• This manual provides important safety-related information. Thoroughly read and understand
this manual before installing and using the product.
• Keep this manual in a convenient location so that you can refer to it whenever necessary.
BU1002SWG / BU3002SWG
Uninterruptible Power Supply (UPS/220 to 240V specications)
Instruction Manual
-
バッテリ
交換
バッテリ
増設
電源出力
バイパス
運転
BU1002SWG
BU3002SWG
STATU S
POWER ON/OFF
BEEP STOP/TEST
BYPASS
BATT ERY
WEAK
OUTPUT
LOAD/
BATTERY
STATU S
POWER ON/OFF
BEEP STOP/TEST
BYPASS
BATT ERY
WEAK
OUTPUT
LOAD/
BATTERY

Introduction
Features of this product
Thank you for purchasing Omron's Uninterruptible Power Supply (UPS).
●The UPS protects computers and other devices from power failures, voltage variations,
instantaneous voltage drops, and surge voltage such as that caused by lightning (a
phenomenon in which extraordinary high voltage occurs instantaneously).
●
This unit is an uninterruptible power supply (UPS) with power supply output of 220 to 240V AC.
●Under normal conditions, it converts the commercial power to a direct current once,
reconverts it to a stable AC sine wave, and outputs it.
When a commercial power failure is detected, the unit switches to battery supply to
provide continuous sine wave output. This is especially suitable for use where power
supply conditions are poor (for example, when there are large variations in voltage).
●
BU1002SWG output capacity is 1000VA/700W, and BU3002SWG output capacity is 3000VA/2100W.
©OMRON Corporation. 2017 All Rights Reserved.
Notes on the use of the Backup Power Supply
●This product is designed and manufactured for use for FA, OA equipment such as
personal computers.
Do not use it when very high reliability and safety are required as listed below.
• Medical equipment that may cause death directly
• Applications that may cause injury (applications that directly affect the operation and
control of planes, ships, railroads, elevators, and so on)
• Applications that are always subjected to vibration such as cars and ships
• Applicationsinwhichafailureofthisproductmaycausesignicantdamageoreffectto
the society and public (important computer systems, main communication equipment,
public transportation systems, and so on)
• Equipment with the same level of importance
●For equipment that greatly affects the safety of people and maintaining public functions,
special considerations related to operation, maintenance, and management must be taken
such as duplicating the system and emergency power generation facilities.
●Observe the contents of this manual such as the use conditions and environments.
●When you want to use this product for an important system that requires very high
reliability, contact Omron representatives.
●Do not modify/alter this product.
●Make sure to read the safety precautions before using the unit.
●In the event you transfer or sell this unit to a third party, please include all of the
documentation that came with this unit. This is to ensure that the unit is used in line with
the conditions described in the included documentation.
• This manual contains important safety-related information. Please read and understand
the contents of the manual before beginning operation.
If you discover any omissions or errors in the manual, please contact the shop of
purchase.
●Windows is the registered trademark of Microsoft Corporation in the United States and/or other
countries.
●The names of other companies and products mentioned herein are the trademarks or
registered trademarks of their respective owners.
Disclaimers
We are not liable for any damage or secondary damage resulting from the use of our product,
including malfunction and failure of equipment, connected devices, or software.

IMPORTANT SAFETY INSTRUCTION
1.SAVE THESE INSTRUCTIONS.
This manual contains important instructions for BU1002SWG that
should be followed when using the UPS and batteries.
2.SYMBOL
This symbol indicates earth ground.
This symbol indicates turning on UPS.
This symbol indicates turning off UPS.
3.INTERNAL BATTERY
Internal battery voltage is 36V DC for BU1002SWG and 72V DC for
BU3002SWG.
4.TEMPERATURE RATING
The maximum ambient temperature of the UPS is 40°C.
5.ENVIRONMENT
The unit is intended for installation in a temperature controlled, indoor
area free of conductive contaminants.

BU1002SWG / BU3002SWG
i
Procedure from installation to operation
Start
Installation/connection
Preparation for operation
Maintenance/
inspection
Yes
No
No
Yes
Read “Safety precautions”
Page iii
Remove the product from the
package and check the contents
Page 1
Perform installation and
connection Page 6
Check the operation and
displays Page 22
Charge the battery
Page 24
Measure the backup time
Page 24
Read “Using the UPS
monitoring software and
contact signal” Page 55
Operate Page 25
Deteriorated
battery?
Perform maintenance
and inspection Page 44
Replace the battery
Page 46
Are you
using UPS monitoring
software or contact
signal?
Charge the battery again
Page 24
* Preparation for operation is
complete.

ii
Table of Contents
■ Table of Contents ■
Introduction
Important safety instruction
Safety precautions............................................................................................................................................. iii
1. Preparation................................................................................................................................ 1
1-1 Unpacking the product................................................................................................................................... 1
1-2 Checking the contents ................................................................................................................................... 1
1-3 Name of each part ......................................................................................................................................... 2
1-4 Explanation of symbols used on unit ............................................................................................................. 5
2. Installation and connection........................................................................................................ 6
2-1 Precautions and notes on installation and connection .................................................................................. 6
2-2 Installation and connection .......................................................................................................................... 10
2-3 Connecting the equipment........................................................................................................................... 13
2-4 Checking the operation................................................................................................................................ 22
2-5 Charging the battery .................................................................................................................................... 24
2-6 Measuring the initial value of backup time................................................................................................... 24
2-7 Recharging the battery ................................................................................................................................ 24
3. Operation................................................................................................................................. 25
3-1 Precautions and notes for operation............................................................................................................ 25
3-2 Start and stop procedures and basic operation........................................................................................... 27
3-3 Interpreting beeps and displays................................................................................................................... 30
4. UPS functions.......................................................................................................................... 32
4-1 Suspending a beep...................................................................................................................................... 32
4-2 Self-diagnosis test ....................................................................................................................................... 32
4-3 Description of the auto battery test function ................................................................................................ 33
4-4 Changing the setting of the functions .......................................................................................................... 33
5. Measuring the backup time ..................................................................................................... 42
5-1 How to measure backup time ...................................................................................................................... 42
5-2 Estimated backup time ................................................................................................................................ 42
6. Maintenance and Inspection ................................................................................................... 44
6-1 Checking the battery.................................................................................................................................... 45
6-2 Replacing the battery................................................................................................................................... 46
6-3 Cleaning ...................................................................................................................................................... 54
7. Using the UPS monitoring software and contact signal .......................................................... 55
7-1 When using the included UPS monitoring ......................................................................................................
software to perform auto shutdown ............................................................................................................. 57
7-2 When performing auto-save functions using the UPS service in Windows Server 2003/XP/2000 +
UPS service driver....................................................................................................................................... 60
7-3 Contact signal (SC07: NPN output)............................................................................................................. 61
7-4 Contact signal (SC08G: PNP output) .......................................................................................................... 67
8. Using an SNMP/Web card....................................................................................................... 75
8-1 Adding an SNMP/Web card......................................................................................................................... 75
8-2 SNMP/Web card outline .............................................................................................................................. 76
9. Troubleshooting....................................................................................................................... 78
Reference.................................................................................................................................... 79
A. Specications................................................................................................................................................ 79
B. Dimensions ................................................................................................................................................... 80
C. Circuit block diagram .................................................................................................................................... 81
D. Related products........................................................................................................................................... 81

iii
BU1002SWG / BU3002SWG
: Indicates prohibition. For example, indicates that disassembly is prohibited.
: Indicates obligation. For example, indicates that grounding is necessary.
Misuse may cause death or serious injury.
Warning
Caution
Safety precautions
●The safety symbols and their meaning used in this manual are as follows:
* Property damage means damage to houses/household effects, livestock, and pets.
Note that events categorized as a caution required matter also may cause more serious results under certain
conditions.
Do not use this unit when very high reliability and safety are required as
listed below. This unit is designed and manufactured for use with FA, OA
equipment such as personal computers.
●Medical equipment or system that may cause death directly.
●Applications that directly affect the safety of people (For example, the operation and control
of cars and elevators).
● Applicationsinwhichafailureoftheunitmaycausesignicantdamagetothesocietyand
public (For example, essential computer systems and main communication equipment.)
●Applications with the same level of importance.
Warning
Important information for safe operation is described.
Be sure to read it before installation and start of use.
Misuse may cause injury or property damage.
Two or more people should work together to carry, unpack and install
the BU3002SWG.
●Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.
Carry the unit considering its weight and balance, and place it on a stable
and robust base.
●Dropping or toppling the unit may cause injury.
●Approximate weight of the unit:
15.5 kg (BU1002SWG)
35 kg (BU3002SWG)
●If you drop the unit, stop using it and have it inspected and repaired.
For repair, contact Omron representatives.
Keep plastic package bags out of reach of children.
●Children may suffocate if they place their heads into plastic bags.
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage (220 to 240V AC).
●Connecting to a wall outlet (commercial power) of a different rated input voltage may result
inre.
●The unit may fail.
Caution (for installation and connection)

Safety precautions
iv
When an abnormality (unusual sound or smell) occurs, turn OFF the unit's
power switch and disconnect the AC input plug from the wall outlet.
Install the unit soon after the AC input plug is disconnected from the
wall outlet.
●When performing maintenance on the connected devices, follow the above instructions to
ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc. ,
which have a half-wave rectier that allows only half-cycle AC power to
ow through.
●Overcurrent may damage the UPS.
Connect the BU1002SWG to a wall outlet (commercial power) with a
capacity of 5.8A or more, and connect the BU3002SWG to a wall outlet
(commercial power) with a capacity of 16A or more.
●Otherwise, the power cord may be heated.
●When equipment with the maximum output capacity is connected, a maximum current of
5.8A (BU1002SWG) or 16A (BU3002SWG) flows.
Provide secure grounding.
●After checking the plug shape of the wall outlet, directly connect the AC input plug of the
unit to it. A failure or leak that occurs when the unit is not properly grounded may result in
electric shock.
Do not disassemble, repair, or modify the unit.
●Doing so may cause an electric shock or a fire.
Do not install the unit in other than specied orientations.
●Dropping or toppling the unit may cause injury.
● Ifyouinstalltheunitinanorientationotherthanspecied,theunitcannotbeprotectedfrom
abatteryuidleakage.
Do not use the unit where the maximum temperature exceeds 40°C.
● Thebatterybecomesweakrapidly,whichmaycauseare.
●Doing so may cause a failure or malfunction of the unit.
Do not exceed the ranges specied for environmental conditions during
use/storage.
Do not install or store the unit in the places listed below.
●Do not store in places where the humidity is lower than 10% or higher than 90%.
●Do not use in places where the humidity is lower than 25% or higher than 85%.
●Do not install/store the unit in closed places such as cabinets with no clearance, places
wherethereisammableorcorresevegas,placeswithlargeamountsofdust,placesex-
posed to direct sunlight, places exposed to shock or vibration, or outdoors.
●Installation or storing the unit in such a place may cause a fire.
Do not connect equipment that exceeds the output capacity of the unit.
You can use a 220V plug strip to connect additional devices, but do not
connect devices that exceed the current capacity of the plug strip.
●The current protection of the unit may operate, which may stop the output.
●The wiring of the plug strip heats up, which may cause a fire.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.
●Doing so may cause the cable to be damaged or heated, which may cause an electric
shockorare.
●If the cable is damaged, stop using the unit and have the cable repaired.
For repair, contact Omron representatives.
Caution (for installation and connection)

v
BU1002SWG / BU3002SWG
Caution (for installation and connection)
All of the included accessories are designed to be used exclusively with
the unit. Do not use the accessories with other devices.
●Doing so may compromise the safety of devices.
●This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit
The unit contains no user serviceable parts. Only factory service personnel may perform
repairs.
●Connection to any other type of receptacle other than a two-pole,three-wire grounded
receptacle may result in shock hazard as well as violate local electical codes.
●Do not allow liquids or any foreign object to enter the UPS. DO not place beverages or any
other liquid-containing vessels on or near the unit.
●This unit intended for installation in a controlled environment (temperature controlled, indoor
area free of conductive contaminants). Avoid installing the UPS in locations where there is
standing or running water,or excessive humidity.
●Do not attach a power strip or surge suppressor to the UPS.
●Do not attach non-computer-related items,such as medical equipment,life-support
equipment,microwave ovens,or vacuum cleaners to UPS.
●With the installation of the equipment it should be prevented, that the sum of the leakage
current of the UPS and the connected consumer does not exceed 3.5mA.
Do not block the air vents on the unit. The BU1002SWG has air vents
on the front, side and back, while the BU3002SWG has air vents on the
front and back.
●Doing so will cause the internal temperature to rise, which may cause the unit to fail and the
battery to deteriorate.
●Leave at least 5 cm of space between the vent and the wall.
Do not connect a standalone transformer such as a voltage transformer
or isolating transformer to the output side.
●Overcurrent may damage the UPS.
●There is no problem in connecting a transformer to the input side.
Do not connect devices that cannot be used with commercial power
supply.
●When the unit’s power switch is turned ON and an error occurs with the connected device,
bypass operation is performed and commercial power supply is supplied as is to the
connected devices.
Do not connect devices with rated voltage of 220 to 240 VAC or higher.
●The rated output voltage of this device is 220 to 240 VAC.
●Overcurrent may damage the connected devices.
When in use, make sure the output terminal block cover is attached.
Do not turn ON the power switch when it is detached.
●Voltage is applied to the output terminal block when the power switch is ON, which can
result in electric shock.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installer near
the equipment and shall be easily accessible.

Safety precautions
vi
Caution (for use)
Never touch the metal part of the input plug if it is disconnected while
the unit is operating.
●Doing so may result in electric shock.
●The leak current of this product itself is less than the value of the safety standard (leak
current: 1 mA). However, because connected equipment causes the leak current to
increase, you must never touch the metal part of the input plug.
●When the unit is operating, voltage is generated in the metal parts of the input plug via
capacitors in the internal circuit, regardless of the elapsed time.
Do not allow the unit to come in contact with water.
● Doingsomaycauseanelectricshockorare.
●If the unit becomes wet, stop using it and have it inspected and/or repaired.
For repair, contact Omron representatives.
When the battery is dead, replace it immediately or stop using the unit.
●Continuing the use of it may cause a re.
Using a dry cloth, periodically wipe the dust from the AC input plug,
power supply output receptacles and output terminal block.
● Accumulateddustmaycauseare.
Do not use the unit in a closed place and do not cover the unit.
● Doingsomaycauseabnormalheatingorare.
If you notice abnormal sound or smell, smoke, or leakage from the
inside, immediately turn off the power switch and disconnect the AC
input plug from a wall outlet (commercial power).
● Usingtheunitundersuchconditionsmaycauseare.
●
If you notice such a condition, stop using the unit and contact Omron representatives for inspec-
tion and repairs.
●Use the unit under the conditions in which you can immediately disconnect the AC input
plug from a wall outlet (commercial power) in the case of an abnormal event.
If uid leaks from the unit, do not touch the uid.
●Doing so may cause blindness or burns.
●
If the uid contacts your eyes or skin, wash it out with lots of clean water and consult your
doctor.
Do not place objects heavier than 25kg on the unit, and do not drop
heavy objects onto the unit.
●Doing so may cause distortion/damage to the case or a failure of the internal circuit, which
maycauseare.
* The values in the table are the expected life under standard
use conditions and are not guaranteed.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years
2 to 2.5 years

vii
BU1002SWG / BU3002SWG
Caution (for maintenance)
When maintaining the connected equipment, turn OFF the power switch
and disconnect the AC input plug.
● Even if you disconnect the AC input plug while the UPS is operating, the power output of
this unit does not stop and power is supplied from the outlet during a power failure.
Do not disassemble, repair, or modify the unit.
●Doing so may cause an electric shock or a fire.
If uid leaks from the unit, do not touch the uid.
●Doing so may cause blindness or burns.
●
Iftheuidcontactsyoureyesorskin,washitoutwithlotsofcleanwaterandconsultyourdoctor.
Do not throw the unit into re.
●The lead battery in the unit may explode, or leak dilute sulfuric acid.
Do not insert metal objects into the power supply output receptacle or
terminal block of the UPS.
●Doing so may result in electric shock.
Do not insert metal objects into the battery connectors.
●Doing so may result in electric shock.
Caution (for battery replacement)
Perform replacement on a stable and at place.
●Handle the battery carefully so that you do not drop it.
●Not doing so could cause injury or burns due to liquid (acid) leakage.
Use a specied battery for replacement.
● Notdoingsomaycauseare.
●Product model: BP100XSG (Replacement battery pack for BU1002SWG)
BP150XSG: Two required (Replacement battery pack for BU3002SWG)
Do not replace the battery in a place where there is ammable gas.
● Sparkmayoccurwhenconnectingthebattery,whichmaycauseanexplosionorre.
If uid (dilute sulfuric acid) leaks from the battery, do not touch the uid.
●Doing so may cause blindness or burns.
●If it contacts your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not disassemble or modify the battery.
●Doing so could cause dilute sulfuric acid leak, which could cause blindness and burns.
Do not drop the battery and do not expose it to strong impact.
●Dilute sulfuric acid may leak.
Do not short the battery with metal objects.
● Doingsocouldcauseanelectricshock,reorburn.
●Some electrical energy still remains inside the spent battery.

Safety precautions
viii
Caution (for battery replacement)
Do not put the battery into re and do not break it.
●The battery may explode or leak dilute sulfuric acid.
Do not use a new battery and an old battery at the same time.
●Dilute sulfuric acid may leak.
●A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting batteries terminals.
●Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from batteries.

ix
BU1002SWG / BU3002SWG
Notes
When moving the unit from a cold place to a warm place, leave it for several hours
before using it.
●If the unit is promptly turned ON after being moved to a warmer place, condensation may form inside the
unit and cause it to fail.
Charge the battery for at least 8 hours soon after purchasing the unit.
●If you do not use the unit for a long time after the purchase, the battery may deteriorate and the battery
may become unusable.
●To charge a battery, connect the AC input plug of the unit to a wall outlet (commercial power).
When storing the unit, charge the battery for at least 8 hours and turn OFF the power
switch.
●Even if the unit is not used, the battery gradually discharges, and if it is left for a long time, it goes into an
over discharge state.
The backup time may become shorter or the battery may become unusable.
●We recommend keeping the temperature 25°C or less when storing the unit for long periods of time.
Connect the unit’s AC input plug to a wall outlet (commercial power) for at least 8 hours at the following
intervals:
- Every 6 months when storage temperature is 25°C or less
- Every 2 months when storage temperature is 40°C or less
●Turn off the power switch of the unit during storage.
Do not short the output lines of the unit to each other, and do not short the output
lines to the ground.
●The unit may fail.
Do not connect the AC input plug of the unit to its Power Supply Output Receptacle
during the Battery Mode.
●The unit may fail.
Do not connect a page printer (such as a laser printer) to the unit.
●The unit repeatedly and frequently switches between Commercial Power Mode and Battery Mode, which
may shorten the life of the battery.
●The page printer has a large peak current, so an excess of the connection capacity or a power failure due
to instantaneous voltage drop may be detected.
Check system operation beforehand if the unit is used in combination with a device
whose power supply frequency fluctuates widely, such as a personal electric
generator.
●The unit automatically recognizes the input power frequency when input power is supplied. If the unit
is connected when the input power frequency is not stable at the rated level, the unit may misidentify
the power supply frequency and may fail to operate normally. (If the unit is in operation, changing from
commercial power supply to another power supply source, such as generating equipment, will cause no
problem. Set the generator's frequency to the same level as that of the commercial power supply.)
Do not install or store the unit in a place exposed to direct sunlight.
●The rise of temperature may cause the built-in battery to deteriorate rapidly and become unusable.
Do not perform a withstand voltage test.
●The input circuit has a built-in surge absorption device. A withstand voltage test may break it.
●When performing an insulation resistance test, use the 400V DC range.
Before stopping the commercial power to the unit, turn OFF the power switch of the
unit.
●The unit enters Battery Mode when commercial power is stopped. If you frequently use the unit in Battery
Mode,thebatterylifemaybesignicantlyshortened.

Safety precautions
x
See also
Notes
Check the operation beforehand if the unit is used in any mode other than “Output
220V mode”.
●In Battery Mode, the maximum voltage (peak voltage) of output (rectangular wave) may be lower than
the maximum voltage in Commercial Power Mode. For this reason, some connected devices may fail to
operate normally.
If this unit is used with an inductive device such as a coil or motor, check the
operation beforehand.
●With some types of devices, the effect of inrush current may cause this unit to stop operating properly.
In the event you transfer or sell this unit to a third party, please include all of the
documentation that came with the unit. This is to ensure that the unit is used in line
with the conditions described in the included documentation.
●This manual contains important safety-related information. Please read and understand the
contents of the manual before beginning operation.
Take measures for handling unforeseen accidents, such as data backup and
system redundancy.
●The output may stop when there is a circuit failure in the UPS.
This unit uses lead acid batteries,
●Which are a valuable recyclable resource. Please recycle.
Pb
Explanation
Usual operation
●You may either leave the power switch of the unit ON (operation status) or turn it OFF each time when
stopping the connected system. Choose whichever operation method is more convenient. We recommend
turning OFF the power switch when you do not use connected devices for a long time.
●
The battery can be charged once the AC input plug of the unit is connected to a wall outlet (commercial
power).
Quitting Battery Mode
● If a power failure lasts for an extended period of time, the battery discharges and power output from the
unit stops. Shut down your computer after performing appropriate procedures (for example, saving data)
while the unit is still supplying power.
Rebooting
●If the battery discharges completely during a power failure, the unit stops. After recovery from the power
failure, the unit automatically restarts and supplies power. If you do not want to restart the connected
devices, turn OFF the power switch of either the unit or the connected devices.
Setting switch 2can be used to select whether or not auto restart is performed. See Page 34
Scheduled operation using the UPS monitoring software
●When performing scheduled operation in which the UPS is stopped and a device such as a breaker is
used to stop the UPS at the same time that commercial power stops, specify a period of no more than 3
months for the start of the next operation.
If you specify a period longer than 3 months, the internal timer is reset and the scheduled operation does
not start. Note that this period reduces to approximately half when the battery is dead. If a period of 3
months is exceeded, you start operation by supplying commercial power and pressing the start switch.
However, if the battery is dead, you may not be able to start operation.
In this case, replace the battery according to the instructions in “6-2 Replacing the battery” on page 46.

1
1
2
3
4
5
6
7
8
9
10
BU1002SWG / BU3002SWG
Check whether all the package contents are included and there is no damage found on their appearance.
If you should notice defects or anything wrong, contact Omron representatives.
(1) Accessories related to the main unit
(2) UPS monitoring software related items
Open the package box and take out the UPS and accessories.
Two or more people should work together to carry, unpack and install
the BU3002SWG.
●Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.
The weight of the product is 15.5 kg (BU1002SWG) , 35 kg (BU3002SWG).
Unpack/transport this product considering this weight.
●Dropping may cause injury.
Caution
Manual Sheet Quick installation
guide
CD-ROM
Connection cable(USB)
(Approx. 2.2 m)
<Accessories related to main unit> <UPS monitoring software>
Connector for
remote
ON/OFF
Compliance
Information
Sheet
Contact
signal card
(SC08G)
Connection cable(RS-232C)
(Approx. 2.2 m)
Terminal block cover
for BU1002SWG
(with cable clamp)
Terminal block cover
for BU3002SWG
(with cable clamp)
1-1
Unpacking the product
Preparation
1
1-2
Checking the contents
BU1002SWG BU3002SWG
Manual Sheet 1
Connector for remote ON/OFF 1
Terminal block cover for output (with cable clamp) 1
Compliance Information Sheet 1
Contact signal I/O card (SC08G) 1
BU1002SWG BU3002SWG
Quick installation guide 1
CD-ROM 1
Connection cable (RS-232C) 1
Connection cable (USB) 1

2
1. Preparation
This section describes the name of each part of the UPS.
For information on the function of each part, refer to "2. Installation and connection" on page 6 and "3.
Operation" on page 25 that provides the details.
Front view
[ Enlarged view of the display panel ]
BU1002SWG
STAT US
POWER ON/OFF
BEEP STOP/TEST
BYPASS
BAT TER Y
WEAK
OUTPUT
LOAD/
BATTERY
A. Status indicator digital display
B. Power switch
C. Beep stop/test switch
D. Battery replacement lamp
E. Power supply output lamp
F. Bypass operation lamp
(The input power supply is output as is.)
G. Setting switch cover
H. Connection capacity/battery level meter
STATUS
POWER ON/OFF
BEEP STOP/TEST
BYPASS
BATTERY
WEAK
OUTPUT
LOAD/
BATTERY
A
H
B
C
G
FE D
<BU1002SWG>
STAT US
POWER ON/OFF
BEEP STOP/TEST
BYPASS
BAT TERY
WEAK
OUTPUT
LOAD/
BATTERY
BU3002SWG
<BU3002SWG>
<Display panel>
(Carrying handle)
(Air vent)
1-3
Name of each part

3
1
2
3
4
5
6
7
8
9
10
BU1002SWG / BU3002SWG
Side view
Air inlet
Rear side
Front side
Rear side
Front side
<BU1002SWG>
<BU3002SWG>

4
1. Preparation
Rear view
A. USB connector
B. RS-232C connector
C. Contact signal card (SC07)
D. Contact signal connector
E. Remote ON/OFF connector
F. Power supply output receptacle A (IEC60320 C13)
G. Power supply output receptacle B (IEC60320 C13)
H. Power supply output receptacle C (IEC60320 C13)
I. Terminal block for output
J. Grounding terminal
K. AC input cable
L. AC input overcurrent protection
M. Cooling fan
<BU1002SWG>
A
J
L
K
M
B C D
E
F
H
G
I
USBRS232C
OPTION SLOT
OUTPUT
AC220-240V
50/60Hz 4.6A Max 1φ3W
OUPUT POWER
1kVA / 700W Max.
AC INPUT
OVER CURRENT
PROTECTION 10A
INPUT AC220-240V
50/60Hz 5.8A 1φ3W
COOLING FAN
Uninterruptible Power Supply
MODEL : BU1002SWG
Rated Voltage: AC220-240V
Max. Current: 5.8A Rated Freq.:50/60Hz
GND
B
A
C
G
CB
L2CL2B L1CL1B
OMRON CorporationMADE IN TAIWAN
A B C D
S
F
E
I
H
G
J
K
R
L
M
N
O
P
O
P
Q
OUTPUT
AC220-240V
50/60Hz 15A
Max. 1φ3W
OUPUT POWER
3kVA / 2.1kW
(OUT-Total)
OUT
USB RS232C
OPTION SLOT
A (C19)
OUTA (C13)
OUT
B
(C13)
OUT
C
(C13)
OUTPUT
OUT(-)
OVER CURRENT
PROTECTION
15A
AC INPUT
OVER CURRENT
PROTECTION
20A
INPUT AC220-240V
50/60Hz 16A Max 1φ3W
OUPUT TERMINAL BLOCK
GND
COOLING FAN
COOLING FAN
Uninterruptible Power Supply
MODEL : BU3002SWG
Rated Voltage: AC220-240V
Max.Current: 16A Ra ted Freq.:50/6 0Hz
OMRON Corporation MADE IN TAIWAN See Installation Instractions
before connecting the supply.
Not for Current Interrupting.
<BU3002SWG>
A. USB connector
B. RS-232C connector
C. Contact signal card (SC07)
D. Contact signal connector
E. Remote ON/OFF connector
F. Handle
G. Power supply output receptacle A (IEC60320 C19)
H. Power supply output receptacle A (IEC60320 C13)
I. Power supply output receptacle B (IEC60320 C13)
J. Overcurrent protection switch for output 15A
K. Power supply output receptacle C (IEC60320 C13)
L. AC input overcurrent protection switch 20A
M. AC input cable
N. Terminal block for output
O. Fixed stand
P. Casters
Q. Grounding terminal
R. Cooling fan
S. Additional battery connector (No use)

5
1
2
3
4
5
6
7
8
9
10
BU1002SWG / BU3002SWG
Symbol Description
Start the UPS.
Stop the UPS.
Suspend a beep.
UPS output power enabled, supplied by operating on line mode, battery mode.
UPS operating on bypass mode.
Batteries at end of useful life, necessary to replace the batteries.
1-4
Explanation of symbols used on unit

6
2. Installation and Connection
Two or more people should work together to carry, unpack and install
the BU3002SWG.
●Because the unit is heavy, you may injure yourself or drop the unit, or it may fall over.
Carry the unit considering its weight and balance, and place it on a stable
and robust base.
●Dropping or toppling the unit may cause injury.
●Approximate weight of the unit:
15.5 kg (BU1002SWG)
35 kg (BU3002SWG)
●If you drop the unit, stop using it and have it inspected and repaired.
For repair, contact Omron representatives.
Keep plastic package bags out of reach of children.
●Children may suffocate if they place their heads into plastic bags.
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage (220 to 240V AC).
●Connecting to a wall outlet (commercial power) of a different rated input voltage may result
in re.
●The unit may fail.
When an abnormality (unusual sound or smell) occurs, turn OFF the
unit's power switch and disconnect the AC input plug from the wall
outlet.
Install the unit soon after the AC input plug is disconnected from the wall
outlet.
●When performing maintenance on the connected devices, follow the above instructions to
ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc. ,
which have a half-wave rectier that allows only half-cycle AC power to
ow through.
●Overcurrent may damage the UPS.
Connect the BU1002SWG to a wall outlet (commercial power) with a
capacity of 5.8A or more, and connect the BU3002SWG to a wall outlet
(commercial power) with a capacity of 16A or more.
●Otherwise, the power cord may be heated.
●When equipment with the maximum output capacity is connected, a maximum current of 5.8A
(BU1002SWG) or 16A (BU3002SWG) flows.
Provide secure grounding.
●After checking the plug shape of the wall outlet, directly connect the AC input plug of the
unit to it. A failure or leak that occurs when the unit is not properly grounded may result in
electric shock.
Do not disassemble, repair, or modify the unit.
● Doing so may cause an electric shock or a re.
Caution (for installation and connection)
2-1
Precautions and notes on installation and connection
Installation and connection
2

7
1
2
3
4
5
6
7
8
9
10
BU1002SWG / BU3002SWG
Caution (for installation and connection)
Do not install the unit in other than specied orientations.
●Dropping or toppling the unit may cause injury.
● If you install the unit in an orientation other than specied, the unit cannot be protected from
a battery uid leakage.
Do not use the unit where the maximum temperature exceeds 40°C.
● The battery becomes weak rapidly, which may cause a re.
●Doing so may cause a failure or malfunction of the unit.
Do not exceed the ranges specied for environmental conditions during
use/storage.
Do not install or store the unit in the places listed below.
●Do not store in places where the humidity is lower than 10% or higher than 90%.
●Do not use in places where the humidity is lower than 25% or higher than 85%.
●Do not install/store the unit in closed places such as cabinets with no clearance, places
where there is flammable or correseve gas, places with large amounts of dust, places
exposed to direct sunlight, places exposed to shock or vibration, or outdoors.
● Installation or storing the unit in such a place may cause a re.
Do not connect equipment that exceeds the output capacity of the unit.
You can use a 220V plug strip to connect additional devices, but do not
connect devices that exceed the current capacity of the plug strip.
●The current protection of the unit may operate, which may stop the output.
● The wiring of the plug strip heats up, which may cause a re.
Do not pinch or sharply bend the cable.
Do not fold or knot the cable.
●
Doing so may cause the cable to be damaged or heated, which may cause an electric shock or a
re.
●If the cable is damaged, stop using the unit and have the cable repaired.
For repair, contact Omron representatives.
All of the included accessories are designed to be used exclusively with
the unit. Do not use the accessories with other devices.
●Doing so may compromise the safety of devices.
●This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit
The unit contains no user serviceable parts.Only factory service personnel may perform
repairs.
●Connection to any other type of receptacle other than a two-pole, three-wire grounded
receptacle may result in shock hazard as well as violate local electical codes.
●Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any
other liquid-containing vessels on or near the unit.
●This unit intended for installation in a controlled environment (temperature controlled, indoor
area free of conductive contaminants). Avoid installing the UPS in locations where there is
standing or running water, or excessive humidity.
●Do not attach a power strip or surge suppressor to the UPS.
●Do not attach non-computer-related items, such as medical equipment, life-support equip-
ment, microwave ovens, or vacuum cleaners to UPS.
●With the installation of the equipment it should be prevented, that the sum of the leakage
current of the UPS and the connected consumer does not exceed 3.5mA.
This manual suits for next models
2
Table of contents
Other Omron UPS manuals

Omron
Omron BU5002R User manual

Omron
Omron BU100RS User manual

Omron
Omron S8T-DCBU-01 User manual

Omron
Omron POWLI BU100XR2 User manual

Omron
Omron BN50T User manual

Omron
Omron BU5002RWLG User manual

Omron
Omron BU2002RWL User manual

Omron
Omron Powli BU1002SW User manual

Omron
Omron BN75R User manual

Omron
Omron Powli BU75RW User manual

Omron
Omron BL50T User manual

Omron
Omron POWLI BX75XS2 User manual

Omron
Omron S8BA-B120L User manual

Omron
Omron S8BA-S Series L User manual

Omron
Omron S8BA-24D24D480SBF User manual

Omron
Omron BW40T User manual

Omron
Omron POWLI BU60RE User manual

Omron
Omron BU1002RW User manual

Omron
Omron S8BA-24D24D960SBF User manual

Omron
Omron BA75T User manual