Zeta ZT-30P User manual

User Guide of ZT-30P
1
Issue 1 / Rev.1
Flame Detector
Model: ZT-30P
User Guide
Document Ref: GLT-300-7-1
Zeta Alarms Limited
72 –78 Morfa Road, Swansea, SA1 2EN, United Kingdom
Phone: +441792 455 175 Fax: +441792 455 176
Website: www.zetaalarmsystems.com Email: info@zetaalarmsystems.com

User Guide of ZT-30P
2
Issue 1 / Rev.1

User Guide of ZT-30P
3
Issue 1 / Rev.1
<User Guide of ZT-30P>
TABLE OF CONTENTS
<User Guide of ZT-30P> ……....................................................................................................3
1Unpack & Checking Contents ………………………………………………………………………………..……4
2DIP Switch Settings (If Required)…………………………………………………………………………………5
3Install………………………………………………………………………………………………………………………….6
4Operation……………………………………………………………………………………………………………………7
5Operation Technical Specification……………………………………………………………………………….8
LIST OF FIGURES
Figure 1. Product Contents & Outline Indication ............................................................. 4
Figure 2. Change of DIP Switch Setting ............................................................................ 5
Figure 3. Final Installation & Adjustment ........................................................................ 6
Figure 4. Typical 4-Wiring Relay Contact Outputs ........................................................... 9
LIST OF TABLES
Table 1. LED Indications of Operation & Output Status .................................................. 7
Table 2. DIP Switch Settings ............................................................................................ 8

User Guide of ZT-30P
4
Issue 1 / Rev.1
1 Unpack & Checking Contents
- Unpack the delivered pack and check the following contents.
Figure 1. Product Contents & Outline Indication

User Guide of ZT-30P
5
Issue 1 / Rev.1
2 DIP Switch Settings (If necessary)
1). After removing the Sunshade, separate TOP Cover & Base cover and change the
Setting of the DIP Switch.
Figure 2. Change of DIP Switch Setting
2). After completing the change of DIP Switch Setting, combine the TOP Cover and
BASE Cover by screwing together.
Make sure that they are screwed together securely otherwise the detector may
fail to be waterproof.

User Guide of ZT-30P
6
Issue 1 / Rev.1
3 Installation
1). Shown Fig.3, after screwing Top / Base Covers & Sunshade, place the detector in
its designated locations on the wall and secure it with the provided three (3)
fasteners through three (3) holes of detector mounting bracket.
Release the locking three (3) “Hexagonal Socket Set Screws” in such a way that
allows rotating detector and point the detector towards the protected area and
make certain the view of area I unobstructed.
Secure the detector that position by tightening the locking three (3) “Hexagonal
Socket Set Screws” on the mounting bracket.
Figure 3. Final installation & Adjustment

User Guide of ZT-30P
7
Issue 1 / Rev.1
The Detector is now correctly located, aligned and ready to be connected to the
system.
4 Operation
Once powered up, the detector will begin appr. 20 sec start-up routine. During
this time, all three (3) LED indicators will be blinking. Once the start-up
procedure has finished and no faults are present, the detector will begin normal
operation (Green LED will remain on).
Table1. Output Signals/LED Indicator versus Detector State
Detector Status
Green
LED
(Power)
Red
LED
(Alarm)
Yellow
LED
(Fault)
Power Up –20 Second Start
Flicker
Internal Power Fault or System Power
Out of Range / Fault
Off
Off
Blinking
Normal Operation (Stand-By)
On
Off
Off
Fire Detection (Warning)
Off
On
Off
Fire Confirmed
All LEDs Blinking Simultaneously

User Guide of ZT-30P
8
Issue 1 / Rev.1
Table 2. DIP Switch Settings
DIP Switch Position No.
Mode Selections
1
2
3
4
5
6
Sensitivity Range (1)
OFF-OFF(00) : Highest
OFF-ON(01) : High
ON-OFF(10) : Medium <default>
ON-ON(11) : Low
Alarm Delay Time (2)
OFF-OFF(00) : 1 Sec
OFF-ON(01) : 3 Sec
ON-OFF : 7 Sec <default>
Alarm Latch Setting (3)
OFF(0) : 20 Sec <default>
ON(1) : Until Reset
Reserved (for design Setting)
OFF(0) : <default>
Notes:
(1). The detector offers four (4) sensitivity settings. The settings refer to the n-Heptane fore of
33 cm-sq.
(2). When an Alarm (Detection) level condition is encountered, the detector delays the
execution of the Alarm output relay by the specified period of time. The detector will then,
additionally, evaluate the fire condition during the specified Alarm Delay Time. If the Alarm
level is still present, the Alarm outputs will be activated. If this condition no longer exists,
the detector will return to its standby state. The LED will indicate warning level during the
delay time only if the fire condition exists.
(3) The detector has a selectable latched alarm output capability, which operates according to
the selectable function. If selected, upon the detection of a fire, the detection signal is
latched until manually reset (disconnecting the power supply or performing a manual BIT).
Latching affects the ALARM RELAY, 4-20mA output, the ALARM LED…

User Guide of ZT-30P
9
Issue 1 / Rev.1
Notes: 1. ( ): denotes an example of optional colour wirings.

User Guide of ZT-30P
10
Issue 1 / Rev.1
5 Techncial Specification
Model
ZT-30P
Part Number
47-156
Spectrum Response
UV/IR (Dual Bands)
Spectrum Response
(at highest sensitivity setting for
0.1m2pan fire)
Fuel
n-Heptane
Gasoline
Diesel
LPG*
Ethanol
IPA
Methane**
Distance
30m
30m
20m
20m
20m
25m
20m
*0.5m high/0.2m width plume fire, **30” plume fire
Response Time
Typically 5 seconds
Adjustable Time Delay
Up to 20 seconds
Sensitivity Range
4 sensitivity ranges for 0.1m2 n-Heptane pan fire from 15m to 65m
Field of View
Horizontal / Vertically Typical 120º & 120º Max
Built-in-Test
Automatic self-check to verify the lens cleanliness/electronic circuits & etc
Temperature Range
Operating/Storage:-40ºC to 75ºC
Humidity
Up to 95% non-condensing
Operating Voltage
24VDC nominal (18-32VDC)
Power Consumption
Standby: max. 50mA, Alarm: max. 70mA
Cable Entry
1 x Ø6mm
Wiring
According to the requirements
Electromagnetic Compatibility
Complies with EN 61000-6-4 and EN 50130-4
Electrical Interface
4-Wiring relay contact outputs
Relays
Alarm(N.O.), Fault(N.C)
SPST volt-free contacts rated 5A at 30VDC or 250VAC
RS-485 (option)
RS-485 Modbus compatible communication link that can be used in computer
controlled installations

User Guide of ZT-30P
11
Issue 1 / Rev.1
Materials
Heavy duty copper free aluminium with white powder coating
Mounting (Tilt Mount)
Heavy duty copper free aluminium with white powder coating
Dimensions
Detector 63(D) x 110 (L) mm
Weight
Detector & Mounting Bracket (Aluminium): 0.3kg
Water and Dust
IP65
EMI/RFI
EN61000
Hazardous Area
N/A
Performance
Designed to meet FM3260 (EN54-10)
- END -