
20
Each time
the key
is pressed,
the setting
item is
switched.
8. Operation flowchart
(Fixed value control)
(In the case of Program control standby)
PV indication: The MEMO/STEP display is
unlit. Only PV is indicated.
SV indication: is indicated.
PV/SV indication
PV/SV or
• Select PV or SV with the ,
keys.
AT
PV/SV , Selection
• If AT is cancelled during the process,
PID values return to previous values.
OUT2 (Cooling)
proportional band
PV/SV , Set value
• Set the value with the , keys.
• Not available when OUT1 is ON/OFF
action
OUT1 (Heating)
integral time
PV/SV , Set value
• Set the value with the , keys.
• Setting the value to 0 disables the
function.
OUT1 (Heating)
proportional band
PV/SV , Set value
• Set the value with the , keys.
• ON/OFF action when set to 0.0
OUT1 (Heating)
derivative time
PV/SV , Set value
• Set the value with the , keys.
• Setting the value to 0 disables the
function.
OUT1 (Heating)
proportional cycle
PV/SV , Set value
• Set the value with the , keys.
• Not available for DC current output
type or if OUT1 is ON/OFF action.
OUT2 (Cooling)
proportional cycle
PV/SV , Set value
• Set the value with the , keys.
• Not available if OUT2 is ON/OFF
action.
ARW
PV/SV , Set value
• Set the value with the , keys.
• Available only for PID action
A2 value
PV/SV , Set value
• Set the value with the , keys.
• Not available if ,or
is selected during A2 type
selection.
A1 value
PV/SV , Set value
• Set the value with the , keys.
• Not available if ,or
is selected during A1 type
selection.
Reverts to the PV/SV display.
SV1
(Step 1 SV)
MEMO/STEP
PV/SV , SV1
Reverts to the
Alarm 1 (A1) setting procedures
(Numbers (1) to (5) are indicated on the flowchart.)
(1) Select an alarm type during [A1 type selection].
[If ,or is selected, (2) to (5)
are not indicated.]
(2) Set A1 hysteresis during [A1 hysteresis setting].
(3) Set A1 action delayed timer during [A1 action delayed
timer].
(If input enters alarm action range and setting time has
elapsed, the alarm is activated.)
(4) Select if the alarm output is held or not during [Alarm
HOLD function selection] (common to A1, A2).
(5) Set A1 action point during [A1 value setting].
[Note] If an alarm type is changed, the alarm value
becomes 0 (0.0). Therefore it is necessary to
Set value lock
PV/SV ,
Selection
• Make a selection with the ,
keys.
• If Lock 1 or Lock 2 is selected, AT
does not work.
• Be sure to select Lock 3 when
using Serial communication.
Sensor correction
PV/SV , Set value
• Set the value with the ,
keys.
Communication protocol
PV/SV , Selection
• Make a selection with the ,
keys.
Instrument number
PV/SV , Set value
• Set the value with the ,
keys.
Communication speed
PV/SV , Selection
• Make a selection with the ,
keys.
Reverts to the PV/SV display.
[Sub setting mode]
uxiliary function setting mode 1]
Step 1 time
MEMO/STEP
PV/SV , Set value
SV2
(Step 2 SV)
MEMO/STEP
PV/SV , SV2
Step 2 time
MEMO/STEP
PV/SV , Set value
Step 3 SV
MEMO/STEP
PV/SV , Step 3 SV
Step 3 time
MEMO/STEP
PV/SV , Set value
Step 9 time
MEMO/STEP
PV/SV , Set value
Set SV
and time
for the
necessary
step.
• : This means that if the key is pressed, the set
value is saved, and the controller proceeds to the
next setting item.
• If the key is pressed for approx. 3sec, the controller
reverts to the PV/SV display mode from any mode.
(5)
• Characters and set (selected) value of the setting item are
indicated on the PV/SV display alternately.
• Setting items with dotted lines are optional and they appear
only when the options are added.
Manual reset
PV/SV , Set value
• Set the value with the , keys.
• Available only for P and PD action.
Step 9 SV
MEMO/STEP
PV/SV , Step 9 SV
Press the key.
Press the key.
Automatically
returns 2sec later.
selected, and vice versa Control output OFF
(Fixed value control)
MV indication
Flashes
Program control RUN
(Program control)
Press the key. Press the key while holding down the key. Press the while holding down the for 3sec.
Press the key.
Press the key
for 3 seconds.
Press the key
for 1 second.
Press the key
for 1 second.