Opera 6000 series User manual

Version 6.2
OPERATION MANUAL
Digital Gas Monitor/Controller

TABLE OF CONTENTS
1.0 General Description
1.1 Applications
1.2 Features
1.3 Specications
1.4 User Interface
2.0 Model Selection Guide
3.0 Installation
3.1 Monitor Placement
3.2 Wiring
3.3 Installation Check List
4.0 Operation
4.1 Screen Display
4.2 Default Settings
4.3 Changing Settings
4.4 List of Settings
4.5 Sequence of Operation
5.0 Network Conguration
5.1 Using CAN Network, Central Controller
5.2 Using CAN Network No Central Controller
5.3 Defaults Conguration
5.4 Creating Zones or Groups
5.5 Addresses
5.6 Output Relays
6.0 Maintenance Guide
6.1 Calibration Procedure
7.0 BACnet Network Conguration

6000 Series Digital Gas Monitor/Controller
Important Information !
This manual provides information required to install, operate and
maintain the series 6000 gas monitoring system. Read and study
before attempting to install or operate monitors. Installation
and operation not in accordance with this manual can result in a
hazardous situation or harm. Relay connections may be used to
control 120 Vac equipment. Ensure power is disconnected from
relays before attempting to service this unit.
1.0 General Description
Series 6000 gas monitors provide air quality monitoring for
commercial properties. Close monitoring of indoor air-born
pollutants and automatic fresh air controls improve the health and
well being of occupants and, also minimize excess ventilation,
reducing both energy costs and maintenance costs. The key to
maintaining this balance is a high level of precision coupled with a
robust design suited to tough commercial applications.
Each 6000 monitor can measure one or two gases and control
ventilation directly. They communicate with each other (up to 32)
via the chain network, so some monitors activate the ventilation
and others send the commands. The monitors are easily assigned
to groups on site for ventilation zoning on the same network. This
reduces control wiring signicantly.
The use of this peer-to-peer CAN network eliminates the need for a
costly controller on smaller projects. For the larger ones, a 6000-B
controller or addressable relay units can be added where starters
are centralized in the mechanical room. The monitors can also be
tied into a BACnet building automation system by simply connecting
an MS/TP cable to any monitor or 6000 controller on the CAN
network. The gas readings from all the monitors will display on the
BMS and the BMS can over-ride output relays on the monitor it is
connected to.

6000 Series Digital Gas Monitor/Controller
1.1 Applications:
• Vehicle emissions in indoor parking garages
• Municipal maintenance facilities
• Bus terminals
• Automobile dealerships
• Hospital parking for ambulances and visitors
• Volatile organic vapor control from soil contamination
• Refrigerant Gas Leak Monitoring
• CO2 demand control ventilation for meeting rooms
• Warehouse ventilation Control
1.2 Features:
• Stand-alone operation with adjustable alarm relays,
indicators and strobe
• BACnet Laboratory (BTL) listed Smart Sensor
• BACnet MS/TP RS485 interface
• CAN network master-slave operation or central control via
6000-B controller.
• Pre-calibrated plug-and-play sensor modules avoid the
need to recalibrate when upgrading expired sensors.
• Impact resistant, water resistant enclosure, with top wire
entry and drip proof wire guide.
• Binary input for conrmation of external action (fan on or
damper open)
1.3 Specications
• Supply 24 vac 50/60 hz (17-28 vac) 0.21 amps, 5 va
• Relays (1 or 2) SPDT, 5 amp @ 125 vac, non-inductive
On delay; 0-999 seconds (16 minutes)
Off delay; 0-999 seconds (16 minutes)
• Operating temperature -20 ºC to 40 ºC (-4 ºF to 104 ºF)
• For indoor use
• Flame resistant Polycarbonate ABS enclosure rated UL94
V0, 5VB, and 5VA
• Standards. Listed to CSA C22.2. no. 205-17.
Conforms to CSA C22.2 61010-1.
• Analogue 4-20 ma or 2-10v (model 6000-A)

1.0 General Description
• Pollution degree 2
• Installation catagory II
• Altitude 2000 m
• Humidity max 80% rh. 80% to temperatures up to 31 ºC
88 ºF, decreasing linearity to 50% rh at 40 ºC (104 ºF)
1.4 User Interface:
• Back lit LCD display shows gas concentration, user
settings, calibration controls
• Red LED alarm indicators, gas level 1 and 2
• High intensity white LED strobe on level 3
• Audible alarm, 85 db at 1 meter
• 4 pushbutton user keypad
• Password control for settings

6000 Series Digital Gas Monitor/Controller
2.0 Model Selection Guide
6000-B _
• 2 relays
• no analogue outputs
6000-A
• 1 relays
• 2 analogue outputs
6002-14-B _6002-14-A
Controller Only
Example: Monitor for CO + NO2
Gas Type
(see chart)
Gas type
if second
sensor
installed
55-xx
Controller with
Sensor(s) inside
Sensor Replacement
Module
Gas Type
(see chart)
Gas Type
(see chart)
Gas type
if second
sensor
installed

2.0 Model Selection Guide
Gas Type Range
-Controller only, no sensor 00
NH3Ammonia 04 0-250 ppm
Ar Argon (O2depletion) 23 0-50% O2
CO2Carbon dioxide (air quality) 15-2000 0-2000 ppm
CO2Carbon dioxide (compressed) 15-5000 0-5000 ppm
CO Carbon Monoxide 02 0-100 ppm
CO Carbon Monoxide 02-250 0-250 ppm
CO nil H2Carbon Monoxide nil H2 effect 02nilH2 0-100 ppm
CL2Chlorine 17 0-10 ppm
C2H5OH Ethanol 07 0-50% LEL
HCFCs 13
HFCs 20
He Helium (O2depletion) 23 0-25% O2
H2O in air Humidity (relative) 25 0-100% RH
H2Hydrogen 08 0-50% LEL
H2S Hydrogen Sulde 16 0-50 ppm
CH4Methane 05 0-50% LEL
CH3OH Methanol 07 0-50% LEL
N2Nitrogen (oxygen depletion) 23 0-50% O2
NO2Nitrogen Dioxide 14 0-10 ppm
VOCs Organic Vapors 01 0-1000 ppm
O2Oxygen Leak 22 0-50% O2
O2Oxygen Depletion 23 0-50% O2
C3H8Propane 06 0-50 % LEL

6000 Series Digital Gas Monitor/Controller
3.0 Installation
3.1 Monitor Placement
Coverage
Guidelines for placement of diffusion type monitors are based on
the reasonable delay for gas to get from the source to the sensor.
All monitor sensors combinations are created equal in this regard.
• For air quality control of exhaust emissions and
accumulations of toxic gases the generally acceptable
maximum radius of coverage is 50 feet (15 meters).
Approximately 7500 square feet (700 square meters).
• For leak detection of combustible gases, ammonia,
refrigeration gases the maximum radius is 30 feet (10 meters).
The radius of coverage of any monitor does not extend beyond
any obstruction that impedes natural circulation of air. This
includes walls, stairs, elevators, shelving with solid ll, tool
chests, etc. The sensor must “see” the area of coverage; if not,
additional monitors are required.
Mounting Heights
Mounting heights for gas monitors are based on their density,
relative to air. There are three groups;
1. Lighter than air and will be more concentrated near the
ceiling; hydrogen, methane (natural gas), ammonia.
Install at 1 to 3 feet from ceiling.
2. Similar density to air and will be diluted in air equally at
all levels; - carbon monoxide, nitrogen dioxide, hydrogen
sulde, oxygen, carbon dioxide. Install from 3 feet (1
meter) off oor to one half of the ceiling height. For vehicle
emissions carbon monoxide sensors combined with nitrogen
dioxide sensors are installed at 3 to 5 feet (1 to 2 meters)
from the oor when the ceiling height is 7 to 10 feet. If the
ceiling height is higher than 10 feet, example- for heavy
equipment, the carbon monoxide monitors are installed

at 3 to 5 feet (1 to 1.5 meters) from the oor as per the
requirements of the Canada building codes and the nitrogen
dioxide monitors should be installed at 50% of the ceiling
height and above the vehicle height. If the exhaust pipes
of diesel vehicles are below the vehicles, then the nitrogen
dioxide monitors should be installed at 3 to 5 feet (1 to 1.5
meters) from the oor. In all cases the monitors must be
installed above obstructions blocking circulation of air in
front of the monitors; example, maintenance garages in
automobile dealerships where tool chests, work tables and
storage racks typically line all walls.
3. Heavier than air and will concentrate near the oor; - HFCs,
HCFCs, propane, chlorine, most organic vapors (consult
Opera). Install 1-2 feet (30cm to 50cm) from oor.
For all types of monitors avoid drafts, obstacles, aerosols, silicones.
Place sensors in the center of its coverage area as much as
possible.
3.0 Installation

6000 Series Digital Gas Monitor/Controller
3.2.1 Wiring Model 6000-A
ac
Supply
Independant
Circuit
120 Vac
To magnetic starter coil or
control relay coil for ventilation
Transformer
120/24 Vac
To Other
units
BACnet
MSTP
network
CAN
network
Binary
input
to limit
switch
see 4.4 #32
End of line jumper
CAN bus
Down = Off
Up for rst and last
unit on cable
Up Position 4-20Ma
or
Down Position 2-10V EOL BACnet
5 Va for
each unit
NO COM
Relay 1
NC ANA1 G
Analogue Output
ANA2
–
+
SHIELD
(no connect)
High (H)
Low (L)
Shield
(on 1rst unit only)
to other
units

3.2.2 Wiring Model 6000-B
ac
Supply
Independant
Circuit
120 Vac
To magnetic starter coil or
control relay coil for ventilation
Transformer
120/24 Vac
To Other
units
BACnet
MSTP
network
CAN
network
Binary
input
to limit
switch
see 4.4 #32
End of line jumper
CAN bus
Down = Off
Up for rst and last
unit on cable EOL BACnet
5 Va for
each unit
NO COM
Relay 1
NC NO COM
Relay 2
NC
3.2 Wiring
–
+
SHIELD
(no connect)
–
+
Shield
(no connect)
High (H)
Low (L)
Shield
(on 1rst unit only)
to other
units

6000 Series Digital Gas Monitor/Controller
3.3 Installation Check List
Important. All wiring must conform to local building codes,
regulations and laws. If the equipment is used in a manner not
specied by the manufacturer, the protection provided by the
equipment may be impaired.
1. Use ½ inch EMT conduit for all wiring.
2. A switch or circuit breaker must be included in the installation. It
must be suitably located and easily reached in a secure location
and identied as the disconnect for the “Gas Monotoring System”.
3. Install enclosed 120/24 vac transformer. For the size of transformer
allow 5 va for each sensor or controller. Use 18 to 20 AWG two
conductor wire. Do not tie the secondary to ground. Connect
multiple monitors to one transformer. Ensure that the polarity of the
AC connections is the same at each monitor or controller, otherwise
communication will not function.
4. Connect relay contacts (usually relay 1) to ventilation system.
Use a magnetic starter so that the sensor contacts energize the
starter coil and not the fan motor directly.
5. For multiple monitors, inter-connected using the CAN network.
Connect a shielded twisted pair cable 22 to 24 AWG from
screw “L” and “H” (screw 11 and 12) on one sensor, to the next
monitor and continue chain to the last sensor. Maintain the same
polarity on each unit. Do not use star, T, or H junctions, only a
continuous chain. Make all chain connections at the sensors.
Connect shield to “S” on the rst sensor or controller only and
join shields together at each sensor/controller after the rst.
6. Move the end-of-line jumper (the one above terminal 11, 12) to
the on position (UP) on the rst monitor (or controller) on the chain
and the last monitor/controller on the chain. A controller with no
sensor module can be located anywhere on the chain. Ensure its
EOL jumper is off (down) if it is in the middle. Monitor/controller
addresses can be in any location on the chain.
7. Power on the units. They will display the gas type and reading.
To verify if monitors are communicating correctly, change setting

no. 56 on one unit. Press → until you reach option 56. Press → to
switch from 0 to 1, to turn on the network display. Press → and →
simultaneously to save, then press and hold → for a few seconds
to return home. The unit will display each monitor connected
in order of their address. If the unit does not display the others
scrolling by, check the following;
• each unit must have a unique address, setting 39, with no
duplicates
• end-of-line jumpers are set on units at ends of cable only
• polarity of the communication cable and the 24 Vac is the
same on all units
• verify wire connections for shorts, and loose wires, etc.
8. To further test communication, press and hold the up button on
a monitor for 5 seconds to start manual mode (5 minutes). This
will close the relay 1 on that unit and all of the other units on the
network. See section 5 to set up a conguration for multiple
zones.
For assistance contact Opera Inc.
(see back cover for contact info)
3.3 Installation
Electrical
Distribution
Panel
Magnetic
Starter
Exhaust Fan
Dampers
Fan Power
Source
Power source
for controls
to other
sensors
H
S
L
5
6
4
3
2
1
1
24 Vac
Transformer

6000 Series Digital Gas Monitor/Controller
4.0 OPERATION
4.1 Screen Display
The LCD shows the type of gas and the current gas
concentration. If two sensor modules are installed, the display
will alternate between them.
1indicates alarm 1 on, per settings 0, 1, 2 or if activated by
another sensor on the CAN network via setting 36. This is
usually the low gas level alarm.
2indicates alarm 2 on. Per settings 3, 4, 5 or if activated by
another monitor on CAN network per setting 37.
3indicates alarm 3 on. Per settings 6, 7, 8 or if activated
by another monitor on CAN network per setting 38. Alarm 3
activates the sounder and strobe.
Mindicates manual override mode on. Useful to start ventilation
system without the risk of leaving it on too long in cold weather.
From the home screen, press and hold ↑for 5 seconds to start.
Then click again to increase time from 5 to 60 minutes. This
activates alarm 1 (or 2, and 3 per setting 69) and sends alarm
transmit messages (settings 9-17) to other monitor on the CAN
Address
(See setting 56)
Alarm status
Type of gas
Concentration

network. The unit will return to automatic operation after the
time runs down. To cancel manual mode press ↓several times to
reduce time left to run. It will take a few seconds to stop. “M”
also displays when auto-cycle is on. See setting 73.
Tindicates alarm 1 on due to high ambient temperature (setting
51). Useful for summer ventilation.
4.2 Default Settings
User settings are factory pre-loaded with default values to
facilitate set up and can be changed at any time. Upgrading
rmware will not affect user settings.
Alarm thresholds should be set to suit local regulations.
Default values for these are general guidelines only.
4.3 Changing Settings
Press →and ←to move through the settings. If the keypad lock
is on then enter the password rst. The screen will display the
setting number 0, 1, 2, etc. plus the short description (e.g.; AL1
for Alarm 1 and the current setting.)
Press the↑or ↓buttons to increase or decrease the setting.
To save, press ↑and ← buttons at the same time. The word
“OK” will appear. If you do not see “OK” and the new value it is
because the buttons were not pressed simultaneously. Try again.
4.0 Operation
Type of gas
Concentration

6000 Series Digital Gas Monitor/Controller
No. Name Description Range Default
0 AL1 Alarm 1 threshold, activates relay 1 by sensor
1 A1Del Alarm 1 Delay on (seconds) 0-999 30
2 A1Off Alarm 1 Delay off (seconds) 0-999 20
3 AL2 Alarm 2 threshold, activates relay 2 by sensor
4 AL2Del Alarm 2 Delay on (seconds) 0-999 30
5 AL2Off Alarm 2 Delay off (seconds) 0-999 20
6 AL3 Alarm 3 threshold, sounder by sensor
7 A3Del Alarm 3 Delay on (seconds) 0-999 180
8 A3Off Alarm 3 Delay off (seconds) 0-999 20
9 A1Tx Alarm 1 transmit message, CAN
network 0-255 1
10 A1Tx Alarm 1 transmit message, CAN
network 0-255
11 A1Tx Alarm 1 transmit message, CAN
network 0-255
12 A2Tx Alarm 2 transmit message, CAN
network 0-255 2
13 A2Tx Alarm 2 transmit message, CAN
network 0-255
14 A2Tx Alarm 2 transmit message, CAN
network 0-255
15 A3Tx Alarm 3 transmit message, CAN
network 0-255 3
16 A3Tx Alarm 3 transmit message, CAN
network 0-255
17 A3Tx Alarm 3 transmit message, CAN
network 0-255
4.4 List of Settings Sensor A
(upper socket) settings

No. Name Description Range Default
18 AL1-B Alarm 1 threshold, activates
relay 1 by sensor
19 A1Del Alarm 1 Delay on (seconds) 0-999 30
20 A1Off Alarm 1 Delay off (seconds) 0-999 20
21 AL2-B Alarm 2 threshold, activates
relay 2 by sensor
22 A2Del Alarm 2 Delay on (seconds) 0-999 30
23 A2Off Alarm 2 Delay off (seconds) 0-999 20
24 AL3-B Alarm 3 threshold, sounder and
strobe by sensor
25 A3Del Alarm 3 Delay on (seconds) 0-999 180
26 A3Off Alarm 3 Delay off (seconds) 0-999 20
27 A1Tx Alarm 1 transmit message,
CAN network 0-255 1
28 A1Tx Alarm 1 transmit message,
CAN network 0-255
29 A1Tx Alarm 1 transmit message,
CAN network 0-255
30 A2Tx Alarm 2 transmit message,
CAN network 0-255 2
31 A2Tx Alarm 2 transmit message,
CAN network 0-255
32 BiTx Binary input transmit message
when limit switch is closed,
CAN bus. See 3.2.1
0-255 0
33 A3Tx Alarm 3 transmit message,
CAN network 0-255 3
34 A3Tx Alarm 3 transmit message,
CAN network 0-255
35 A3Tx Alarm 3 transmit message,
CAN network 0-255 0
4.4 List of Settings Sensor B
(lower socket) settings
4.4 List of Settings

6000 Series Digital Gas Monitor/Controller
No. Name Description Range Default
36 R1Rx Receive message to activate relay 1,
CAN network
0-255 1
37 R2Rx Receive message to activate relay 2,
CAN network
0-255 2
38 R3Rx Receive message to activate sounder
and strobe CAN network
0-255 0
39 Adr Monitor identication address, CAN
network
0-32 0
40 AnZA Accessing this option forces analogue
output A to low for testing with meter
only and no external cables attached.
Use up and down arrows to adjust
lowest setting (2v or 4 ma) and save
41 AnSA Accessing this option forces analogue
output A to high for testing with meter
only and no external cables attached.
Use up and down arrows to adjust
lowest setting (10v or 20 ma)
42 AnZB As option 40 but for output B
43 AnSB As option 41 but for output B
44 Temp Temperature display enable off/on 0/1 0
45 Aud Local audio alarm enable on alarm 3 0/1 1
46 BAC BACnet MSTP mode select
0 = BACnet communication disabled
1 = BACnet communication enabled
2 = BACnet communication enabled
and display all sensors on CAN
network
0/1/2 0
47 BMA BACnet MAC address 127 0
48 BBR BACnet baud rate
0 = 9600
1 = 19200
2 = 38400
3 = 76800
0/1/2/3 3
49 KBL Keyboard lock, blocks access to
options
0/1 0
4.4 List of Settings Continued
General settings

No. Name Description Range Default
50 TMod Temperature modify/calibrate -9/+9 ºC 0
51 ATHi High temperature alarm limit used
for summer ventilation. Alarm 1 is
activated when temperature exceeds
option. Temp setting 72 deg C/ F will
auto convert
0-99 ºC
0-210 ºF
60
140
52 W/U Warm up delay disables alarms, seconds 0-255 60
53 BMM BACnet maximum MAC address when
polling for master
0-127 127
54 BDiag BACnet diagnostic display while
accessing this option. In format
XXXXYYZZ. Where YY is MAC
address (in hex) of the monitor that
just passed the token to the current
one. ZZ is the monitor to which the
token was passed to. Example 0305
would display on monitor with MAC
address 4
55 ATLo Low temperature alarm limit (alarm 3).
0=off
0C/ 32F
56 Net Enables display on home screen of all
monitor on CAN network. 1=0n
0/1 0
57 Ref-A To select scale and type of gas for
sensor A.
For model 6020: R507, R23, R134a,
R152a, R492a, R404a, R407a, R408a,
R410a, R500, R502, R507
For model 6013: R22, R21, R141b,
R142b, R401a, R402a, R408a, R409a,
R502a
For Model 6021: R134a, R125,
R404a, R410a, R407a, R407c, R407f,
R448a, R449a, R513a, R22, R123,
R507, R1234yf, R1234zf
select
from list
R507
R22
58 Ref-B As setting no. 57 but for sensor B
(bottom socket)
59 FltTx Fault alarm transit message, CAN
network 0-255 0
4.4 List of Settings

6000 Series Digital Gas Monitor/Controller
No. Name Description Range Default
60 ADTxA Analogue drive transmit message,
sensor A (top) CAN network 0-255 0
61 AMinA Analogue drive. Minimum percent of
scale for zero output. Sensor A 0-100 0
62 AMAxA Analogue drive. Maximum percent of
scale for full scale output. Sensor A 0-100 100
63 ADRxA Receive message code to control local
analogue output. Sensor A 0-255 0
64 ADTxB Analogue drive transmit message,
sensor B (bottom) CAN network 0-255 0
65 AMinB Analogue drive. Minimum percent of
scale for zero output. Sensor B 0-255 0
66 AMaxB Analogue drive. Maximum percent of
scale for full scale output. Sensor B 0-100 100
67 ADRxB Receive message code to control local
Analogue output B 0-255 0
68 Baud
Baud rate for CAN network
Maximum network wire length is 1500
feet at rate 0 and 3000 feet at rate 1
Use rate 0 with model 5000
0-1 0
69 Man
Manual over-ride from home screen
activates alarms 1, 1+2, 1+2+3. See
section 4.1
1-3 1
70 BDI
Bacnet device instance
Enter part 1 (1000 to 4,194,303)
Press right arrow
Enter part 2 (0 to 999)
0-4,194,
303
60,000
+BMA
71 Light 1 = backlight always on
0 = on when keyboard activated 0-1 0
72 °C/°F Display 0 = degrees C, 1 = degrees F
Will also convert settings 51 and 55 0-1 0
73 Cycle
Automatic cycle timer Alarm 1
00C = total Cycle time in minutes
Press right arrow
00R = Run time in minutes
0-255 00/00
74 Age Sensor module A age in days
Press enter to display Sensor B 0
4.4 List of Settings Continued
General settings
Other manuals for 6000 series
2
This manual suits for next models
2
Table of contents
Other Opera Controllers manuals