaces of the
detector may require cleaning. Clean the sensor windows and light
guide ends. After cleaning, initiate the manual test.
If the detector again fails manual test, check the wiring to the supply
voltage terminals 8 or 9 and 10 or 11. The detector may not be
receiving enough power; the wiring connections may be loose or
intermittent. If the red LED is illuminated and there is no re output,
then check all connections to the re alarm panel or annunciating
devices. A defective test switch may prevent the test circuit from
initializing. Initiate the manual test by connecting a wire from the
test switch terminals to the positive terminal of the input power
supply. Replace the switch if the manual test operates when the wire
is connected.
Warning:
In addition to detecting re, the Omniguard® 760 Series Flame
Detector will annunciate a warning of potentially hazardous
conditions that could cause a re.
When the detector senses a persistent source of infrared radiation
from heat sources the Warning Outputs will change state. To enable
the Warning Outputs for the relay, the Warning option (switch position
5) must be “ON”. When the Warning Outputs are activated, it will cause
the fault relay to be“OFF” and the amber LED to be “ON” constantly.
If the 0 to 20 mA is “ON”, it will set the output to 16 mA for the Fire
IR Warning and 15 mA for the Reference IR Warning. The Warning
Outputs are non-latching and will change states if the problem source
is removed.
This Warning alarm is used as a tool to help prevent unwanted Fire
alarms. By identifying problem heat sources in the detector’s eld-
of-view and making appropriate changes, i.e. shielding or re-aiming
of the detector, potential false re alarms can be avoided. A Warning
should always be investigated with caution. Inspect the protected
area. If no radiation sources are apparent, cover the detector with
opaque material to test whether the Warning disappears when the
sensor windows are blocked. If the Warning does not disappear after
blocking the windows, a sensor channel may be faulty and in need of
repair.
RS485 User Interface (UI)
If no communication has been established, check the wiring to be sure
that the polarity is not reversed on the two wires. The network can
be daisy chained, but it does require two 120 terminating resistors
in order to minimize reections. One resistor should be placed at the
network controller or master device. The other resistor should be
placed at the farthest location from the network controller or master
device. RS485 allows up to 4000 feet or 24 AWG twisted-pair wire
driving into 120 loads. Line polarization should be implemented at
the network controller or master device.
Service and repair
Contact Firey AB or your Firey AB distributor for details on our
customer support and repair services. Prior to returning defective
material, please contact the Firey AB service and repair department
for additional procedural information.
Omniguard® 760 Series Flame Detectors are not eld-serviceable
and the ameproof joints are not intended to be repaired.. An
unauthorized attempt to repair or re-calibrate a detector will void the
warranty.
Detectors should be carefully packaged to avoid damage from shock,
moisture and dust. When shipping detectors back to Firey AB,
use the original shipping carton, if available. If the original packing
material is not available, wrap the detector in plastic and ample
packing material to cushion the detector.
Warranty
The warranty period is thirty-six (36) months for the Omniguard®
760 Series Flame Detectors and ve (5) years for the IR Sensors.
Firey AB will, at its option, repair and return without charge (freight
prepaid) any Omniguard® product, used in accordance with Firey AB
ratings and instructions and conrmed by Firey AB to be defective
in workmanship or materials. This warranty shall be valid only if
the product is returned, within the applicable warranty period, to
the factory at Stockholm, Sweden properly packed and with all
transportation charges prepaid.
All warranty periods commence from the date the product is shipped
to the end user, provided that delivery is within six (6) months of the
date the product was originally shipped from the factory. There are
no warranties of merchantability, tness, or implied warranties of any
kind, or representations for any other Firey AB product, except the
warranty specied herein. In no event shall Firey AB be liable for any
consequential, special, or other damages attributable to our product.
The buyer is solely responsible for the proper installation, maintenance
and use of the Omniguard® Flame Detectors, and agrees Firey AB
is not in any way liable for any special incidental or consequential
damages whatsoever.

13
©Firey AB (Oktober 2016)
Ordering information
Fire type
0 Hydrocarbon/non-hydrocarbon
1 Hydrocarbon (only available with Approval 3)
Housing material/conduit entry
0 Aluminium, 3/4-14 NPT (white)
2 Stainless Steel, 3/4-14 NPT
3 Aluminium, M20-1.5 (white)
5 Stainless Steel, M20-1.5
Test feature
1 Auto self-test
Type:
Omniguard® model 760
Ordering number:
760 - X X X X X
Approval
0FM, SIL2, CSA, Russian Fire Certicate,
IECEx, ATEX, EMC, LVD, CSFM
3SIL2, IECEx, ATEX, EMC, LVD
Fire relay conguration
0 Latching
1 Non-Latching
Designation:
Multi-spectrum infrared ame detector
To order, please specify

14
©Firey AB (Oktober 2016)
Notes

15
©Firey AB (Oktober 2016)

Firey AB
Phone: +46 (0)8 449 25 00
Fax: +46 (0)8 449 25 01
E-mail: omniguardsales@rey.se
www.omniguardbyrey.se
Address
Heliosgatan 3
120 30 Stockholm
Sweden
Publication No. 1031231 Rev. D
Table of contents