Onicon Air Monitor VOLU-probe/1SS User manual

VOLU-probe/1SS for Rectangular Ducts
INSTALLATIONPROCEDURE
WARRANTY
Air Monitor Corporation (hereinafter referred to as "Seller") warrants that at the time of shipment, products sold
pursuant to this contract will be free from defects in materials and workmanship, and will conform to the
specifications furnished or approved in writing by Seller. No warranty is given that delivered products will conform
to catalog sheets, data sheets, and the like, which are subject to change without notice.
Seller will repair or replace, at its option, any products listed under this warranty which is returned freight pre-
paid to Seller and within the earlier of one (1) year after start-up or fifteen (15) months after shipment, prove upon
test and examination by Seller to be defective within the terms of this warranty. The warranty period for any item
repaired or replaced shall be for the time remaining on the warranty period for the original components. Purchaser
shall notify Seller in writing of such defect within sixty (60) days of discovery of the defect.
This warranty does not extend to any product sold by Seller which has been the subject of misuse, neglect,
accident, damage or malfunction caused by interconnection with equipment manufactured by others, improper
installation or storage, or used in violation of instructions furnished by Seller, nor does it extend to any product
which has been repaired or altered by persons not expressly approved by Seller. Nor does Seller warrant
equipment against normal deterioration due to environment; nor items such as thermocouples, electrodes, and
similar items subject to wear or burnout through usage. Adjustments for items or equipment not manufactured
by Seller shall be made to the extent of any warranty of the manufacturer or supplier thereof.
Seller shall not be liable for any special or consequential damages or for loss of damage directly or indirectly
arising from the use of the products.
The warranty set forth above is in lieu of all other warranties either express or implied and constitutes the full extent
of Air Monitor Corporation's liability to the customer, or any other party for breach of warranty. THERE ARE NO
EXPRESS WARRANTIES EXCEPT AS SET FORTH HEREIN. THERE ARE NO IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE, WHICH ARE PARTICULARLY
DISCLAIMED.

VOLU-probe/1SS for Rectangular Ducts – Installation Procedure
INSPECTION & HANDLING. VOLU-probes should be carefully inspected for damage prior to installation. Report
damage to your Freight Department, or contact delivery carrier. Almost any means of handling can be utilized
depending on the length and weight of the probes. Probes may be handled while in any position, however, it is
important not to drop or mishandle the probes such that damage is done to the sensing holes, tubular members,
signal connection fittings, end studs, or mounting plates.
ORIENTATION OF PROBES. Using the AIRFLOW directional arrow on the probe mounting flange to determine
correct orientation, install VOLU-probes with sensing holes facing airflow.
- 2 -
INSTALLING VOLU-probes. To achieve published performance standards, the location of VOLU-probes in
ductwork must comply with the Minimum Requirements for Installation (Page 6). VOLU-probes must be mounted
so that the sensing holes on the probes are at the center of equal areas in the duct. Refer to dimensions A and
B in Figure 1:
A = inside dimension (I.D.) of the duct wall on which the probes are to be mounted
B = dimension A divided by the quantity of probes furnished per location
VOLU-probe insertion and end support holes must be cut in the duct on the center lines shown in Figure 1.
Caution: VOLU-probe/1SS over 10 feet in length require mid-span support to eliminate excessive droop or
oscillation during operation.

VOLU-probe/1SS for Rectangular Ducts – Installation Procedure
-3-
FASTENERS.
Gasket mounting surfaces should be clean and burr free. VOLU-probe mounting plates are predrilled for 1/4"
mounting fasteners. Air Monitor recommends the use of 1/4-20 bolts, nuts, and lock washers (or flat washers
and lock nuts). Fasteners should be stainless steel to be compatible with probes.
DIMENSIONAL SPECIFICATIONS.
VOLU-probe/1SS
THREAD SEALANT.
Appropriate thread sealant should be selected depending on maximum air temperature. Use of a high
temperature pipe sealant at the probe signal fittings is recommended. Teflon tape or equivalent products are not
recommended for high temperature applications

VOLU-probe/1SS for Rectangular Ducts – Installation Procedure
-4-
INTERCONNECTING TUBING. Interconnecting tubing and fitting makeup is to be per Table 1 (see Page 5).
Refer to illustrations below for typical tubing configurations.

SIGNAL TUBING. Signal tubing commences at the total and static pressure takeoff connections at the center of
the interconnecting tubing array shown in Details B and C. Two signal tubing conditions are possible; tubing with
an AUTO-purge panel and tubing without an AUTO-purge or CAMS panel.
If an AUTO-purge panel or CAMS panel is not furnished, signal tubing for total and static pressure take-off
connections may be 1/4" O.D. if the distance from the measuring device to the transmitter is 200' or less.
If an AUTO-purge panel is furnished, the total and static pressure signal tubing should be sized per the following
Table:
It is not recommended that AUTO-purge panels be located more than 50 feet from takeoff connections. Signal
tubing from the purge panel to a transmitter should be sized 1/4" if the distance is 200' or less.
CAUTION:After tubing is completed, signal lines should be leak tested prior to operation. Care must be taken
not to overpressurize measuring device.
VOLU-probe/1SS for Rectangular Ducts – Installation Procedure
-5-
TUBING SIZE
1/2” O.D. x 0.035” Wall
3/4” O.D. x 0.065” Wall
DISTANCE FROM TAKEOFF
FITTINGS TO PURGE PANEL
Under 25 ft.
25ft. to 50 ft.

VOLU-probe/1SS for Rectangular Ducts – Installation Procedure
-6-
AIRBORNE CONTAMINANTS.
The levels of air filtration and cleanliness associated with commercial HVAC Systems, whether supply/return/
exhaust/outside air, are satisfactory for operation of the VOLU-probe. Industrial applications containing airborne
contaminants may require periodic manual or automatic cleaning using compressed air applied to the signal
fittings, and/or removal from the duct or stack for physical cleaning.
MINIMUM REQUIREMENTS FOR INSTALLATION.
Note: VOLU-probe locations shown are NOT ideal. They indicate the minimum clearance required from air
turbulence producing sources. Wherever possible, the VOLU-probe should be installed where greater runs of
straight duct (or clearances) than shown exist.
Rectangular Duct: x = Circular Duct: x = Duct Diameter
2 H x W
H + W

VOLU-probe/1SS for Rectangular Ducts – Installation Procedure
-7-
1050 Hopper Avenue • Sant a Rosa, CA 95403 • 707-544-2706
www.airmonitor.com
INSTALL11A (2/16)
CUSTOMER SERVICE. Air Monitor Corporation provides in-house technical support for all our products:
Monday through Friday, 7 am to 5 pm (pst)
Phone: 707-544-2706 or 1-800-AIRFLOW / Fax: 707-526-2825
If after contacting the Customer Service Department it is determined that equipment will require return to Air Monitor
Corporation for further repair, a Return Authorization number will be issued. A Confirmation of Return Authorization with
shipping instructions will be sent via facsimile or e-mail. Equipment to be returned to Air Monitor should be returned in
its original shipping container if possible. If this is not possible, ensure equipment is packaged sufficiently to protect it
during shipment.
Caution: All damage occurring during transit is the Customer’s responsibility.
List the Return Authorization (R/A) number on the packing list and clearly mark this number on the outside of each
shipping container. Costs associated with the return of equipment to Air Monitor Corporation are the customer ’s
responsibility regardless whether the repair/return is under warranty. Once the Customer Service Department determines
that the equipment repair is under warranty, the item will be repaired and returned to the customer at no charge. If the
equipment is not under warranty, customer will need to approve a repair quote which will be invoiced along with return
shipping charges.
Table of contents
Other Onicon Security Sensor manuals
Popular Security Sensor manuals by other brands

System Sensor
System Sensor AFD Accuflow Installation and maintenance instructions

olympia electronics
olympia electronics ZLD-34 Operation instructions

Bentel Security
Bentel Security ZT100H quick start guide

Besantek
Besantek BST-HVD9 instruction manual

Risco
Risco iWISE QUAD AM Grade 3 installation guide

Spectrex
Spectrex SharpEye 40/40R user guide