Panasonic KT7 User manual

1
Instruction manual Temperature Controller KT7 No. KT71E7 2013.05
To prevent accidents arising from the misuse of this controller, please ensure the operator receives
this manual.
SAFETY PRECAUTIONS
Be sure to read these precautions before using our products.
The safety precautions are classified into categories: “Warning” and “Caution”.
Warning: Procedures which may lead to dangerous conditions and cause death or serious injury, if not
carried out properly.
Caution : Procedures which may lead to dangerous conditions and cause superficial to medium injury
or physical damage or may degrade or damage the product, if not carried out properly.
Warning
• When using this controller on occasions which serious injury would be expected to occur or when damage
is likely to expand or proliferate, make sure to take safety measures such as installing double safety
structures.
• Do not use this controller in an environment with flammable gases, or it may cause explosion.
Caution
• Fasten the electric wire with the terminal screws securely. Imperfect connection may cause abnormal
heating or fumes.
• Use this controller according to the rating and environmental conditions. Otherwise abnormal heating or
fumes may occur.
• Do not touch the terminals while the power is supplied to the controller, as this may cause electric shock.
• Do not disassemble or modify the controller, as this may cause electric shock or fumes.
Caution
•This instrument should be used according to the specifications described in this manual.
If it is not used according to the specifications, it may malfunction or cause fire.
•Be sure to follow the warnings, cautions and notice. If not, it could cause serious injury or accidents.
•The contents of this instruction manual are subject to change without notice.
• This instrument is designed to be installed in a control panel. If not, measures must be taken to ensure
that the operator cannot touch power terminals or other high voltage sections.
• Be sure to turn the power supplied to the instrument OFF before cleaning this instrument.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may tarnish or deface the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
•Matsushita Electric Works, Ltd. is not liable for any damage or secondary damage(s) incurred as a result
of using this product, including any indirect damage.
1. Model number
1.1 Explanation of model number
A K T 7 1 1 0
(1) (2) (3) (4) (5) (6)
(1) Supply voltage ------------ 1: 100 to 240V AC, 2: 24V AC/DC
(2) Input type ------------------- 1: Multi-input (Thermocouple, RTD, DC current and DC voltage can be
selected by keypad operation. For DC current input, 50 shunt resistor
(AKT4810, sold separately) must be connected between input terminals.)
(3) Control output (OUT) ---- 1: Relay contact, 2: Non-contact voltage (Voltage output for SSR drive),
3: DC current
(4) Alarm output --------------- 1: Alarm output (1 point)
(The alarm type and Energized /Deenergized can be selected
by keypad operation)
(5) Heater burnout alarm ---- 0: Not available, 1: Available (5A), 2: Available (10A), 3: Available (20A),
4: Available (50A)
(Heater burnout alarm is not available for the DC current output)
(6) Serial communication --- 1: Applied (The number is indicated only when Serial communication is added.)

2
1.2 How to read the rated label
The rated label is attached to the case.
When Heater burnout alarm is added, CT rated current is written in the bracket ( ).
(1) Model number, supply voltage, input type, output type, etc. are entered.
(2) Lot number is entered.
2. Name and functions of the sections
(1) EVT indicator
The red LED lights when Event output [Alarm, Loop break alarm
or Heater burnout alarm (Option)] is ON.
(2) OUT indicator
When OUT (control output) is ON, the green LED lights.
For DC current output type, this flashes corresponding to the
output manipulated variable.
(3) T/R indicator
The yellow LED flashes during serial communication.
(4) AT indicator
The yellow LED flashes while PID auto-tuning is being performed.
(5) PV display
Indicates the PV (input value) with a Red LED.
(6) SV display
Indicates the SV (main set value) with a Green LED.
(7) Increase key
Increases the numeric value.
(8) Decrease key
Decreases the numeric value.
(9) Mode key
Selects the setting mode or registers the set value.
(By pressing the Mode key, the set value can be registered)
(10) Sub mode key
Enters Auxiliary function setting mode 2 in combination with the Mode key. (Fig. 2-1)
Notice
When setting the specifications and functions of this controller, connect terminals 1 and 2 for power
source first, then set them referring to “5. Setup” and “8. Operation flowchart” before performing
“3. Mounting to the control panel” and“4. Wiring”.
3. Mounting to the control panel
3.1 Site selection
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
•A minimum of dust, and an absence of corrosive gases
•No flammable, explosive gases
•Few mechanical vibrations or shocks
•No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
that does not change rapidly
•An ambient non-condensing humidity of 35 to 85%RH
•No large capacity electromagnetic switches or cables through which large current is flowing
•No water, oil or chemicals or where the vapors of these substances can come into direct
contact with the controller
(1)
(2)
(5)
(3)
(6)
(7)
(8)
(9)
(10)
(4)
AKT71111001
No.
Relay contact output
Alarm output (1 point)
Heater burnout alarm is not added
(1)
(2)
(e.g.)
Supply voltage: 100 to 240V AC
Multi-input
Serial communication is added

3
(B)
(A)
3.2 External dimensions (Unit: mm)
(Fig. 3.2-1)
3.3 CT (Current transformer) external dimensions (Unit: mm)
AKT4815 (for 5A, 10A, 20A) AKT4816 (for 50A)
(Fig. 3.3-1)
3.4 Mounting to DIN rail
Caution
Mount the DIN rail horizontally.
When DIN rail is mounted vertically, be sure to use commercially available fastening plates at both ends of
KT7 series. Mount the KT7 series to the DIN rail so that the KT7 series cannot move.
However, if the DIN rail is mounted horizontally in a position susceptible to vibration or shock, the
fastening plates must be used as well.
Recommended fastening plate
Fastening plate ATA4806
(1) Hook (A) of KT7 series on the upper side of
the DIN rail. (Fig. 3.4-1)
(2) Making (B) part of the KT7 series as a support,
fit the lower part of the KT7 series to the DIN rail.
KT7 series will be completely fixed to DIN rail with
a “Click” sound. (Fig. 3.4-1)
(Fig. 3.4-1)
4. Wiring
Warning
Turn the power supplied to the instrument OFF before wiring or checking it.
Working on or touching the terminal with the power switched ON may result in severe injury or
death due to Electric Shock.
4
100
97
22.5
75

4
Power
supply
Heater
CT
Terminal arrangement
•OUT : Control output
•RELAY: Relay contact output
•V/A : DC voltage output/ DC current
output
•EVT : Event output [Activated when
Alarm, Loop break alarm or
Heater burnout alarm (option)
is ON]
•TC : Thermocouple
•RTD : Resistance temperature detector
•DC : DC current or DC voltage
For DC current input, 50 shunt
resistor(AKT4810) must be
connected between input terminals.
•RS-485: Serial communication
(Fig. 4-1)
Caution
• Do not leave bits of wire in the KT7 series when wiring, because they could cause a fire or malfunction.
• Insert the connecting cable into the designated connector securely. Otherwise malfunction may occur due
to imperfect contact.
• Connect the AC power wire to the designated terminal as is written in this instruction manual, otherwise
it may burn and damage the KT7 series.
• Tighten the terminal screw with the specified torque. Excessive force could damage the terminal screw
and deface the case.
• To extend a thermocouple’s lead wire, be sure to use a compensating lead wire in accordance with the sensor
input specification. (If any other compensating lead wire is used, a temperature indication error may be caused.)
• Use the 3-wire RTD that corresponds to the sensor input specification of this unit.
• When using DC voltage and current input types, do not confuse the polarity when wiring.
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• Keep input wires (Thermocouple, RTD, etc) away from power source and load wires to avoid external
interference.
• To prevent the unit from harmful effects of the unexpected level noise, it is recommended that a surge
absorber be installed between the electromagnetic switch coils.
• This unit does not have built-in power switch, circuit breaker or fuse. Therefore, it is necessary to install
them in the circuit externally, near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
Note: Tighten the terminal screw properly referring to the table below.
Recommended ferrules
Terminal
number Terminal
screw Ferrules with
insulation sleeve Conductor cross
sections Tightening torque Crimping pliers
AI 0.25-8 YE 0.2 to 0.25mm2
AI 0.34-8 TQ 0.25 to 0.34mm2
AI 0.5-8 WH 0.34 to 0.5mm2
AI 0.75-8 GY 0.5 to 0.75mm2
AI 1.0-8 RD 0.75 to 1.0mm2
1 to 4 M2.6
AI 1.5-8 BK 1.0 to 1.5mm2
0.5 to 0.6N・m
AI 0.25-8 YE 0.2 to 0.25mm2
AI 0.34-8 TQ 0.25 to 0.34mm2
5 to 9 M2.0 AI 0.5-8 WH 0.34 to 0.5mm20.22 to 0.25N・m
CRIMPFOX ZA3
CRIMPFOX UD6
Option: Heater burnout alarm
(1) This alarm is not available for detecting heater current
under phase control.
(2) This alarm is not available for detecting 3-phase
heater current.
(3) Use the current transformer (CT) provided, and pass one
lead wire of the heater circuit into the hole of the CT.
(4) When wiring, keep CT wire away from AC sources
or load wires to avoid the external interference.
(5) Solder the wire harness to the CT.
(There is no polarity.) (Fig. 4-2)
Bottom of the unit
CT
input
Communication
C5 (RS-485)
Wire harness
Solder the wire harness to the
CT. (There is no polarity.)
Connector
(Connect to the KT7.)

5
5. Setup
Wire the power terminals only. After the power is turned on, the sensor input characters and temperature
unit are indicated on the PV display and the input range high limit value is indicated on the SV display for
approx. 3 seconds (Table 5-1).
(If any other value is set during the scaling high limit value setting, the value is indicated on the SV display.)
During this time all outputs and the LED indicators are in OFF status.
Control will then start, indicating the input value on the PV display and SV on the SV display.
(While control output OFF function is working, is indicated on the PV display.)
(Table 5-1)
Sensor input PV display SV display PV display SV display
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 5V DC
0 to 10V DC
1 to 5V DC
Scaling high
limit value Scaling high
limit value
5.1 Main setting mode
Character
(PV display) Name, Description, Setting range Default value
(SV display)
SV 0
• Sets the SV.
• SV low limit to SV high limit or scaling low limit value to scaling high limit value
(For DC voltage and current inputs, the placement of the decimal point follows
the selection)
5.2 Sub setting mode
Character
(PV display) Name, Description, Setting range Default value
(SV display)
AT setting
• Performs PID auto-tuning. However when PID auto-tuning has
not finished after 4 hours, PID auto-tuning is cancelled automatically.
•If Auto-tuning is cancelled during the process, P, I, D values return to the previous value.
• PID auto-tuning cancellation: , PID auto-tuning performance:
OUT proportional band setting 2.5%
• Sets the OUT proportional band.
• The control action becomes ON/OFF action when set to 0 or 0.0.
• 0.0 to 110.0% [Percentage of the scaling span (scaling high limit-scaling low limit)]
Integral time setting 200 seconds
• Sets the integral time.
• Setting the value to 0 disables the function.
• Not available for ON/OFF action.
• 0 to 1000 seconds
Derivative time setting 50 seconds
• Sets the derivative time.
• Setting the value to 0 disables the function.
• Not available for ON/OFF action.
• 0 to 300 seconds
Anti-reset windup setting 50%
• Sets anti-reset windup.
• Available only for PID action.
• 0 to 100%

6
OUT proportional cycle setting
• Sets the proportional cycle value for OUT. Relay contact output: 30sec
Non-contact voltage output: 3sec
• Not available for ON/OFF action or DC current output type
With the relay contact type, if the proportional cycle time is decreased, the
frequency of the relay action increases and the life of the relay contact is
shortened.
• 1 to 120 seconds
Manual reset setting 0.0
• Sets the reset value manually.
• Available only for P and PD action.
• Proportional band converted value (For DC voltage and current inputs, the
placement of the decimal point follows the selection)
Alarm value setting 0
• Sets the action point for the alarm output.
Setting the value to 0 or 0.0 disables the function (excluding Process high and
Process low alarm).
• Alarm, Loop break alarm and Heater burnout alarm (option) utilize common output
terminals.
• Not available if No alarm action is selected during the Alarm type selection.
• See (Table 5.2-1).
Heater burnout alarm value setting 0.0A
.
and
measured
current
value are
indicated
alternately.
• Sets the heater current value for Heater burnout alarm.
• Available only when Heater burnout alarm (option) is added.
• Setting the value to 0.0 disables the function.
• It is recommended to set approx. 80% of the heater current value (set value)
considering the voltage fluctuation of power supply.
• Upon returning to set limits, the alarm will stop.
• Heater burnout alarm (option), Alarm and Loop break alarm utilize common output
terminals.
• Rating 5A : 0.0 to 5.0A Rating 10A: 0.0 to 10.0A
Rating 20A: 0.0 to 20.0A Rating 50A: 0.0 to 50.0A
Loop break alarm action time setting 0 minutes
• Sets the action time to assess the Loop break alarm.
• Setting the value to 0 disables the function.
• Loop break alarm, Alarm and Heater burnout alarm (option) utilize common output
terminals.
• 0 to 200 minutes
Loop break alarm action span setting 0
• Sets the action span to assess the Loop break alarm.
• Setting the value to 0 disables the function.
• Loop break alarm, Alarm and Heater burnout alarm (option) utilize common output
terminals.
• Thermocouple, RTD input: 0 to 150 ( ) or 0.0 to 150.0 ( )
DC voltage, current input: 0 to 1500 (The placement of the decimal point
follows the selection)
(Table 5.2-1)
Alarm type Setting range
High limit alarm –(Input span) to input span ( ) *1
Low limit alarm –(Input span) to input span ( ) *1
High/Low limits alarm 0 to input span ( ) *1
High/Low limit range alarm 0 to input span ( ) *1
Process high alarm Input range low limit value to input range high limit value *2
Process low alarm Input range low limit value to input range high limit value *2
High limit alarm with standby –(Input span) to input span ( ) *1
Low limit alarm with standby –(Input span) to input span ( ) *1
High/Low limits with standby 0 to input span ( ) *1
•When input has a decimal point, negative low limit value is –199.9, and positive high limit value is 999.9.
• All alarm types except process alarm are deviation setting from the SV.
*1: For DC input, input span is the same as the scaling span.
*2: For DC input, input range low (or high) limit value is the same as scaling low (or high) limit value.

7
5.3 Auxiliary function setting mode 1
Character
(PV display) Name, Description, Setting range Default value
(SV display)
Set value lock selection Unlock
• Locks the set value to prevent setting errors.
The setting item to be locked depends on the selection.
•If Lock 1 or Lock 2 is selected, PID auto-tuning or auto-reset cannot be carried out.
• (Unlock): All set values can be changed.
(Lock 1): None of set values can be changed.
(Lock 2): Only main setting mode can be changed.
(Lock 3): All set values exceptinput type and Controller/Converter function
can be changed. However, they return to their previous value after power is
turned off because they are not saved in the non-volatile memory. Be sure to
select Lock 3 when changing the set values frequently via communication
function, (If the value set by the communication function is the same as the
value before the setting, the value will not be written in the non-volatile memory.)
Do not change anysetting item in Auxiliary function settingmode 2. If any item in
themode is changed, it will affect other setting itemssuchas SV and Alarm value.
Sensor correction setting 0.0
• Sets the sensor correction value for the sensor.
• Thermocouple, RTD input: –100.0 to 100.0 ( )
DC voltage, current input: –1000 to 1000 (The placement of the decimal
point follows the selection)
Communication protocol selection
• Selects the communication protocol.
• Available only when Serial communication (option) is applied.
• Not available if is indicated
• Modbus ASCII mode: , Modbus RTU mode:
Instrument number setting 0
• Sets the instrument number. (Communication cannot be carried out unless an
instrument number is individually set when communicating by connecting plural
instruments in serial communication.)
• Available only when Serial communication (option) is added.
• 0 to 95
Communication speed selection 9600bps
• Selects a speed to be equal to the speed of the host computer.
• Available only when Serial communication (option) is added.
• 2400bps: , 4800bps: , 9600bps: , 19200bps:
Parity selection Even parity
• Selects the parity.
• Not available if Serial communication (option) is not added or if
is selected during the Communication protocol selection.
• No parity: , Even parity: , Odd parity:
Stop bit selection 1
• Selects the stop bit.
• Not available if Serial communication (option) is not added or if
is selected during the Communication protocol selection.
• 1 or 2
5.4 Auxiliary function setting mode 2
Character
(PV display) Name, Description, Setting range Default value
(SV display)
Input type selection
• Theinput type can be selected from thermocouple (10 types),RTD K
(–200 to 1370 )
(2 types), DC current(2 types) and DC voltage(4 types), and the unit / can be selected.
K –200 to 1370 : K –320 to 2500 :
–199.9 to 400.0 : –199.9 to 750.0 :
J –200 to 1000 : J –320 to 1800 :
R 0 to 1760 : R 0 to 3200 :
S 0 to 1760 : S 0 to 3200 :
B 0 to 1820 : B 0 to 3300 :
E –200 to 800 : E –320 to 1500 :
T –199.9 to 400.0 : T –199.9 to 750.0 :
N –200 to 1300 : N –320 to 2300 :
PL- 0 to 1390 : PL- 0 to 2500 :
C (W/Re5-26) 0 to 2315 : C (W/Re5-26) 0 to 4200 :
Pt100 –199.9 to 850.0 : Pt100 –199.9 to 999.9 :

8
JPt100 –199.9 to 500.0 : JPt100 –199.9 to 900.0 :
Pt100 –200 to 850 : Pt100 –300 to 1500 :
JPt100 –200 to 500 : JPt100 –300 to 900 :
4 to 20mA –1999 to 9999:
0 to 20mA –1999 to 9999:
0 to 1V –1999 to 9999:
0 to 5V –1999 to 9999:
1 to 5V –1999 to 9999:
0 to 10V –1999 to 9999:
Scaling high limit setting 1370
• Sets the scaling high limit value.
• Scaling low limit value to input range high limit value
(The placement of the decimal point follows the selection.)
Scaling low limit setting –200
• Sets the scaling low limit value.
• Input range low limit value to scaling high limit value
(The placement of the decimal point follows the selection.)
Decimal point place selection No decimal point
• Selects decimal point place.
• Available only for DC input.
• No decimal point: 1 digit after decimal point:
2 digits after decimal point: 3 digits after decimal point:
PV filter time constant setting 0.0 seconds
• Sets PV filter time constant.
(If the set value is too large, it affects control result due to the delay of response)
• 0.0 to 10.0 seconds
OUT high limit setting 100%
• Sets OUT high limit value.
• Not available for ON/OFF action.
• OUT low limit value to 105%
(Setting higher than 100% is effective to DC current output type)
OUT low limit setting 0%
• Sets OUT low limit value.
• Not available for ON/OFF action.
• –5% to OUT high limit value
(Setting less than 0% is effective to DC current output type)
OUT ON/OFF action hysteresis setting 1.0
• Sets OUT ON/OFF action Hysteresis.
• Available only when the control action is ON/OFF action
• Thermocouple, RTD input: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection)
Alarm type selection No alarm action
• Selects an alarm type.
No alarm action : Process high alarm :
High limit alarm : Process low alarm :
Low limit alarm : High limit alarm with standby :
High/Low limits alarm : Low limit alarm with standby :
High/Low limit range alarm: High/Low limits alarm w/standby:
Alarm action Energized/Deenergized selection Energized
• Selects the alarm action Energized/Deenergized.
• Not available if No alarm action is selected during the Alarm type selection.
• Energized: Deenergized:
Alarm HOLD function selection Alarm Not Holding
• Selects either [Holding] or [Not Holding] of alarm HOLD function.
If alarm HOLD function is set to [Holding], once the alarm functions, alarm output
remains until the power is turned off.
• Not available if No alarm action is selected during the Alarm type selection
• Alarm Not Holding: Alarm Holding:
Alarm hysteresis setting 1.0
• Sets the alarm hysteresis.
• Not available if No alarm action is selected during the Alarm type selection
• Thermocouple, RTD input: 0.1 to 100.0 ( )
DC input: 1 to 1000 (The placement of the decimal point follows the selection)

9
Alarm action delayed timer setting 0 seconds
• Sets the alarm action delayed time.
When the setting time has passed after the input enters alarm output range, the
alarm is activated.
• Not available if No alarm action is selected during the Alarm type selection.
• 0 to 9999 seconds
Direct/Reverse control action selection Reverse (Heating) action
• Selects either Reverse (Heating) or Direct (Cooling) control action.
• Reverse (Heating) action :
Direct (Cooling) action :
AT bias setting 20
• Sets bias value during PID auto-tuning.
• Not available for the DC voltage or current input
• 0 to 50 (0 to 100 ) or 0.0 to 50.0 (0.0 to 100.0 )
Setting item not used: This item is indicated when Serial communication (option) is
added. However, this cannot be used.
Output status selection when input abnormal Output OFF
• Selects the output status of OUT when DC input is overscale or underscale.
See “Input abnormality indication” on page 18.
• Available only for DC current output with DC input
• : OFF(4mA) or OUT low limit
: Outputs a value between OFF (4mA) and ON (20mA) or between OUT low
limit value and OUT high limit value, depending on a deviation.
Controller/Converter function selection Controller function
• Selects either controller or converter function.
• Available only when the control output is DC current output type.
• Controller function:
Converter function:
ARW function
ARW (Anti-reset windup) prevents overshoot caused by the integral action. The smaller the ARW value, the less
the overshoot caused by the integral action in the transition status, however it takes time until stabilization.
Sensor correction function
This corrects the input value from the sensor. When a sensor cannot be set at a location where control
is desired, the sensor measuring temperature may deviate from the temperature in the controlled
location. When controlling with plural controllers, the accuracy of sensors affects the control. Therefore,
sometimes the measured temperatures (input value) do not concur.
In such a case, the control can be set at the desired temperature by adjusting the input value of sensors.
Energized/Deenergized function
When [alarm action Energized] is selected, the alarm output (between terminals 8-9) is conducted (ON)
while the alarm output indicator is lit.
The alarm output is not conducted (OFF) while the alarm output indicator is not lit.
When [alarm action Deenergized] is selected, the alarm output (between terminals 8-9) is not conducted
(OFF) while the alarm output indicator is lit.
The alarm output is conducted (ON) while the alarm output indicator is not lit.
[This function is not available for the Loop break alarm and Heater burnout alarm (optional).]
High limit alarm (When Energized is set) High limit alarm (When Deenergized is set)
(Fig. 5.4-1) (Fig. 5.4-2)
5.5 Output MV (manipulated variable) indication
Name and Description
Output MV (manipulated variable) indication
•In the PV/SV display mode, press the key for approx. 3 seconds.
Keep pressing the key until the output manipulated variable appears, though the main
setting mode appears temporarily during the process.
(The SV display indicates output manipulated variable and the 1st decimal point from the right
flashes in 0.5 second cycles)
If the key is pressed again, the unit reverts to the PV/SV display mode.
OFF
ON A1 hysteresis
SV setting + A1 set point OFF
ON
SV setting + A1 set point
A1 hysteresis

10
6. Converter function
Caution
• The converter function is selectable only for the DC current output type.
• When using this controller as a converter, take 1 second into consideration since
input/output response time is approx. 1 second.
• When switching from converter function to controller function, the control parameter and
values set by converter function are held even if the function is switched to controller
function.
So, correct the control parameters and values which has been set by converter function to
the values necessary for the controller function after switching to the controller function.
The converter function of this instrument converts each input (thermocouple, RTD, DC voltage and DC
current input) value to “4 to 20mA DC” using the control parameter of the controller, and outputs it.
When this instrument is used as a converter, follow steps (1) to (7) described below.
After steps (1) to (7) are finished, this instrument can be used as a converter.
(1) Wire this controller (Power supply, Input and Output).
(2) Turn the power of this controller ON.
(3) Enter “Auxiliary function setting mode 2” by pressing the and key (for approx. 3sec).
(4) Select the sensor type from “Input type selection ( )”.
(5) Set the high limit of the value that is going to be converted during “Scaling high limit setting ( )”.
(6) Set the low limit of the value that is going to be converted during “Scaling low limit setting ( )”.
(7) Select “Converter ( )” from “Controller/Converter function selection ( )”.
• To activate the alarm action by Converter function, set the alarm type to Process alarm.
If converter function is selected from “Controller/Converter function selection” in Auxiliary function setting
mode 2, the parameter below is automatically set. (Table 6-1)
However, this is applied only to the DC current output type.
(Table 6-1)
Setting item Set value Setting item Set value
SV Scaling low limit Alarm value setting 0
Proportional band 100.0% Loop break alarm action time 0 seconds
Integral time 0 seconds Loop break alarm action span 0
Derivative time 0 seconds Direct/Reverse action selection Direct action
Manual reset setting 0.0
7. Running
After mounting and wiring in the control panel (DIN rail) are completed, operate the unit following the
procedures below.
(1) Turn the power supply to the KT7 Series ON.
For approx. 3sec after power is turned on, the character of the sensor type and temperature unit are
indicated on the PV display, and the input range high limit value is indicated on the SV display.
(If any other value is set during the scaling high limit value setting, SV display indicates it)
During this time, all outputs and LED indicators are in OFF status.
After that, PV display indicates actual temperature and SV display indicates the SV (main set value).
(2) Input each set value.
Input each set value, referring to “5. Setup”.
(3) Turn the load circuit power ON.
Control action starts so as to keep temperature of the control target at the SV.

11
8. Operation flowchart
Outline of operation procedure
Operation before running
[Step 1 Initial setting] : Set Input type, Alarm type, control action, etc.
in Auxiliary function setting mode 2.
[Step 2 Adjusting item] : Set PID values and Alarm value in the Sub setting
mode.
[Step 3 Lock setting] : Set the Set value Lock in Auxiliary function setting
mode 1 (If Step 3 is not necessary, skip this step.)
[Step 4 Run setting] : Set the SV(desired value) in the Main setting mode.
Set value lock
PV SV
Selection
• Make a selection with ,
keys.
• If Lock 1 or Lock2 is selected,
AT or Auto-reset does not work.
• Be sure to designate Lock 3 when
using Serial communication.
[Auxiliary function setting mode 1]
AT
PV SVSelection
• If AT is cancelled during the process,
PID values revert to previous value.
SV (Desired value)
PV SV SV
Integral time
PV SVSet value
• Set the value with , keys.
• PD action when set to 0, and auto-
reset can be performed.
OUT proportional
band
PV SVSet value
• Set the value with , keys.
• ON/OFF action when set to 0 or 0.0
Derivative time
PV SVSet value
• Set the value with , keys.
• Setting the value to 0 disables the
function.
OUT proportional
cycle
PV SVSet value
• Set the value with , keys.
• Not available for DC current output or
when OUT is ON/OFF action
Manual reset
PV SVSet value
• Set the value with , keys.
• Not available when OUT2 is ON/OFF
action
ARW
PV SVSet value
• Set the value with , keys.
• Available for PID action
Alarm value
PV SVSet value
• Set the value with , keys.
• Not available if is selected
during Alarm action selection
Heater burnout alarm value
PV .SVSet value
• Set the value with , keys.
•Setting the value to 0.0 disables the function.
Reverts to the PV/SV display.
Reverts to PV/SV display.
[Main setting mode]
[Sub setting mode]
PV/SV display Output MV indication
Press the key.
Explanation of key
: This means that
if is pressed, the set
value is saved, and the
controller proceeds to the
next setting item.
Alarm setting procedure
(Numbers (1) to (6) are indicated on the flowchart.)
(1) [Alarm type]: Select an alarm type
(If an alarm type except for is selected, items (2) to (6)
are indicated and they can be set if necessary.
(2) [Alarm action Energized/Deenergized]: Select Alarm contact output
ON (Energized: ) or OFF (Deenergized: ).
(3) [Alarm HOLD function]: Select the alarm output Holding or Not Holding.
(4) [Alarm hysteresis]: Set the Alarm hysteresis.
(5) [Alarm action delayed timer]: Set Alarm action delayed time.
(If input enters alarm action range and setting time has passed,
the alarm is activated.)
(6) [Alarm value]: Set action point of Alarm output.
[Note] If an alarm type is changed, the alarm set value
becomes 0 (0.0). Therefore it is necessary to reset it.
Setting items with dotted lines are optional
and they appear only when the options are
added.
Loop break alarm
action time
PV SVSet value
• Set the value with , keys.
• Setting the value to 0 disables the
function.
Loop break alarm
action span
PV SVSet value
• Set the value with , keys.
• Setting the value to 0 disables the
function.
Sensor correction
PV SVSet value • Set the value with , keys.
Communication protocol
PV SVSelection
• Make a selection with , keys.
• Not available for indication
Instrument number
PV SVSet value • Set the value with , keys.
Communication speed
PV SVSelection
• Make a selection with ,
keys.
Stop bit
PV SV
Selection
• Make a selection with , keys.
• Not available if is selected
during Communication protocol
selection
Reverts to the PV/SV display.
Parity
PV SV
Selection
•Make a selection with , keys.
• Not available if is selected
during Communication protocol
selection
(6)
Press the key
for approx. 3sec.
Press the key. Press the key while holding down the key. Press for approx. 3sec while holding down .

12
9. Action explanation
9.1 OUT action
9.2 OUT ON/OFF action
: Acts ON or OFF.
Heating (reverse) action Cooling (direct) action
Control action
Relay contact
output
Non-contact
voltage output
DC current
output
Indicator
(OUT) Green
Lit Unlit
0V DC
+
0V DC
+
12V DC
+
12V DC
+
20mA DC
+
4mA DC
+
4mA DC
+
20mA DC
+
ON
OFF
ON
OFF
Hysteresis
Unlit Lit
Hysteresis
SV setting SV setting
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
: Acts ON or OFF.
Heating (Reverse) action Cooling (Direct) action
Control
action
Cycle action is performed according to deviation
Relay contact
output
Non-contact
voltage output
Changes continuously according to deviation
DC current
output
Indicator
(OUT) Green
Lit Unlit
ON
OFF
SV setting
Proportional band
ON
OFF
0V DC 0/12V DC
12V DC
+
20mA DC 20 to 4mA DC 4 to 20mA DC
Proportional band
Lit
0V DC 12V DC
12/0V DC
20mA DC
4mA DC
Cycle action is performed according to deviation
Cycle action is performed according to deviation Cycle action is performed according to deviation
Changes continuously according to deviation
+ + + + +
++
+++
+
Unlit
4mA DC
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
SV setting

13
Scaling low limit
PV SVSet value
• Set the value with , keys.
Scaling high limit
PV SVSet value
• Set the value with , keys.
Decimal point place
PV SVSelection
• Select the value with , keys.
• Available for DC current, DC voltage input
PV filter time
constant
PV SVSet value
• Set the value with , keys.
OUT low limit
PV SVSet value
• Set the value with , keys.
• Not available for ON/OFF action
OUT high limit
PV SVSet value
• Set the value with , keys.
• Not available for ON/OFF action
OUT ON/OFF action
hysteresis
PV SVSet value
• Set the value with , keys.
• Available for ON/OFF action
Input type
PV SVSelection
• Make a selection with , keys.
• Default value:
Output status selection
when input abnormal
PV SVSelection
• Make a selection with , keys.
• Available only when input is DC current and DC
voltage with DC current output
Controller/Converter
PV SVSelection
• Make a selection with , keys.
• Available for DC current output
Reverts to the PV/SV display.
Alarm type
PV SVSelection
• Make a selection with , keys.
• Default value:
(1)
Alarm action
Energized/Deenergized
PV SV Selection
• Make a selection with , keys.
• Not available if is selected during Alarm
type selection
Alarm HOLD function
PV SV
Selection
• Make a selection with , keys.
• Not available if is selected during Alarm
type selection
Alarm action delayed
timer
PV SVSet value
• Set the value with , keys.
• Not available if is selected during Alarm
type selection
(5)
Direct/Reverse control
PV SVSelection
• Make a selection with , keys.
• Default value:
AT bias
PV SVSet value
• Set the value with , keys.
• Available for thermocouple, RTD input
Setting item not used
PV SVSet value
• Do not set this item even if is indicated
on the PV display.
Input type (character indication) and range
K –200 to 1370 :
–199.9 to 400.0 :
J –200 to 1000 :
R 0 to 1760 :
S 0 to 1760 :
B 0 to 1820 :
E –200 to 800 :
T –199.9 to 400.0 :
N –200 to 1300 :
PL- 0 to 1390 :
C(W/Re5-26) 0 to 2315 :
K –320 to 2500 :
–199.9 to 750.0 :
J –320 to 1800 :
R 0 to 3200 :
S 0 to 3200 :
B 0 to 3300 :
E –320 to 1500 :
T –199.9 to 750.0 :
N –320 to 2300 :
PL- 0 to 2500 :
C(W/Re5-26) 0 to 4200 :
Pt100 –199.9 to 850.0 :
JPt100 –199.9 to 500.0 :
Pt100 –200 to 850 :
JPt100 –200 to 500 :
Pt100 –199.9 to 999.9 :
JPt100 –199.9 to 900.0 :
Pt100 –300 to 1500 :
JPt100 –300 to 900 :
4 to 20mA DC –1999 to 9999:
0 to 20mA DC –1999 to 9999:
0 to 1V DC –1999 to 9999:
0 to 5V DC –1999 to 9999:
1 to 5V DC –1999 to 9999:
0 to 10V DC –1999 to 9999:
Alarm type
High limit alarm: The alarm action is deviation setting from the SV. The alarm is activated
if the input value reaches the high limit set value. Character indication:
Low limit alarm: The alarm action is deviation setting to the SV. The alarm is activated
if the input value goes under the low limit set value. Character indication:
High/Low limits alarm: Combines High limit and Low limit alarm actions. When input value
reaches high limit set value or goes under the low limit set value, the alarm is
activated. Character indication:
High/Low limit range alarm: When input value is between the high limit set value and low
limit set value, the alarm is activated. Character indication:
Process alarm: Within the scale range of the controller, alarm action points can be set
at random and if the input reaches the randomly set action point, the alarm is
activated.
Character indication: Process high alarm , Process low alarm
Alarm with standby function: When the power to the controller is turned on, even if the input
enters the alarm action range, the alarm is not activated. (If the controller is
allowed to keep running, once the input exceeds the alarm action point, the
standby function will be released.)
Character indication:
High limit alarm with standby :
Low limit alarm with standby :
High/Low limits alarm with standby :
Alarm hysteresis
PV SVSet value
• Set the value with , keys.
• Not available if is selected during Alarm
type selection
(2)
(3)
(4)
[Auxiliary function setting mode 2]
Press the key for approx. 3sec while holding down
the key.

14
9.3 EVT (Alarm) action
Terminals 8 & 9 are for the user’s own Alarm (or Loop break alarm/Heater burnout alarm output) indicator,
which correlates directly with the EVT indicator.
9.4 EVT (Heater burnout alarm) action
: Event (EVT) output terminals 8 and 9 are connected (ON).
: Event (EVT) output terminals 8 and 9 are not connected (OFF).
Terminals 8 & 9 are for the user’s own Alarm (or Loop break alarm/Heater burnout alarm output) indicator,
which correlates directly with the EVT indicator.
Heater burnout
alarm action
ON
OFF
Heater burnout alarm set point
Load current LargeSmall
Indicator
UnlitLit
(EVT) Red
High limit alarm
Alarm
action
High/Low limits alarmLow limit alarm
OFF
ON
A1 hysteresis
OFF
ON
SV
setting
A1 set point
OFF
ON
A1 hysteresis
A1 hysteresis
A1 set point
SV
setting + A1 set pointA1 set point A1 set point SV
setting + A1 set point
High/Low limit range alarm Process high alarm Process low alarm
OFF
ON
OFF
ON
OFF
ON
Alarm
action
A1 hysteresis A1 hysteresis A1 hysteresis
A1 set pointA1 set pointA1 set pointA1 set point SV
setting
High limit alarm with standby High/Low limit alarm with standbyLow limit alarm with standby
OFF
ON
OFF
ON
OFF
ON
Alarm
action
A1 hysteresis A1 hysteresis A1 hysteresis
A1 set point A1 set pointSV
setting
SV
setting + A1 set point
A1 set point A1 set point SV
setting + A1 set point
: Standby functions in this section.

15
10. PID auto-tuning of this controller
In order to decide each value of P, I, D and ARW automatically, the auto-tuning process should be
made to fluctuate to obtain an optimal value.
Sometimes the auto-tuning process will not fluctuate if auto-tuning is performed at or near
room temperature. Therefore auto-tuning might not finish normally.
(A) In the case of a large difference between the SV and processing temperature as the
temperature is rising
When AT bias is set to 20 , the AT process will fluctuate at the temperature 20 lower than the SV.
Temperature 20 lower than the SV
(1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
constant set by auto-tuning
(4) AT bias value
(B) When control is stable
The AT process will fluctuate around the SV.
(1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
constant set by auto-tuning
(C) In the case of a large difference between the SV and processing temperature as the
temperature is falling
When AT bias is set to 20 , the AT process will fluctuate at the temperature 20 higher than the SV.
Temperature 20 higher than the SV (1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
constant set by auto-tuning
(4) AT bias value
11. Specifications
11.1 Standard specifications
Model : Temperature controller
Mounting : DIN rail mounting
Setting : Input system using membrane sheet key
Display
PV display : Red LED 4 digits, character size 7.4 x 4mm (H x W)
SV display : Green LED 4 digits, character size 7.4 x 4mm (H x W)
(1) (2) (3)
(4)
AT starting point
SV
Temperature
Time
AT starting point
(1) (2) (3)
Temperature
SV
Time
AT starting point
(1) (2) (3)
(4)
Temperature
SV
Time
(Fig. 10-1)
(Fig. 10-2)
(Fig. 10-3)

16
Input Thermocouple : K, J, R, S, B, E, T, N, PL- , C (W/Re5-26) External resistance; 100 or less
However, for thermocouple B, external resistance, 40 or less
RTD : Pt100, JPt100, 3-wire system
Allowable input lead wire resistance (10 or less per wire)
DC current : 0 to 20mA DC, 4 to 20mA DC, input impedance 50
[Connect 50 shunt resistor (AKT4811, sold separately) between input
terminals 5 and 6]
Allowable input current: 50mA or less
DC voltage : 0 to 1V DC 0 to 5V DC, 1 to 5V DC,
0 to 10V DC
Input impedance 1M or more 100k or more
Allowable input voltage 5V or less 15V or less
Allowable signal source
resistance 2k or less 100 or less
Accuracy (Setting and Indication)
Thermocouple: Within 0.2% of input span 1 digit, or within 2 (4 ) whichever is greater
However, for R, S input, 0 to 200 (0 to 400 ): Within 6 (12 )
B input, 0 to 300 (0 to 600 ): Accuracy is not guaranteed.
K, J, E, T, N input, less than 0 (32 ): Within 0.4% of input span 1 digit
RTD : Within 0.1% of input span 1 digit, or within 1 (2 ) whichever is greater
DC voltage : Within 0.2% of input span 1 digit
DC current : Within 0.2% of input span 1 digit
Input sampling period: 0.25 seconds
Control
Control action
• PID action (with auto-tuning function)
• PI action: When derivative time is set to 0
• PD action (with manual reset function): When integral time is set to 0
• P action (with manual reset function): When derivative and integral time are set to 0
• ON/OFF action: When proportional band is set to 0
OUT proportional band : 0.0 to 110.0% (ON/OFF action when set to 0.0)
Integral time : 0 to 1000 seconds (Off when set to 0)
Derivative time : 0 to 300 seconds (Off when set to 0)
OUT proportional cycle : 1 to 120 seconds
ARW : 0 to 100%
Manual reset : Proportional band converted value
Output limit : 0 to 100% (DC current output type: –5 to 105%)
(Not available for ON/OFF action)
Hysteresis : Thermocouple, RTD input: 0.1 to 100.0 ( )
DC voltage, current input: 1 to 1000
(The placement of the decimal point follows the selection)
Control output (OUT)
• Relay contact: 1a, Control capacity 3A 250V AC (Resistive load)
1A 250V AC (Inductive load COS ø =0.4)
Electrical life, 100,000 cycles
• Non-contact voltage (for SSR drive): 12+2
0V DC Max. 40mA (Short circuit protected)
• DC current: 4 to 20mA DC, Load resistance; Max. 550
Output accuracy: Within 0.3% of output span
Resolution : 12000
EVT output
• Alarm output
[Alarm, Loop break alarm and Heater burnout alarm (option) utilize common output terminals.]
The alarm action point is set by deviation from the SV (excluding Process alarm)
and when input is out of the alarm setting range, alarm (EVT) turns ON or OFF (High/Low limit
range alarm). When Deenergized is selected in the Energized/Deenergized selection, alarm
(EVT) is activated conversely.
Setting accuracy : The same as indication accuracy
Action : ON/OFF action
Hysteresis : Thermocouple, RTD input: 0.1 to 100.0 ( )
DC voltage, current input: 1 to 1000 (The placement of the decimal
point follows the selection)
Output : Open collector,Controlcapacity24VDC 0.1A (Max.),Residual voltage:1.5Vorless
Alarm type : One alarm type is selectable from below by front keypad operation:
High limit, Low limit, High/Low limits, High/Low limit range, Process high,
Process low, High limit with standby, Low limit with standby,
High/Low limits with standby and No alarm action

17
Alarm Energized/Deenergized: Alarm (EVT) output Energized/Deenergized can be selected.
Alarm Energized Alarm Deenergized
Red (EVT) LED Lights Lights
EVT output ON OFF
Alarm HOLD function: Once the alarm is activated, alarm output is held until the power is
turned off.
•Loop break alarm output
[Loop break alarm, Alarm and Heater burnout alarm (option) utilize common output terminals.]
Detects heater burnout, sensor burnout and actuator trouble.
Setting range: Loop break alarm action time setting: 0 to 200 minutes
Loop break alarm action span setting
Thermocouple, RTD input: 0 to 150 ( ) or 0.0 to 150.0 ( )
DC voltage, current input : 0 to 1500
(The placement of the decimal point follows the selection)
Output: Open collector, Control capacity, 24V DC 0.1A (Max.)
Converter function: See “6. Converter function”
Insulation • Dielectric strength: Circuit insulation configuration
Insulation resistance: 10M or more, at 500V DC
Dielectric strength : 1.5kV AC for 1 minute between input terminal and power terminal
1.5kV AC for 1 minute between output terminal and power terminal
Power consumption : Approx. 6VA
Ambient temperature: 0 to 50
Ambient humidity : 35 to 85%RH (no condensation)
Weight : Approx.120g
External dimensions : 22.5 x 75 x 100mm (W x H x D)
Material : Flame-resistant resin (Case)
Color : Ash gray (Case)
Attached functions
[Set value lock]
[Sensor correction]
[Power failure countermeasure]
The setting data is backed up in non-volatile IC memory.
[Self diagnosis]
The CPU is monitored by a watchdog timer, and when an abnormal status is found on the CPU,
the controller is switched to warm-up status with all outputs turned off.
[Automatic cold junction temperature compensation] (Only thermocouple input)
This detects the temperature at the connection terminal between the thermocouple and the
instrument and always maintains it on the same status as when the reference junction is located
at 0 (32 ).
[Warm-up indication]
After the power supply to the instrument is turned on, the sensor input characters and
temperature unit are indicated on the PV display and input range high limit value is indicated
on the SV display for 3 seconds.
For DC current, voltage input, the scaling high limit value is indicated.
[Burnout]
When the thermocouple or RTD input is burnt out, OUT is turned OFF and PV display flashes
“ ” (for DC current output type, OUT low limit value).
EVT
CT input
Input
CPU
Insulated
Power supply OUT
5
43
98
12
7
6
Communication
When OUT is non
-
contact
voltage output or DC current
output, OUT is not insulated
from Communication.

18
[Input abnormality indication] Controller/Converter function selection
Output status
Controller Converter
OUT OUT
Output status
selection when
input abnormal Contents and
Indication Direct
action Reverse action Direct action Reverse
action
ON (20mA)
or OUT high
limit value (*)
Overscale
Measured value
has exceeded
Indication range
high limit value.
" " flashes.
OFF (4mA)
or OUT low
limit value
OFF(4mA)
or
OUT low
limit value
ON (20mA)
or
OUT high
limit value
OFF (4mA)
or
OUT low
limit value
ON (20mA) or
OUT high
limit value (*)
Underscale
Measured value
has dropped
below Indication
range low limit
value.
" " flashes.
OFF (4mA)
or
OUT low
limit value OFF(4mA) or
OUT low
limit value
OFF(4mA)
or
OUT low
limit value
ON (20mA)
or
OUT high
limit value
[Output status selection when input abnormal] is available only for DC input and DC current output.
For other inputs and outputs except for DC input and DC current output, the output status will be
the same as when OFF is selected during [Output status selection when input abnormal].
(*): Outputs a value between OFF (4mA) and ON (20mA) or between OUT low limit value and
OUT high limit value, depending on deviation.
Thermocouple, RTD input
Input Input range Indication range Control range
–199.9 to 400.0 –199.9 to 450.0 –205.0 to 450.0
K,T–199.9 to 750.0 –199.9 to 850.0 –209.0 to 850.0
–199.9 to 850.0 –199.9 to 900.0 –210.0 to 900.0
–200 to 850 –210 to 900 –210 to 900
–199.9 to 999.9 –199.9 to 999.9 –211.0 to 1099.9
Pt100
–300 to 1500 –318 to 1600 –318 to 1600
–199.9 to 500.0 –199.9 to 550.0 –206.0 to 550.0
–200 to 500 –207 to 550 –207 to 550
–199.9 to 900.0 –199.9 to 999.9 –211.0 to 999.9
JPt100
–300 to 900 –312 to 1000 –312 to 1000
Indication range and Control range for thermocouple inputs except above:
Input range low limit value–50 (100 ) to input range high limit value+50 (100 )
DC current, voltage input
Indication range : [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value
+ Scaling span x 10%]
However, if the input value is out of the range –1999 to 9999, the PV
display flashes “ ” or “ ”.
Control range : [Scaling low limit value – Scaling span x 1%] to [Scaling high limit value
+ Scaling span x 10%]
DC input disconnection: When DC input is disconnected, PV display flashes “ ” for 4 to
20mA DC and 1 to 5V DC input, and “ ” for 0 to 1V DC input.
For 0 to 20mA DC, 0 to 5V DC and 0 to 10V DC input, the PV display
indicates the value corresponding with 0mA or 0V input.
Accessories included: Instruction manual 1 copy
When Heater burnout alarm option is added: Wire harness 3m, 1 length
[Wire type: Twisted; Terminations: Connector (KT7 side)/Cut end (CT side)]
When Heater burnout alarm option is added:
For rating 5A, 10A, 20A CT (AKT4815) 1 piece
For rating 50A CT (AKT4816) 1 piece
Accessories sold separately: 50 shunt resistor (AKT4811) for DC current input 1 piece
11.2 Optional specifications
Heater burnout alarm (option)
Watches the heater current with CT (Current transformer) and detects the burnout.
This alarm is also activated when indication is overscale and underscale.
(To detect Heater burnout, a CT for 50A can also be used for 5A, 10A and 20A ratings, however, this
is not suitable for small ampere ratings due to a low degree of accuracy. For a 20A rating or less, use
a CT designated for 20A.)

19
Heater burnout alarm (option), Loop break alarm and Alarm utilize common output terminals.
This option cannot be applied to DC current output type.
Rating : 5A, 10A, 20A, 50A (Must be specified)
Setting range : 5A, 0.0 to 5.0A (Off when set to 0.0) 10A, 0.0 to 10.0A (Off when set to 0.0)
20A, 0.0 to 20.0A (Off when set to 0.0) 50A, 0.0 to 50.0A (Off when set to 0.0)
Setting accuracy: 5% of the rated value
Action : ON/OFF action
Output : Open collector, Control capacity, 24V DC 0.1A (Max.)
Serial communication (option)
The following operations can be carried out from the external computer.
(1) Reading and setting of SV, PID and various set values
(2) Reading of the PV and action status (3) Change of the functions
Cable length : Max. communication distance 1000m, Cable resistance; Within 50
Communication interface : EIA RS-485
Communication method : Half-duplex communication start-stop synchronous
Communication speed : 2400, 4800, 9600, 19200bps (Selectable by keypad)
Parity : Even, Odd and No parity (Selectable by keypad)
Stop bit : 1, 2 (Selectable by keypad operation)
Communication protocol : Modbus RTU, Modbus ASCII (Selectable by keypad)
Connectable number of units : Maximum 31 units to 1 host computer
Communication error detection: Parity, checksum (LRC, CRC)
12. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply to the controller.
12.1 IndicationProblem Presumed cause and solution
PV display is indicating
[ ]. • Control output OFF function is working.
Press the key for approx. 1 second to release the function.
[ ] is flashing on the
PV display.
• Burnoutofthermocouple,RTDordisconnectionofDCvoltage(0to1VDC)
Change each sensor.
How to check whether the sensor is burnt out
[Thermocouple]
If the input terminals of the instrument are shorted, and if a value
around room temperature is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[RTD]
If approx. 100 of resistance is connected to the input terminals
between A-B of the instrument and between B-B is shorted, and
if a value around 0 (32 ) is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[DC voltage (0 to 1V DC)]
If the input terminals of the instrument are shorted, and if a
scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
• Check whether the input terminals of thermocouple, RTD or DC voltage
(0 to 1V DC) are securely mounted to the instrument input terminal.
Connect the sensor terminals to the instrument input terminals securely.
[ ] is flashing on the
PV display.
• Check whether input signal source for DC voltage (1 to 5V DC) or
DC current (4 to 20mA DC) is disconnected.
How to check whether the input signal wire is disconnected
[DC voltage (1 to 5V DC)]
If the input to the input terminals of the instrument is 1V DC and if
a scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
[DC current (4 to 20mA DC)]
If the input to the input terminals of the instrument is 4mA DC and
if a scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
•CheckwhetherinputsignalwireforDCvoltage(1to5VDC)orDCcurrent
(4 to 20mA D
C) is securely connected to the instrument input terminals.
• Check if polarity of thermocouple or compensating lead wire is correct.
• Checkwhethercodes(A,B,B)ofRTDagreewiththeinstrumentterminals.

20
The PV display keeps
indicating the value which
was set during Scaling low
limit setting.
•
Check whether the input signal source for DC voltage (0 to 5V DC,
0 to 10V DC) and DC current (0 to 20mA DC) is disconnected.
How to check whether the input signal wire is disconnected
[DC voltage (0 to 5V DC, 0 to 10V DC)]
If the input to the input terminals of the instrument is 1V DC and
if the value corresponding to 1V DC is indicated, the instrument
is likely to be operating normally, however, the signal wire may
be disconnected.
[DC current (0 to 20mA DC)]
If the input to the input terminals of the instrument is 1mA DC and
if the value corresponding to 1mA DC is indicated, the instrument
is likely to be operating normally, however, the signal wire may be
disconnected.
• Check whether the input lead wire terminals for DC voltage (0 to
5V DC, 0 to 10V DC) or DC current (0 to 20mA DC) are securely
mounted to the instrument input terminals.
The indication of PV display
is abnormal or unstable. • Checkwhethersensorinputortemperatureunit( or )iscorrect.
Select the sensor input and temperature unit ( or ) properly.
• Sensor correcting value is unsuitable. Set it to a suitable value.
• Check whether the specification of the sensor is correct.
• AC leaks into the sensor circuit. Use an ungrounded type sensor.
• There may be equipment that interferes with or makes noise near
the controller. Keep equipment that interferes with or makes
noise away from the controller.
[ ] is indicated on
the PV display. • Internal memory is defective.
Please contact our agency or us.
12.2 Key operation
Problem Presumed cause and solution
Unable to set SV, P, I, D,
proportional cycle, alarm
value, etc.
The values do not change
by the , keys.
• Set value lock (Lock 1 or Lock 2) is selected.
Release the lock selection.
• During PID auto-tuning or auto-reset
Cancel the auto-tuning if necessary.
Auto-reset ends 4 minutes after starting.
Thesettingindicationdoes
not change within the input
range even if the ,
keys are pressed, and
new values are unable to be set.
• Scaling high limit or low limit may be set at the point where the
value does not change.
Set it to a suitable value while in Auxiliary function setting
mode 2.
12.3 Control Problem Presumed cause and solution
Temperature does not rise. • Sensor is out of order. Replace the sensor.
• Check whether the sensor is securely mounted to the instrument
input terminal. Check whether control output terminals are
securely mounted to the actuator input terminals. Mount the
sensor or control output terminal securely.
• Check whether the wiring of sensor or control output terminals is correct.
The control output remains
in an ON status. • OUT low limit value is set to 100% or higher in Auxiliary function
setting mode 2. Set it to a suitable value.
The control output remains
in an OFF status. • OUT high limit value is set to 0% or less in Auxiliary function
setting mode 2. Set it to a suitable value.
• For all other malfunctions, please contact our main office or dealers.
Panasonic Industrial Devices SUNX Co., Ltd.
http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Office)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
Phone: +81-568-33-7861 FAX: +81-568-33-8591
About our sale network, please visit our website.
PRINTED IN JAPAN © Panasonic Industrial Devices SUNX Co., Ltd. 2012
Pursuant to the directive 2004/108/EC, article 9(2)
Panasonic Electric Works Europe AG
Rudolf-Diesel-Ring 2 83607 Holzkirchen, Germany
This product has been developed / produced for industrial use only.
Other manuals for KT7
1
Table of contents
Other Panasonic Temperature Controllers manuals

Panasonic
Panasonic KT4 series User manual

Panasonic
Panasonic KT2 User manual

Panasonic
Panasonic KT9 User manual

Panasonic
Panasonic CZ-64ESMC3 User manual

Panasonic
Panasonic CZ-64ESMC1U User manual

Panasonic
Panasonic KT4H User manual

Panasonic
Panasonic U-8ME1E81 User manual

Panasonic
Panasonic CZ-64ESMC3 User manual

Panasonic
Panasonic KT7 User manual

Panasonic
Panasonic CZ-64ESMC1U User manual