Oppermann Regelgeräte DKM 3.3 User manual

Fire Protection | Data sheet No. 49103 | Version 01-2016 | 1| 6
Manual call point DKM 3.3 – bus capable for STG 1.2
Technical Data
Power supply: 17–31 V DC
from STG 1.2 via system bus
Power consumption: Switch-o current 100 µ A
Standby current 250 µ A
Alarm current 620 µ A
Short-circuit current 8 mA
Rated continuous current 1 A
LED displays:
Alarm: red LED on
Short-circuit: yellow LED on
Alarm- + short-circuit: yellow LED on
Alarm- + fault signal: via bus on STG 1.2
Rated operating
temperature: -10 – + 50 °C
Rated storage
temperature: -30 °C – + 60 °C
Rated humidity: 95 % RH (at 40 °C)
Gehäuse: ABS plastic
Dimensions (L x W x D): 135 x 135 x 37 mm
Weight: approx. 0.3 kg
Protection type: IP52 / IP54 (with gasket)
Connections: 6 x screw terminals 1.5 mm²
Colors: blue, yellow, red
• For Oppermann control unit STG 1.2
• Power supply and communication via safety
ringbus
• Housings in dierent colors
• LED display on alarm (red) and short circuit
(yellow)
• Custom labeling on request
• Installation-friendly housing
• Straightforward installation
Product description / Function
The DKM communicates with the STG via the safety-monitored
system ringbus. The detectors forward fault and alarm mes-
sages to the STG and indicated on a display. A technician or
building manager can therefore see all connected detectors at a
glance. Important .
Note: Please also note separate specication sheets for STG 1.2.
The manual call point consists of the plastic housing and door.
It contains the circuit board with terminals, trigger mechanism,
and push-button. The replaceable standardized thin glass
pane in a lockable door (protected by a standardized lock) is
a safeguard against unintended triggering. In the event of an
alarm, the glass pane is easily broken and the pushbutton can
be pressed without interference. A special retainer keeps the
button in the pressed position. The manually actuated retainer
lever is used to release the push button. The particularly low-
prole conguration of the manual call point eliminates the
need for in-wall installation.
The detector has cable connection terminals on top and on the
bottom. An opening can be punched out on the rear face of
the detector for installation on an in-wall cup. In the event of
an alarm, the glass pane (2) is punched in rst, and the push-
button (3) is then pressed deeply. This actuates the micro-
switch to trigger the alarm; display LED (4) lights up. A locking
mechanism retains the engaged push-button. The engaged
push-button is reset by manually actuating the reset lever (5) or
by opening the detector door (1). The alarm is reset and the LED
(4) goes dark. The alarm must also be reset on the STG.
2
4
1
5
2
3
3
1
2
4
1
5
2
3
3
1

Manual call point DKM 3.3 – bus capable
2| 6| Fire Protection | Data sheet No. 49103 | Version 01-2016
Installation instructions
All work must only be performed by suciently qualied trades-
men. The respectively applicable local rules and regulations (e.g.
national building codes, electrical/VDE regulations, etc.) must be
observed. Installers and operating entities are required to su-
ciently familiarize themselves before startup. We are not liable
for printing errors and changes after printing. Appropriate use
implies compliance with operating and installation instructions.
We are not liable for losses due to inappropriate use. Unautho-
rized or inappropriate manipulations or modications of the
device render the operating permit, the product warranty and
warranty claims null and void.
Other instructions:
• Manual detectors must be installed in a readily visible locations
along escape and emergency routes (e.g. exits, entryways,
stairwells) and must be readily accessible.
• The installation height of 1400 mm ± 200 mm, measured from
center of the push-button to the oor must be observed.
• Manual detectors must be suciently illuminated by daylight
or an alternative light source (including emergency lighting, if
applicable).
• Pursuant to VdS guidelines, a maximum of 10 non-automatic
re detectors can be connected to a primary cable. The test
detector can be used on primary cables together with auto-
matic re detectors. It is connected at the electrical end of the
primary cable (max. 1 test detector per primary cable).
• The distance between non-automatic re detectors should be no
more than 100 meters iaw. DIN 14 675, and 80 meters iaw. VdS.
• Non-automatic re detectors should be separated by a
maximum distance of 40 m (VDE 0833 Part 2, Section 7.2.6) in
particularly high-risk zones.
• Other standards, guidelines, and project planning recommen-
dations regarding installation location, etc. must be taken into
account where appropriate (see re detector manual).
• Local re department regulations must be observed.
Pos. Name
1 Plastic housing
2Cable bushings (replaceable), for in-going and out-going cables. The cable can also be fed through openings in the
housing rear wall.
3 Terminal bar
4 Alarm door with replaceable glass pane, covered lock, standardized key and gasket (accessory)
5 Glass pane
6 Display (LED red and yellow
7 Circuit board clipped into housing bottom.
8 Trigger mechanism (clipped to circuit board), consisting of plastic frame and push-button with spring.
9 Reset lever
1
7
5
2
34
8
2
6
9
Description of components Glass
Inside door
face
Gasket
Retainer clip for
glass pane
Replace the glass pane by pressing the retainer clip slightly to the side.
The function test is performed by pressing the detector button with the door open.

Fire Protection | Data sheet No. 49103 | Version 01-2016 | 3| 6
Manual call point DKM 3.3 – bus capable
Installation dimensions
Space requirements toward the right to open the detector
60 mm
135 mm
37 mm
135 mm
17 mm
13 mm
ca.35mm
Surface-mounted installation
(remove circuit board rst)
In-wall installation
3,4
4 x 40 mm
2x
S 5
2x
5
approx. 35mm

Manual call point DKM 3.3 – bus capable
4| 6| Fire Protection | Data sheet No. 49103 | Version 01-2016
Electrical connection
All work on electrical installations or equipment must only be performed by a trained electrician or by an instructed person under
the direction and supervision of a trained electrician in accordance with electrical engineering principles.
The maximum bus length is 250 m (loop length 500 m).
Each connected detector must be assigned a dedicated,
unique BUS address between 1 and 99. This is accomplished
with the PG 3.3 programming tool (accessory) The assigned
default address is 1. On request, Oppermann can congure the
detectors with custom BUS addresses (indicate in your order).
The positioning of addressed DKMs in the ringbus is arbitrary. A
fault alarm is triggered if the same detector address is assigned
twice on the ringbus. If the detector address is changed, the
detector must be reregistered with the STG in service mode.
1.
3.
2.
1.
2.
4 − 7 mm
8 − 10 mm
For connection to the control unit – system bus STG 1.2 please note the corresponding data sheet 43104.
Druckknopfmelder
DKM 3.3
LOOP + IN
LOOP –IN
LOOP + OUT
LOOP – OUT
SCREEN IN
SCREEN OUT
Detail showing electrical connection and shield
Detectors are supplied with power from the system ringbus. The
bus cable must be shielded on both sides (terminal„Screen“).
Manual call point
DKM 3.3

Fire Protection | Data sheet No. 49103 | Version 01-2016 | 5| 6
Manual call point DKM 3.3 – bus capable
1.
3.
2.
1.
2.
4 − 7 mm
8 − 10 mm
Wiring

6| 6| Fire Protection | Data sheet No. 49103 | Version 01-2016 Specications subject to change.
Manual call point DKM 3.3 – bus capable
Oppermann Regelgeräte GmbH | Im Spitzhau 1 | 70771 Leinfelden-Echterdingen, Germany
Phone +49 711 72723560 | Fax +49 711 7280527 | info@oppermann-regelgeraete.de |www.oppermann-regelgeraete.de
Programming is only possible when the detector is disconnected from power. Programming is not possible if the loop is
connected to power. Programming is also not possible during an alarm. Reset the alarm rst.
Programming:
• Jack plug
connector into programming tool (interface upper left) and the blue programming connector into the programming
interface on the circuit board of the DKM.
• Switch on programming tool by pressing the left gray button. The address is read from the
detector
and shown in the display.
• Change address with the two gray buttons. Dots blink behind the gures while the address is being changed.
• Save address with the
colored
button. The blinking dots behind the gures vanish.
• Unplug
detector
and switch o programming tool
.
Potential fault messages on programming tool:
bAt Replace battery (battery service life: approx. 3,000 programming cycles)
E0 Incorrect programming attempt (Address > 127)
E1 DRM/DKM detector not found
E2 Detector not operational
E3 Incorrect sensor reply
E4 No detector found
E5 Read error
E6 Error while reading analog value (only DRM)
Programming with PG 3.3 programming tool
Socket for jack plug
of programming cable
Battery compartment
9 V battery
• Store address
• Read analog value (for information)
• Switch on
• Adjust address in increments of 10
• Switch o
• Adjust address in increments of 1
• Bus address display
(1 – 127 possible, set 1 – 99 for STG)
• Fault indicator/analog value display
(only on DRM)
The programming cable is only needed for push button alarm DKM 3.3
Table of contents
Other Oppermann Regelgeräte Accessories manuals
Popular Accessories manuals by other brands

X10
X10 AM14A Installation and operating instructions

Raymarine
Raymarine 4000 mk2 Wheel Drive install guide

Zephyr
Zephyr Adjustable Depth Liners AK088xAS installation manual

Tridonic
Tridonic LCAI 2x038/0500 K013 one4all product manual

SMC Networks
SMC Networks PFM5 Series Operation manual

Petromax
Petromax kx-bag8-sand user manual