Oppermann Regelgeräte CO2-W-LC User manual

CO2sensor CO2-W-LC / CO2-K-LC
for interior room (W) or duct (K) installation
Sensor ventilation air conditioning | Data sheet No. 14106 | Version 06-2012 | 1| 4
•Automaticinternalself-calibrationand
self-diagnosticswithserviceintervalsin
excessof5years.
•Latestgeneration(NDIR)infraredtechnology
formeasuringcarbon-dioxidegas.
•Multi-functionaldetectionandcontrolofCO2
•TwolinearanalogoutputsforCO2
•LCDdisplayoptional
•Forcontrollingventilationdemandasa
functionofCO2concentration(recommended
threshold<1,000ppm)
TechnicalData
CO2sensor: Non-dispersiveinfraredtechno-
logy(NDIR)withautomaticbase
correction
Sensor range - CO2: 0–3,000ppm(factorycalibration:
0–2,000ppm)
Error limits - CO2: ±30ppm±3%ofthesensorreading
Repeatability accuracy: ±20ppm±1%ofthesensorreading
CO2pressure sensitivity:+1.6%ofsensorreadingperkPa
variancefromstandardpressure
(100kPa)
Annual zero point drift
: <±10ppm
CE marking: 2004/108/EC(EMC)
Service interval: 5years(recommended
fortherstinspection)
Service life: >15years
Ambient conditions: Humidity0–95%RH,
(non-condensing)
Storagetemperature:-20–+70°C
Operatingtemperature:0–50°C
Protection type: IP30(W),IP65(K)
Dimensions (L x W x D): Seedimensioneddrawing
Weight: Approx.80g(W)/260g(K)
Power supply: 24VAC/DC±20%
50/60Hz
Power consumption: 2watts
Congurations
• Withoutdisplay:CO2-W-LC
• Withdisplay:CO2-W-DLC
• Airductinstallationwithoutdisplay:CO2-K-LC
• Airductinstallationwithdisplay:CO2-K-DLC
• SeeDatasheetNo.14101forcongurationswith
additionaltemperaturesensor
Heat up time: 15min
Response time T 1/e: <10sat30cc/minow-through,
<3minondiusion
Run-in period: 3weeksafterstartup
Screw terminals: Max.1.5mm²
Outputs
Analog output: 2linearanalogoutputs
OUT1andOUT2forCO2
OUT1:xed0–10VDC
(RLoad>5kΩ)
OUT2:2–10Vor4–20mA
(RLoad≤500Ω)adjustablewith
jumper.
Output resolution: 10mV
Analog output accuracy:±2%ofsensorreading±50mV
Wall housing (W)
Duct installation (K)

CO2sensor CO2-W-LC / CO2-K-LC
2| 4| Sensor ventilation air conditioning | Data sheet No. 14106 | Version 06-2012
Productdescription
TheCO2sensorisafullydigitalsensorunitfordetectingpersonsin
rooms.Itisdesignedtomeasurethecarbondioxideconcentration
inairtocontroltheventilationsystemasrequired.Thesensor
consistsofamembraneconnectedtoameasurementcavity.The
diusiontechnologyusedonthiscarbondioxidesensorfacilitates
astableandreliabledevicewithhighaccuracy.TheLCDdisplay
showsCO2inppm(option).Selfcalibrationisautomaticallyperfor-
medeverytimeafterthepowersupplyisconnected,andthenin
regularlyrecurringintervals.Toensureoptimumself-calibration,
theventilationshouldsupplyanormalCO2concentrationfor
severalminutesinintervalsofatleastoneweek.
ThesensorhastwoanalogoutputsOUT1
andOUT2thatbothoutputalinearsignal
correspondingtothesensorrangeofthe
sensor.
OutputOUT1ispermanentlysetto0–10VDC.
OutputOUT2canbeconguredfor4–20mA
(current)or2–10VDC(voltage)withajumper.
OutputOUT2canalsobeusedtodisplaythe
statusbecausethisoutputissetto1Vor2mA
bytheself-diagnosticsintegratedintothe
sensorwhenafaultoccurs.
IfoutputOUT2outputseither0Vor0mA,the
sensorisnotyetready.
Electricalconnection
Jumper setting for output 2 (OUT 2) =
4 – 20 mA
Jumper setting for output 2 (OUT 2) =
2 – 10 V = default setting
+
~
+
~
+
~
+
~
Applications
Thecarbondioxideconcentrationisgenerallyacceptedasa
goodindicatorfortheoccupancyloadonaroom.Sucientven-
tilationcanalsocounteractthespreadofvirusesandbacteria,
thecauseforillnesses,absenteeism,andtheresultinglossof
productivity.
Studiesdemonstratethatcontrollingventilationbasedoncon-
trollingCO2cancutheatingcosts.
Terminals Function Electrical specications Comments
+~ Supply(+) 24VAC/DC+
(±20%),2W
GNDreference/
systemground(-) 24VAC/DC- System
voltagereference
OUT1 Analogoutput1(+) 0–10VDC 0–2,000ppmCO2
OUT2 Analogoutput2(+) 2.0–10.0VDCor
4.0–20.0mA 0–2,000ppmCO2
0.9–1.6VDCor
1.5–2.5mA Status=ERROR
0VDCor0mA Status=NOTREADY
Attention:
The same GND
reference (Power
Ground) must be
used for all connected devices
and sensors to avoid incorrect
readings.Connectanalogoutputs
beforemeasurement.Afterinstal-
lingthesensor,continuetoapply
powertoallowtheCO2sensorcell
torun-in.
Option Display
CO2-Sensor
+
~
Power supply
24 V AC/DC ± 20 %
Output 0 – 10 V DC
Output 2 – 10 V DC
or 4 – 20 mA
Jumper for OUT 2

Sensor ventilation air conditioning | Data sheet No. 14106 | Version 06-2012 | 3| 4
CO2sensor CO2-W-LC / CO2-K-LC
Wallversioninstallation
Attention:thecorrectpositioningandconnectionofcablesto
tradestandardsisabasicconditionforproperfunctionality.
Ventilationisparticularlyimportant.
Notethefollowinginstructions:
• Thesensormustbemountedverticallyonaninteriorwall.
• Ensureunrestrictedaircirculationoninletsandoutlets.
• Attention:Noadditionalopeningsonthehousingorother
measurestomodifyaircirculationandheatdistributionare
permittedonthedevice.
• Onlyinstallthesensorwhereitisnotexposedtostronglight,
heat,sunirradiation,orairow.
• Waituntilconditionshavestabilized.
Installbypushingintheretaininghookalongthetopofthe
housingwithascrewdriver(seegure)andremovethehousing
cover.
Wallhousingdimensions
80
28
30
60
44
30
100
Zum Önen hier drücken
80
28
30
60
44
30
100
Press here to open
Installation
Pleaseobservetheseinstructions.
Allwork(suchasinstallation,electricalconnection,startup,
operation,andmaintenance)mustonlybeperformedbysuf-
cientlyqualiedtradesmen.Therespectivelyapplicablelocal
rulesandregulations(e.g.nationalbuildingcodes,electrical/
VDEregulations,etc.)mustbeobserved.Installersandopera-
tingentitiesarerequiredtosucientlyfamiliarizethemselves
beforestartup.Readtheproductdescriptionbeforeoperating
theequipment.Verifythattheproductcanbeusedforthe
relevantapplicationwithoutrestrictions.Wearenotliablefor
printingerrorsandchangesafterprinting.Appropriateuse
impliescompliancewithoperatingandinstallationinstruc-
tions.Wearenotliableforlossesduetoinappropriateuse.
Unauthorizedorinappropriatemanipulationsormodications
ofthedevicerendertheoperatingpermit,theproductwarranty
andwarrantyclaimsnullandvoid.
Dimensions in mm

4| 4| Sensor ventilation air conditioning | Data sheet No. 14106 | Version 06-2012 Specications subject to change.
CO2sensor CO2-W-LC / CO2-K-LC
Oppermann Regelgeräte GmbH | Im Spitzhau 1 | 70771 Leinfelden-Echterdingen, Germany
Phone +49 711 72723560 | Fax +49 711 7280527 | info@oppermann-regelgeraete.de |www.oppermann-regelgeraete.de
InstallationofductversionK
Thecorrectpositioningandconnectionofcablestotrade
standards,aswellaspropersealingisabasicconditionfor
properfunctionality.Notethefollowinginstructions:
• Attention:Duetothepressuredierentialbetweentheduct
andtheenvironment,thesealandcablefeed-throughmust
beinstalledwithspecialcare.Incorrectreadingscanbe
theresultofairinltration.Noadditionalopeningsonthe
housingorothermeasurestomodifyaircirculationandheat
distributionarepermittedonthedevice.Ifnecessary,seal
theductinletwithadditionalsealantiftheincludedgasket
isinsucientbyitself(e.g.onsmallerradii/pipes).
• Cablebushingsinparticularmustbesealedproperly.Never
insertmorethanonecablepercablebushing,sinceleaks
canresultinincorrectreadings.Onlyinstallthesensor
whereitisnotexposedtostronglight,heat,sunirradiation,
orairow.
• Probe tube installation:
DrillaØ25mm(10)fortheprobetube(1)and2Ø4mmfor
themountingscrews(5)atasuitablelocationintotheduct.
Thenmounttheprobetubeincludinggasket(2)totheduct
withscrews(5).Notethatthelargesttap(3)islocatedonthe
bayonetlockoftheprobetube.Ifnecessary,sealtheareaof
thegasket(2)withadditionalsealant..
• Housing installation:
Thehousingwithfactory-installedO-ring(6)andelectronics(7)
issimplyconnectedtotheprobetubewiththebayonetlock.
Engagetheuppersideofthehousinglightlyinacounter-
clockwisedirectionfromthelargesttap(3)oftheprobetube
andthenrotatethehousingtotheright(seesupplemental
drawing12).Insertthecableintothecablethread(9)and
connectittothefactory-installedelectronics(7).Thensecure
thesnap-onlid(8)tohousing.Theunitisdisassembledinthe
reverseorder.
4
Dimensions
4
Dimensions
4
Dimensions
1
CO2/ temperature transmitter for
mounting in ventilation ducts
1
2
1
2
3
456
7
9
8
10
1 Sampling probe 6 O-ring 29,2x3,53 (Factory supplied mounted in box)
2 Sealing gasket 7 PCB (Factory supplied mounted in box)
3 Largest locking nob 8Snap-in lid
4 2 washers 9PG9 cable entry bushing
5 2 screws 10 Temperature sensor (to be put into the sampling tube)
2
Mounting of aSENSE on to the duct.
11
10
10 Hole with 25 mm diameter
11 Temperature sensor with 110 mm cable mounted in the sampling probe
Mounting Instruction
Since there might be a substantial pressure difference in duct mounting applications,
it is essential to avoid ambient air from suction into the duct mounting box. For
correct function it is indispensible that the sealing of the box cover, the cable entry
bushings, the cable feed through and the duct entrance are absolutely tight. The duct
entrance may need extra sealing paste in order to prevent leakage. The PCB must
be handed carefully and protected from electrostatic discharge.
1) Electrical cable entry: The box has a factory mounted cable entry bushing in
dimension PG9. Never feed more than one cable through each cable entry
bushing, or else gas might leak through!
Dimensions in mm (inch)