Panasonic KT9 User manual

TEMPERATURE CONTROLLER
KT9
INSTRUCTION MANUAL

2
P
Pr
re
ef
fa
ac
ce
e
Thank you for the purchase of Temperature controller KT9.
This manual contains instructions for the mounting, functions, operations and notes when
operating the KT9.
For model confirmation and unit specifications, please read this manual carefully before
starting operation.
To prevent accidents arising from the misuse of this controller, please ensure the
operator receives this manual.
Notes
• This instrument should be used according to the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause fire.
• Be sure to follow the warnings, cautions and notices. If they are not observed, it could cause
serious injury or accidents.
• The contents of this instruction manual are subject to change without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if
there are any doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed in a control panel. If it is not, measures must be
taken to ensure that the operator cannot touch power terminals or other high voltage
sections.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
•Panasonic Industrial Devices SUNX Co., Ltd. isnot responsible for anydamage or secondary
damage(s) incurred as a result of using this product, including any indirect damage.
• To pull out the inner assembly, release the hooks at the top and bottom of the instrument
with thin, hard tweezers. (If the hooks are released too far, they may be broken, or IP66
function could deteriorate. Do not pull out the inner assembly except when repairing the
instrument.)
SAFETY PRECAUTIONS
(Be sure to read these precautions before using our products.)
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on circumstances, procedures indicated by Caution may be linked to serious
results, so be sure to follow the directions for usage.
Warning
Procedures which may lead to dangerous conditions and cause death or serious
injury, if not carried out properly.
Procedures which may lead to dangerous conditions and cause superficial to medium
injury or physical damage or may degrade or damage the product, if not carried out
properly.
Caution

3
1
1.
.I
In
ns
st
ta
al
ll
la
at
ti
io
on
np
pr
re
ec
ca
au
ut
ti
io
on
ns
s
Caution
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current
is flowing
• No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
Note: Do not install this instrument near flammable material even though the case of
this instrument is made of flame-resistant resin.
Avoid setting this instrument directly on flammable material.
2
2.
.W
Wi
ir
ri
in
ng
gp
pr
re
ec
ca
au
ut
ti
io
on
ns
s
Caution
• Use the solderless terminal with an insulation sleeve that fits in the M3 screw when
wiring the KT9 Series.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with
the terminal screw.
• Tighten the terminal screw within the specified torque.
If excessive force is applied to the screw when tightening, the terminal screw or
case may be damaged.
• Do not apply a commercial power source to the sensor which is connected to the
input terminal nor allow the power source to come into contact with the sensor.
• This controller does not have built-in power switch, circuit breaker or fuse.
It is necessary to install them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
3
3.
.R
Ru
un
nn
ni
in
ng
ga
an
nd
dm
ma
ai
in
nt
te
en
na
an
nc
ce
ep
pr
re
ec
ca
au
ut
ti
io
on
ns
s
Warning
• It is recommended that the PID auto-tuning be performed on the trial run.
• Do not touch live terminals. This may cause electric shock or problems in operation.
• Turn the power supply to the instrument OFF before retightening the terminal
and cleaning.
Working on or touching the terminal with the power switched ON may result in
severe injury or death due to Electric Shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit)
• As the display section is vulnerable, do not strike or scratch it with a hard object.

4
--- CONTENTS ---
1. Model number
1.1 Explanation of model number ---------------------------------------------------- 6
1.2 Rated input ----------------------------------------------------------------------------7
1.3 How to read the rated label ------------------------------------------------------- 7
2. Name and functions of the sections ------------------------------------ 8
3. Mounting to the control panel
3.1 Site selection ----------------------------------------------------------------------- 10
3.2 External dimensions (Unit: mm) ----------------------------------------------- 10
3.3 Panel cutout (Unit: mm) ---------------------------------------------------------- 10
3.4 CT (current transformer) external dimensions (Unit: mm) --------------- 11
3.5 Mounting ----------------------------------------------------------------------------- 11
4. Wiring
4.1 Terminal arrangement ------------------------------------------------------------ 12
4.2 Wiring examples ------------------------------------------------------------------- 13
5. Setup
5.1 Operation flowchart --------------------------------------------------------------- 16
5.2 Main setting mode
SV1 -------------------------------------------------------------------------------------18
SV2 -------------------------------------------------------------------------------------18
5.3 Output MV indication --------------------------------------------------------------18
5.4 Sub setting mode
AT/Auto-reset ------------------------------------------------------------------------ 18
OUT1 proportional band ---------------------------------------------------------- 19
OUT2 proportional band ---------------------------------------------------------- 19
Integral time -------------------------------------------------------------------------- 19
Derivative time ---------------------------------------------------------------------- 19
ARW (Anti-reset windup) --------------------------------------------------------- 19
OUT1 proportional cycle ---------------------------------------------------------- 19
OUT2 proportional cycle --------------------------------------------------------- 19
A1 value ------------------------------------------------------------------------------ 20
A2 value ------------------------------------------------------------------------------ 20
HB (Heater burnout alarm) value ---------------------------------------------- 20
5.5Auxiliary function setting mode 1
Set value lock ----------------------------------------------------------------------- 21
SV high limit ------------------------------------------------------------------------- 21
SV low limit -------------------------------------------------------------------------- 21
Sensor correction ------------------------------------------------------------------ 21
Communication protocol --------------------------------------------------------- 21
Instrument number ---------------------------------------------------------------- 21
Communication speed ------------------------------------------------------------ 21
Parity ---------------------------------------------------------------------------------- 22
Stop bit -------------------------------------------------------------------------------- 22
5.6Auxiliary function setting mode 2
Input type ----------------------------------------------------------------------------- 22
Scaling high limit ------------------------------------------------------------------- 23
Scaling low limit -------------------------------------------------------------------- 23
Decimal point place --------------------------------------------------------------- 23
PV filter time constant ------------------------------------------------------------ 23

5
--- CONTENTS ---
OUT1 high limit ----------------------------------------------------------------------23
OUT1 low limit -----------------------------------------------------------------------23
OUT1 ON/OFF action hysteresis ----------------------------------------------- 23
OUT2 action mode ----------------------------------------------------------------- 23
OUT2 high limit ----------------------------------------------------------------------24
OUT2 low limit ----------------------------------------------------------------------- 24
Overlap band/Dead band --------------------------------------------------------- 24
OUT2 ON/OFF action hysteresis ----------------------------------------------- 24
A1 type -------------------------------------------------------------------------------- 24
A2 type -------------------------------------------------------------------------------- 25
A1 action Energized/Deenergized --------------------------------------------- 25
A2 action Energized/Deenergized --------------------------------------------- 25
A1 hysteresis ------------------------------------------------------------------------ 25
A2 hysteresis ------------------------------------------------------------------------ 25
A1 action delayed timer ----------------------------------------------------------- 25
A2 action delayed timer ----------------------------------------------------------- 25
Direct/Reverse action ------------------------------------------------------------- 26
AT bias -------------------------------------------------------------------------------- 26
Setting item not used -------------------------------------------------------------- 26
SV2 indication ---------------------------------------------------------------------- 26
Output status selection when input abnormal ------------------------------- 26
OUT/OFF key function ------------------------------------------------------------ 26
5.7 Control output OFF function --------------------------------------------------- 27
5.8 Auto/Manual control -------------------------------------------------------------- 27
6. Running ----------------------------------------------------------------------------- 28
7. Action explanation
7.1 OUT1 action ------------------------------------------------------------------------ 29
7.2 Heater burnout alarm action (option) ----------------------------------------- 29
7.3 OUT1 ON/OFF action ------------------------------------------------------------ 30
7.4 OUT2 (Heating/Cooling control) action (option) --------------------------- 31
7.5 OUT2 (Heating/Cooling control) action (when setting Dead band) --- 32
7.6 OUT2 (Heating/Cooling control) action (when setting Overlap band)-33
7.7 A1, A2 action ------------------------------------------------------------------------ 34
7.8 SV1/SV2 external selection ----------------------------------------------------- 35
8. Control action explanations
8.1 PID ------------------------------------------------------------------------------------ 35
8.2 PID auto-tuning of this controller ---------------------------------------------- 35
8.3 Auto-reset (offset correction) --------------------------------------------------- 36
9. Specifications
9.1 Standard specifications ---------------------------------------------------------- 37
9.2 Optional specifications ----------------------------------------------------------- 42
10.Troubleshooting
10.1 Indication -------------------------------------------------------------------------- 44
10.2 Key operation -------------------------------------------------------------------- 45
10.3 Control ----------------------------------------------------------------------------- 46
11. Character table ----------------------------------------------------------------- 46

6
1. Model number
1.1 Explanation of model number
A K T 9 1
(1) (2) (3) (4) (5) (6) (7)
(1) Supply voltage ---------------------- 1: 100 to 240V AC 2: 24V AC/DC
(2) Input type ----------------------------- 1: Multi-input (Thermocouple, RTD, DC current
and DC voltage can be selected
by keypad operation.
For DC current input, 50 shunt
resistor (AKT4810, sold separately)
must be connected between input
terminals.)
(3) Control output (OUT1) ----------- 1: Relay contact 2: Non-contact voltage (Voltage
output for SSR drive) 3: DC current
(4)Alarm output ------------------------- 1:A1 output 2:A1 output + A2 output
(The alarm type and Energized /Deenergized
can be selected by keypad operation)
(5) Heating/Cooling control (OUT2) output:
0: Not available 1: Relay contact
2: Non-contact voltage 3: DC current
(6) Heater burnout alarm ------------- 0: Not available 1: Available (5A) 2: Available
(10A) 3: Available (20A) 4:Available (50A)
(Heater burnout alarm is not available for the DC
current output)
(7) Serial communication ------------- 1:Applied (The number is added only when Serial
communication is applied.)

7
1.2 Rated input
Input type Input range Resolution
–200 to 1370 –320 to 2500 1 ( )
K–199.9 to 400.0 –199.9 to 750.0 0.1 ( )
J–200 to 1000 –320 to 1800 1 ( )
R 0 to 1760 0 to 3200 1 ( )
S 0 to 1760 0 to 3200 1 ( )
B 0 to 1820 0 to 3300 1 ( )
E–200 to 800 –320 to 1500 1 ( )
T –199.9 to 400.0 –199.9 to 750.0 0.1 ( )
N –200 to 1300 –320 to 2300 1 ( )
PL- 0 to 1390 0 to 2500 1 ( )
C(W/Re5-26) 0 to 2315 0 to 4200 1 ( )
–199.9 to 850.0 –199.9 to 999.9 0.1 ( )
Pt100 –200 to 850 –300 to 1500 1 ( )
–199.9 to 500.0 –199.9 to 900.0 0.1 ( )
JPt100 –200 to 500 –300 to 900 1 ( )
4 to 20mA DC –1999 to 9999 *1, *2 1
0 to 20mA DC –1999 to 9999 *1, *2 1
0 to 1V DC –1999 to 9999 *1 1
0 to 10V DC –1999 to 9999 *1 1
1 to 5V DC –1999 to 9999 *1 1
0 to 5V DC –1999 to 9999 *1 1
*1: For DC input, the input range and decimal point place can be changed.
*2: For DC current input, 50 shunt resistor (AKT4810, sold separately) must be
connected between input terminals.
1.3 How to read the rated label
The rated label is attached to the case.
AKT91111001
No.
Relay contact output
A1 output
Heater burnout alarm is not added.
(1)
(2)
(e.g.)
Supply voltage: 100 to 240V AC
Multi-input
(1) Model number, supply voltage, input type, output type, etc. are entered.
(2) Lot number is entered.
Heating/Cooling control is not added.
Serial communication is added.

8
2. Name and functions of the sections
(Fig. 2-1)
(1) PV display
Indicates the PV (process variable) with a red LED.
(2) SV display
Indicates the SV (main set value) or MV (manipulated variable) with a green LED.
(3) SV1 indicator
The green LED lights when SV1 is selected.
(4) SV2 indicator
The yellow LED lights when SV2 is selected.
(5) OUT1 indicator
When OUT1 or Heating output is on, the green LED lights.
(For the DC current output type, this flashes corresponding to the output manipulated
variable in 0.25 second cycles)
(6) OUT2 indicator
When OUT2 is on, the yellow LED lights.
(For the DC current output type, this flashes corresponding to the output manipulated
variable in 0.25 second cycles)
(7) HB indicator
WhenHeaterburnoutalarmoutputorsensorburnoutalarm outputison, the redLED lights.
(When Heater burnout alarm is added and if indication is overscale or underscale,
the red LED lights as well)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(14)
(15)
(12)
(13)

9
(8) AT indicator
The yellow LED flashes during auto-tuning or auto-reset.
(9) TX/RX indicator
The yellow LED flashes during Serial communication.
(10)A1 indicator
WhenA1 output is on, the red LED lights.
(11) A2/LA indicator
WhenA2 output is on, the red LED lights.
(12) Increase key: Increases the numeric value.
(13) Decrease key: Decreases the numeric value.
(14) Mode key: Selects the setting mode or registers the set value.
(By pressing the Mode key, the set value or selected value can be registered.)
(15) OUT/OFF key
•If OUT/OFF function is selected during OUT/OFF function selection, the control output
is turned on or off.
Once the control output OFF function is enabled, the function cannot be released even
if the power to the instrument is turned OFF and turned ON again.
To cancel the function, press the OUT/OFF key again for approx. 1 second.
•If Auto/Manual control function is selected from OUT/OFF function selection, automatic
control is performed when the power to the controller is turned on. In this status, if the
OUT/OFF key is pressed, the automatic control output is switched to manual control
output and vice versa. However, this function can be switched only in the PV/SV
display mode.
Notice
When setting the specifications and functions of this controller, connect terminals 2
and 3 for power source first, then set them referring to “5. Setup” before performing “3.
Mounting to the control panel” and “4. Wiring”.

10
□92
+0.8
0
130
□92+0.8
0
n×96-3
+0.5
0
3. Mounting to the control panel
3.1 Site selection
This instrument is intended to be used under the following environmental
conditions (IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
(1) A minimum of dust, and an absence of corrosive gases
(2) No flammable, explosive gases
(3) No mechanical vibrations or shocks
(4) No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 ) that does not change rapidly
(5) An ambient non-condensing humidity of 35 to 85%RH
(6) No large capacity electromagnetic switches or cables through which large
current is flowing
(7) No water, oil or chemicals or where the vapors of these substances can
come into direct contact with the unit
3.2 External dimensions (Unit: mm)
(Fig. 3.2-1)
3.3 Panel cutout (Unit: mm)
Lateral close mounting
n: Number of units mounted
Caution: If lateral close mounting is used for the controller,
IP66 specification may be compromised, and all
warranties will be invalidated.
(Fig. 3.3-1)
96
11.5
98.5
104.5 (*)
91
106.2
96
Gasket
Screwtype mounting bracket
(*): When terminal cover is used
Terminalcover

11
3.4 CT (Current transformer) external dimensions (Unit: mm)
AKT4815 (for 5A, 10A and 20A) AKT4816 (for 50A)
(Fig. 3.4-1)
3.5 Mounting
Notice
As the case is made of resin, do not use excessive force while screwing in the
mounting bracket, or the case or screw type mounting bracket could be damaged.
The torque should be 0.12N•m.
Mount the controller vertically to the flat, rigid panel to ensure it adheres to the
Dust-proof/Drip-proof specification (IP66).
Mounting panel thickness: 1 to 8mm.
Insert the instrument from the front side of the panel.
Attach the mounting bracket by the holes at the top and bottom of the case and secure
in place with the screws.
(Fig. 3.5-1)

12
4. Wiring
Warning
Turn the power supply to the instrument off before wiring or checking.
Working on or touching the terminal with the power switched on may result
in severe injury or death due to Electric Shock.
Moreover, the instrument must be grounded before the power supply to the
instrument is turned on.
4.1 Terminal arrangement
• OUT1 : Control output 1
(Heating output)
• OUT2 : Control output 2
(Cooling output)
• RELAY: Relay contact output
• V/A : Non-contact voltage
output/DC current output
• A1 : Alarm 1 output
• A2 : Alarm 2 output
• HB : Heater burnout alarm
output
• RS-485: Serial communication
• SV2 : 2nd SV
• CT : CT input
• TC : Thermocouple
• RTD : Resistance
temperature detector
• DC : DC current or
DC voltage
For DC current input,
50 shunt resistor
(Fig. 4.1-1) (AKT4810, sold
separately) must be
connected between
input terminals.

13
Notice
• The terminal block of KT9 series is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened
with the terminal screw.
• Dotted lines show options.
• If A2 (option) and Heater burnout alarm (option) are applied together, use
terminals 12-13 for A2, and 9-10 for the Heater burnout alarm.
• If the Heating/Cooling control (option) and Heater burnout alarm (option) are
applied together, use terminals 9-10 for the Heating/Cooling control, and 12-13
for the Heater burnout alarm.
• When only Heater burnout alarm option is applied, use terminals 9 and 10.
Lead wire solderless terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown
below.
(Fig. 4.1-2)
4.2 Wiring examples
Notice
• To extend a thermocouple’s lead wire, be sure to use a compensating lead wire in
accordance with the sensor input specification. (If any other compensating lead wire
is used, a temperature indication error may be caused.)
• Use the 3-wire RTD according to the sensor input specifications of this controller.
• This controller does not have built-in power switch, circuit breaker or fuse.
It is necessary to install them in the circuit externally, near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24VAC/DC power source, do not confuse polarity when using direct current (DC).
• When using a relay contact output type, use a relay externally according to the
capacity of the load to protect the built-in relay contact.
• When wiring, keep the input wire (Thermocouple, RTD, etc.) away from AC sources
or load wires to avoid external interference.
• Use a thick wire (1.25 to 2.0mm2) for grounding.
Solderless
terminal Manufacturer Model Tightening torque
Nichifu Terminal Industries CO.,LTD. TMEV1.25Y-3
Y type Japan Solderless Terminal MFG CO.,LTD. VD1.25-B3A
Nichifu Terminal Industries CO.,LTD. TMEV1.25-3
Round type Japan Solderless Terminal MFG CO.,LTD. V1.25-3
0.63N•m
3.2mm
5.8mm or less
3.2mm
5.8mm or less

14
[Heater burnout alarm output]
(1) This alarm is not available for detecting
heater current under phase control.
(2) This alarm is not available for detecting
3-phase heater current.
(3) Use the current transformer (CT) provided,
and pass one lead wire of the heater
circuit into the hole of the CT.
(4) When wiring, keep CT wire away from
anyAC source and load wire to avoid
external interference.
(5) Solder the CT and wires connected to the
CT input terminals. (There is no polarity.) (Fig. 4.2-1)
[AKT9111100]
(Fig. 4.2-2)
*To prevent the unit from harmful effects of unexpected high level noise, it is
recommended that a surge absorber be installed between the electromagnetic
switch coils.
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
CT input terminals
Power source
CT
Heater
15
16
3-phase
Electro-
magnetic
switch
Heater
Electric furnace
Alarm unit
Thermocouple
100 to 240V AC
or 24V AC/DC
Power supply
for Alarm unit
Solder the CT and wires connected
to the CT input terminals.
(There is no polarity.)

15
5. Setup
For the thermocouple and RTD input, the sensor input characters and temperature unit
are indicated on the PV display and the input range high limit value is indicated on the SV
display for approx. 3 seconds after the power is turned on. See (Table 5-1).
For DC input, the sensor input characters are indicated on the PV display and the scaling
high limit value is indicated on the SV display. See (Table 5-1).
If any other value is set during the scaling high limit setting, the set value is indicated on
the SV display.
During this time, all outputs and the LED indicators are in OFF status.
Control will then start and the PV (process variable) will be indicated on the PV display
and SV1 or SV2 will be indicated on the SV display.
While control output OFF function is working, is indicated on the PV display.
To release the function, press the OUT/OFF key for approx. 1 second.
(Table 5-1)
Sensor input PV display SV display PV display SV display
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 10V DC
1 to 5V DC
0 to 5V DC
Scaling high limit value

16
5.1 Operation flow chart
Outline of operation procedure
Operation before running
[Step 1 Initial setting] : Set Input type,Alarm type, control action,
etc. inAuxiliary function setting mode 2.
[Step 2 Adjusting item] : Set PID values and Alarm values in the
Sub setting mode.
[Step 3 Lock setting] : Set the Set value Lock, SV high limit and SV low
limit in Auxiliary function setting mode 1 (If Step 3
is not necessary, skip this step.)
[Step 4 Run setting] : Set SV1 (desired value) in the Main setting mode.
Set value Lock
PV SV
Selection
• Make a selection with ,
keys.
• If Lock 1 or Lock 2 is selected,
AT or Auto-reset does not work.
• Be sure to select Lock 3 when
using Serial communication.
[Auxiliary function setting mode 1]
AT/Auto-reset
PV SV
Selection
• IfAT is cancelled during the process,
PID values revert to previous value.
• Auto-reset is automatically cancelled
in 4 minutes.
SV1 (Desired value)
PV SV SV
OUT2 proportional
band
PV SVSet value
• Set the value with , keys.
• Available when Heating/Cooling
control (OUT2) is added
Integral time
PV SVSet value
• Set the value with , keys.
• PD action when set to 0, and auto-
reset can be performed.
OUT1 proportional
band
PV SVSet value
• Set the value with , keys.
• ON/OFF action when set to 0 or 0.0
Derivative time
PV SVSet value
• Set the value with , keys.
• PI action when set to 0
OUT1 proportional
cycle
PV SVSet value
• Set the value with , keys.
• Not available for DC current output or
when OUT1 is ON/OFF action
OUT2 proportional
cycle
PV SVSet value
• Set the value with , keys.
• Not available for DC current output or
when OUT2 is ON/OFF action
ARW
PV SVSet value • Set the value with , keys.
• Available for PID action
A1 value
PV SVSet value
• Set the value with , keys.
• Not available if is selected
during A1 type selection
Heaterburnoutalarmvalue
PV .SVSet value • Set the value with , keys.
• OFF when set to 0.0
A2 value
PV SVSet value
• Set the value with , keys.
• Not available if is selected
during A2 type selection
Reverts to the PV/SV display.
Reverts to PV/SV display.
Press the key.
[Main setting mode] [Sub setting mode]
(5)
PV/SV display
Control output OFF function or
Auto/Manual control function Press keyforapprox.1sec. Output MV indication
Explanation of key
: This means that
if is pressed, the set
value is saved, and the
controller proceeds to the
next setting item.
Alarm 1 (A1) setting procedure
[Numbers (1) to (5) are indicated on the flow chart.]
(1) [A1 type]: Select an alarm type
[If an alarm type except for is selected, items (2) to (5)
are indicated and they can be set if necessary.]
(2) [A1 action Energized/Deenergized]: SelectAlarm 1 contact
output ON (Energized: ) or OFF (Deenergized: ).
(3) [A1 hysteresis]: SetA1 hysteresis.
(4) [A1 action delayed timer]: SetA1 action delayed time.
(If input enters alarm action range and setting times has passed,
the alarm is activated.)
(5) [A1 value]: Set action point ofA1 output.
[Note] If an alarm type is changed, the alarm set value
becomes 0 (0.0). Therefore it is necessary to reset it.
Setting items with dotted lines are optional
and they appear only when the options are
added.
SV low limit
PV SVSet value • Set the value with , keys.
SV high limit
PV SVSet value • Set the value with , keys.
Sensor correction
PV SVSet value • Set the value with , keys.
Communication protocol
PV SVSelection •Make a selectionwith , keys.
• Not available for indication
Instrument number
PV SVSet value • Set the value with , keys.
Communication speed
PV SVSelection •Makeaselectionwith , keys.
Stop bit
PV SVSelection
•Makea selectionwith , keys.
• Not available if is selected
during Communication protocol
selection
Parity
PV SVSelection
•Makea selectionwith , keys.
• Not available if is selected
during Communication protocol
selection
Reverts to the PV/SV display.
Press the while holding down the key.
Press the key.
Press the key
for approx. 3sec.
Press for approx.3secwhileholdingdown
.
SV2 (Desired value)
PV SV SV

17
Setting item not used
PV SVSet value • Do not set this item even if is indicated
on the PV display.
OUT2 action mode
PV SV
Selection
• Make a selection with the , keys.
• AvailablewhenHeat/Cool control (OUT2) is added
Scaling low limit
PV SVSet value • Set the value with the , keys.
• Available for DC current, DC voltage input
Scaling high limit
PV SVSet value • Set the value with the , keys.
• Available for DC current, DC voltage input
Decimal point place
PV SVSelection
• Make a selection with the , keys.
• Available for DC current, DC voltage input
PV filter time
constant
PV SVSet value • Set the value with the , keys.
OUT1 low limit
PV SVSet value • Set the value with the , keys.
• Not available for ON/OFF action
OUT1 high limit
PV SVSet value • Set the value with the , keys.
• Not available for ON/OFF action
OUT1 ON/OFF action
hysteresis
PV SVSet value
• Set the value with the , keys.
• Available for ON/OFF action
OUT2 high limit
PV SVSet value • Set the value with the , keys.
• Availablewhen Heat/Cool control (OUT2) is added
Overlap/Dead band
PV SVSet value • Set the value with the , keys.
• Availablewhen Heat/Cool control (OUT2) is added
OUT2 low limit
PV SVSet value • Set the value with the , keys.
• Availablewhen Heat/Cool control (OUT2) is added
OUT2 ON/OFF action
hysteresis
PV SVSet value
• Set the value with , keys.
• Availablewhen Heat/Cool control (OUT2)isadded
Input type
PV SV
Selection
• Make a selection with the , keys.
• Default value:
[Auxiliary function setting mode 2]
Output status selection
when input abnormal
PV SV
Selection
• Make a selection with the , keys.
• Available only when input is DC current and DC
voltage with DC current output.
OUT/OFF key function
PV SVSelection • Make a selection with the , keys.
Reverts to the PV/SV display.
A1 type
PV SVSelection
• Make a selection with the , keys.
• Default value:
A1 hysteresis
PV SVSet value • Set the value with the , keys.
• Not available if is selected during A1
type selection
A2 type
PV SVSelection
• Make a selection with the , keys.
• Available whenA2 is added
A1 action Energized/
Deenergized setting
PV SVSelection
• Make a selection with the , keys.
• Not available if is selected during A1
type selection
A2 action Energized/
Deenergized
PV SVSelection
• Make a selection with the , keys.
• Not available if is selected during A2
type selection
A1 action delayed
timer
PV SVSet value
• Set the value with the , keys.
• Not available if is selected during A1
type selection
Direct/Reverse control
PV SVSelection
• Make a selection with the , keys.
• Default value:
A2 action delayed
timer
PV SVSet value
• Set the value with the , keys.
• Not available if is selected during A2
type selection
A2 hysteresis
PV SVSet value • Set the value with the , keys.
• Not available if is selected during A2
type selection
AT bias
PV SVSet value • Set the value with the , keys.
• Available for thermocouple, RTD input
(2)
SV2 indication
PV SVSelection
• Selects whether SV2 is indicated or not.
• Default value: (Indication)
Input type (character indication) and range
K –200 to 1370 :
–199.9 to 400.0 :
J –200 to 1000 :
R 0 to 1760 :
S 0 to 1760 :
B 0 to 1820 :
E –200 to 800 :
T –199.9 to 400.0 :
N –200 to 1300 :
PL- 0 to 1390 :
C(W/Re5-26) 0 to 2315 :
K –320 to 2500 :
–199.9 to 750.0 :
J –320 to 1800 :
R 0 to 3200 :
S 0 to 3200 :
B 0 to 3300 :
E –320 to 1500 :
T –199.9 to 750.0 :
N –320 to 2300 :
PL- 0 to 2500 :
C(W/Re5-26) 0 to 4200 :
Pt100 –199.9 to 850.0 :
JPt100 –199.9 to 500.0 :
Pt100 –200 to 850 :
JPt100 –200 to 500 :
Pt100 –199.9 to 999.9 :
JPt100 –199.9 to 900.0 :
Pt100 –300 to 1500 :
JPt100 –300 to 900 :
4 to 20mA DC –1999 to 9999:
0 to 20mA DC –1999 to 9999:
0 to 1V DC –1999 to 9999:
0 to 5V DC –1999 to 9999:
1 to 5V DC –1999 to 9999:
0 to 10V DC –1999 to 9999:
Alarm type
High limit alarm: The alarm action is deviation setting from the SV. The alarm is activated
if the input value reaches the high limit set value. Character indication:
Low limit alarm: The alarm action is deviation setting to the SV. The alarm is activated
if the input value goes under the low limit set value. Character indication:
High/Low limits alarm: Combines High limit and Low limit alarm actions. When input value
reaches high limit set value or goes under the low limit set value, the alarm is
activated. Character indication:
High/Low limit range alarm: When input value is between the high limit set value and low
limit set value, the alarm is activated. Character indication:
Process alarm: Within the scale range of the controller, alarm action points can be set
at random and if the input reaches the randomly set action point, the alarm is
activated.
Character indication: Process high alarm , Process low alarm
Alarm with standby function: When the power to the controller is turned on, even if the input
enters the alarm action range, the alarm is not activated. (If the controller is
allowed to keep running, once the input exceeds the alarm action point, the
standby function will be released.)
Character indication:
High limit alarm with standby :
Low limit alarm with standby :
High/Low limits alarm with standby :
(1)
(3)
(4)
Press the and keys for approx. 3sec.

18
5.2 Main setting mode
The main setting mode can be selected by pressing the key.
The SV can be increased or decreased by pressing the or key.
The SV is registered by pressing the key, and the unit reverts to the PV/SV
display mode.
Character
(PV display) Name, Function, Setting range Default value
(SV display)
SV1 0
• Sets SV1.
• Setting range: SV low limit to SV high limit, or
scaling low limit value to scaling high limit value
SV2 0
• Sets SV2.
• Not available if Serial communication (option) is added.
• Setting range: SV low limit to SV high limit, or
scaling low limit value to scaling high limit value
5.3 Output MV indication
Output MV (manipulated variable) indication
• In the PV/SV display mode, if the key is pressed for 3 seconds, the output
MV is indicated on the SV display.
While the output MV is indicated, the 1st decimal point from the right on the SV
display flashes in 0.5 second cycles.
By pressing the key again, the unit reverts to the PV/SV display mode.
5.4 Sub setting mode
The sub setting mode can be selected by pressing the key while holding down
the key.
The set value can be increased or decreased by pressing the or key.
The set value is registered by pressing the key, then the next setting item is
selected.
Character
(PV display) Name, Function, Setting range Default value
(SV display)
AT setting/Auto-reset setting Cancel
• Sets AT (auto-tuning) or Auto-reset (offset correction).
• Auto-reset can be performed only in PD or P action.
(Auto-reset cannot be performed when the control action is PID, PI
or ON/OFF action)
•:Auto-tuning/Auto-reset Cancel
/:Auto-tuning/Auto-reset Perform
[Auto-tuning]
• If Auto-tuning “Perform” is selected and the key is pressed, the
AT indicator flashes and the unit reverts to the PV/SV display mode.
• WhenAuto-tuning is finished, the AT indicator is turned off and P, I, D,
ARW values are automatically set.
• During auto-tuning, none of the settings can be carried out.
• IfAuto-tuning is cancelled during the process, P, I, D, ARW values
return to the previous value.
• If OUT/OFF key is pressed during auto-tuning, control output OFF
function activates, and pressing the OUT/OFF key again cancels the
PID auto-tuning.
• If PID auto-tuning does not finish in 4 hours after starting, PID
auto-tuning is cancelled automatically.

19
[Auto-reset]
• If auto-reset “Perform” is selected and the key is pressed,
the AT indicator flashes and the unit reverts to the PV/SV display
mode.
• If auto-reset is performed, offset correction immediately starts.
• To prevent key misoperation, other settings cannot be performed for 4
minutes after auto-reset starts.
• After auto-reset is completed, the AT indicator is turned off and the
reset value is automatically set.
OUT1 proportional band setting 10
• Sets OUT1 proportional band.
The control action becomes ON/OFF action when set to 0 or 0.0.
• Setting range: 0 to 1000 (0 to 2000 )
With a decimal point, 0.0 to 999.9 ( ), DC input: 0.0 to 100.0%
[Percentage of the scaling span (scaling high limit-scaling low limit)]
OUT2 proportional band setting 1.0 times
• Sets OUT2 proportional band.
OUT2 becomes ON/OFF action when set to 0.0.
• Available only when Heating/Cooling control (option) is added.
• Setting range: 0.0 to 10.0 (multiplying factor to OUT1 proportional
band)
Integral time setting 200 seconds
• Sets the integral time.
Setting the value to 0 disables the function (PD action).
• Setting range: 0 to 1000 seconds
Derivative time setting 50 seconds
• Sets the derivative time.
Setting the value to 0 disables the function (PI action).
• Setting range: 0 to 300 seconds
ARW (Anti-reset windup) setting 50%
• Sets the anti-reset windup.
• Available only for PID action.
• Setting range: 0 to 100%
OUT1 proportional cycle setting
• Sets OUT1 proportional cycle. Relay contact output: 30sec
Non-contact voltage output: 3sec
Not available for ON/OFF action and DC current output type
•With the relay contact output type, if the proportional cycle time
is decreased, the frequency of the relay action increases and
the life of the relay contact is shortened.
• Setting range: 1 to 120 seconds
OUT2 proportional cycle setting
• Sets OUT2 proportional cycle. Relay contact output: 30sec
Non-contact voltage output: 3sec
Not available for ON/OFF action and DC current output type
• Available only when Heating/Cooling control (option) is added.
• Setting range: 1 to 120 seconds

20
A1 value setting 0
• Sets the action point for A1 output.
Setting the value to 0 or 0.0 disables the function.
(excluding Process high and Process low alarm)
• Not available if No alarm action is selected during A1 type selection.
• Setting range: See (Table 5.4-1).
A2 value setting 0
• Sets the action point for A2 output.
Setting the value to 0 or 0.0 disables the function.
(excluding Process high and low alarm)
• Not available if A2 (option) is not added or if No alarm action is
selected during A2 type selection.
• Setting rangeanddefaultvalue arethesameas thoseof A1valuesetting.
HB (Heater burnout alarm) value setting 0.0A
.
and
measured
current
value are
displayed
alternately.
• Sets the heater current value for Heater burnout alarm.
• Available only when the Heater burnout alarm (option) is added.
• When OUT1 is OFF, heater current value shows the previous value as
when OUT1 was ON.
• Setting the value to 0.0 disables the function.
It is recommended to set approx. 80% of the heater current value
(set value) considering the voltage fluctuation.
• Upon returning to set limits, the alarm will stop.
• Setting range: Rating 5A: 0.0 to 5.0A Rating 10A: 0.0 to 10.0A
Rating 20A: 0.0 to 20.0A Rating 50A: 0.0 to 50.0A
Setting range of A1 and A2
(Table 5.4-1) Alarm type Setting range
High limit alarm –Input span to input span ( ) *1
Low limit alarm –Input span to input span ( ) *1
High/Low limits alarm 0 to input span ( ) *1
High/Low limit range alarm 0 to input span ( ) *1
Process high alarm Input range low limit to input range high limit *2
Process low alarm Input range low limit to input range high limit *2
High limit alarm with standby –Input span to input span ( ) *1
Low limit alarm with standby –Input span to input span ( ) *1
High/Low limits alarm with standby 0 to input span ( ) *1
• When the input has a decimal point, negative low limit value is –199.9, and positive
high limit value is 999.9.
• All alarm types except Process alarm are deviation setting from the SV.
*1: For DC input, the input span is the same as the scaling span.
*2: For DC input, input range low (or high) limit value is the same as the scaling low
(or high) limit value.
5.5 Auxiliary function setting mode 1
In the PV/SV display mode, if the key is pressed for approx. 3 seconds while
holding down the key, Auxiliary function setting mode 1 can be selected.
The set value can be increased or decreased by pressing the or key.
If the key is pressed, the set value is registered and the next setting item is
selected.
Table of contents
Other Panasonic Temperature Controllers manuals

Panasonic
Panasonic KT2 Use and care manual

Panasonic
Panasonic CZ-64ESMC1U User manual

Panasonic
Panasonic CZ-64ESMC1U User manual

Panasonic
Panasonic KT2 User manual

Panasonic
Panasonic KT4 series User manual

Panasonic
Panasonic KT4H User manual

Panasonic
Panasonic CZ-64ESMC3 User manual

Panasonic
Panasonic KT7 User manual

Panasonic
Panasonic U-8ME1E81 User manual

Panasonic
Panasonic CZ-64ESMC3 User manual