Panasonic KT4H User manual


2
CONTENTS
1. Model number Page
1.1 Model number ----------------------------------------------------------------------------- 5
1.2 How to read the rated label ------------------------------------------------------------ 5
2. Name and functions of the sections ------------------------------------------- 6
3. External dimensions
3.1 External dimensions ---------------------------------------------------------------------- 7
3.2 Tool cable (AKT4H820) external dimensions -------------------------------------- 7
3.3 CT (Current transformer) external dimensions ------------------------------------ 7
3.4 Terminal cover (AKT4H801) external dimensions -------------------------------- 8
4. Mounting to the control panel ------------------------------------------------------ 9
4.1 Panel cutout ------------------------------------------------------------------------------- 9
4.2 Mounting and removal to/from the control panel ---------------------------------- 9
5. Wiring
5.1 Terminal arrangement ------------------------------------------------------------------ 10
5.2 Lead wire solderless terminal -------------------------------------------------------- 10
5.3 Wiring of Heater burnout alarm ------------------------------------------------------ 10
6. Settings
6.1 Setting procedures ---------------------------------------------------------------------- 11
6.2 Setup --------------------------------------------------------------------------------------- 11
6.3 Basic operation of settings ------------------------------------------------------------ 11
6.4 Operation flowchart --------------------------------------------------------------------- 12
6.5 Main setting mode ----------------------------------------------------------------------- 13
6.6 Sub setting mode ------------------------------------------------------------------------ 14
6.7 Auxiliary function setting mode ------------------------------------------------------- 16
6.8 Setup mode ------------------------------------------------------------------------------- 18
7. Operation
7.1 Starting operation------------------------------------------------------------------------ 23
7.2 Control output OFF function----------------------------------------------------------- 23
7.3 Auto/Manual control switching ------------------------------------------------------- 24
7.4 Indicating Output MV (manipulated variable) ------------------------------------ 24
7.5 Auto-tuning/Auto-reset Perform/Cancel ------------------------------------------- 24
8. Basic usage
8.1 ON/OFF control ------------------------------------------------------------------------- 25
8.2 PID control ------------------------------------------------------------------------------- 25
8.3 How to use the alarm output --------------------------------------------------------- 25
8.4 Changing PV color ---------------------------------------------------------------------- 26
9. Auto-reset and ARW
9.1 Auto-reset --------------------------------------------------------------------------------- 27
9.2 ARW (Anti-reset windup) -------------------------------------------------------------- 27
10. Auto-tuning --------------------------------------------------------------------------------- 28
11. Action explanation
11.1 OUT1 PID, PI, PD, P actions ------------------------------------------------------- 29
11.2 OUT1 ON/OFF action ---------------------------------------------------------------- 29
11.3 Heater burnout alarm action -------------------------------------------------------- 30
11.4 Alarm action ----------------------------------------------------------------------------- 30
11.5 OUT2 (Heating/Cooling control) action [Reverse (Heating) action] ------- 31
11.6 OUT2 (Heating/Cooling control) action [Reverse (Heating) action]
(When setting dead band) ----------------------------------------------------------- 31
11.7 OUT2 (Heating/Cooling control) action [Reverse (Heating) action]
(When setting overlap band) ------------------------------------------------------- 32
11.8 OUT2 (Heating/Cooling control) action [Direct (Cooling) action] ---------- 32
11.9 OUT2 (Heating/Cooling control) action [Direct (Cooling) action]
(When setting dead band) ---------------------------------------------------------- 33
11.10 OUT2 (Heating/Cooling control) action [Direct (Cooling) action]
(When setting overlap band) ------------------------------------------------------ 33
11.11 SV rise rate, SV fall rate setting action ----------------------------------------- 34
12. Communication
12.1 System configuration ----------------------------------------------------------------- 36
12.2 Wiring ------------------------------------------------------------------------------------ 36
12.3 Communication parameter setting ------------------------------------------------ 38
12.4 Communication procedures -------------------------------------------------------- 39
12.5 MEWTOCOL --------------------------------------------------------------------------- 40
12.6 Modbus protocol ----------------------------------------------------------------------- 47
13. Specifications
13.1 Standard specifications -------------------------------------------------------------- 57
13.2 Optional specifications --------------------------------------------------------------- 60
14.Troubleshooting
14.1 Indication -------------------------------------------------------------------------------- 62
14.2 Key operation -------------------------------------------------------------------------- 63
14.3 Control ----------------------------------------------------------------------------------- 63
14.4 Communication------------------------------------------------------------------------- 64

3
Preface
Thank you for purchasing this Temperature controller KT4H/B.
This manual contains instructions for the mounting, functions, operations and notes when operating the KT4H/B.
For model confirmation and unit specifications, please read this manual carefully before starting operation.
To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
Notes
• This instrument should be used in accordance with the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause fire.
• Be sure to follow the warnings, cautions and notices. Not doing so could cause serious injury or accidents.
• The contents of this instruction manual are subject to change without notice.
• Care has been taken to assure that the contents of this instruction manual are correct, but if there are
any doubts, mistakes or questions, please inform our sales department.
• This instrument is designed to be installed in a control panel. If it is not, measures must be taken to
ensure that the operator cannot touch power terminals or other high voltage sections.
• Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
•Panasonic Industrial Devices SUNX Co., Ltd. is not responsible for any damages or secondary
damages incurred as a result of using this product, including any indirect damages.
Safety precautions (Be sure toread these precautions before using this instrument.)
The safety precautions are classified into categories: “Warning” and “Caution”.
Depending on circumstances, procedures indicated by Caution may be linked to serious results, so be
sure to follow the directions for usage.
Warning
Procedures which may lead to dangerous conditions and cause death or serious injury, if not carried
out properly.
Caution
Procedures which may lead to dangerous conditions and cause superficial to medium injury or
physical damage or may degrade or damage the product, if not carried out properly.
Warning
• To preventan electric shock or fire, do not handle the innerassembly.
• To prevent an electric shock, fire or damage to instrument, do not replace parts.
Safety precautions
• To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.
• This instrument is intended to be used for industrial machinery, machine tools and measuring
equipment. Verify correct usage after consulting purpose of use with our agency or main office. (Never
use this instrument for medical purposes with which human lives are involved.)
• External protection devices such as protection equipment against excessive temperature rise, etc.
must be installed, as malfunction of this product could result in serious damage to the system or injury
to personnel.
• This instrument must be used under the conditions and environment described in this manual.
Panasonic Industrial Devices SUNX Co., Ltd. does not accept liability for any injury, loss of life or
damage occurring due to the instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in,or as being utilized in the manufacture of weapons
of mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and
the final use of this instrument. In the case of resale, ensure that this instrument is not illegally exported.

4
Precautions
1. Installation precautions
Caution
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not change
rapidly
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come into direct contact with
the unit
Note: Do not install this instrument near flammable material even though the case of this instrument is
made of flame resistant resin.
Avoid setting this instrument directly on flammable material.
2. Wiring precautions
Caution
• Do not leave bits of wire in the instrument, because they could cause fire or malfunction.
• Use the solderless terminal with an insulation sleeve in which the M3 screw fits when wiring the KT4H/B.
• The terminal block of this instrument is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened with the terminal screw.
• When using a Terminal cover (AKT4H801), pass terminal wires numbered 7 to 12 into the holes of the
terminal cover. See (Fig. 3.4-2) on page 8.
• Tighten the terminal screw to within the specified torque.
If excessive force is applied to the screw when tightening, the terminal screw or case may be damaged.
• This controller does not have a built-in power switch, circuit breaker or fuse. It is necessary to install
them near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• Do not apply a commercial power source to the sensor which is connected to the input terminal nor
allow the power source to come into contact with the sensor.
• To extend a thermocouple’s lead wire, be sure to use a compensating lead wire in accordance with
the sensor input specification.
(If any other compensating lead wire is used, a temperature indication error may be caused.)
• Use the 3-wire RTD according to the sensor input specifications of this controller.
• (+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC differs from that of 0 to 1V DC.
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC: 9
(+) side input terminal number of 0 to 1V DC: 10
• When using a relay contact output type, use a relay according to the capacity of the load to protect the
built-in relay contact.
• When wiring, keep input wires (thermocouple, RTD, etc.) away from AC sources or load wires to avoid
external interference.
3. Operation and maintenance precautions
Caution
• It is recommended that the PID auto-tuning be performed on the trial run.
• Do not touch live terminals. This may cause electric shock or problems in operation.
• Turn the power supply to the instrument OFF before retightening the terminal and cleaning.
Working on or touching the terminal with the power switched ON may result in severe injury or death
due to Electric Shock.
• Use a soft, dry cloth when cleaning the instrument.
(Alcohol based substances may deface or tarnish the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object.

5
1. Model number
1.1 Model number
A K T 4 1
(1) (2) (3) (4) (5) (6) (7) (8)
(1) Color ---------------------------------------- H: Gray, B: Black
(2) Supply voltage ---------------------------- 1: 100 to 240V AC 2: 24V AC/DC
(3) Input type ---------------------------------- 1: Multi-input (Thermocouple, RTD, DC current and DC voltage can
be selected by key operation.
For DC current input, 50 shunt resistor (AKT4810, sold separately)
must be connected between input terminals.)
(4) Control output (OUT1) ------------------ 1: Relay contact 2: Non-contact voltage (Voltage output for SSR drive)
3: DC current
(5)Alarm output ------------------------------- 1: 1 point (1a) 2: 2 points (1a+1a)
(Alarm type and Energized/Deenergized can be selected by key
operation)
(If 2 points of alarm are selected, Heating/Cooling control cannot
be added.)
(6) Heating/Coolingcontrol (OUT2) --------- 0: Not available 1: Relay contact
2: Non-contact voltage (for SSR drive)
(7) Heater burnout alarm ------------------- 0: Not available 3: Single phase 20A 4: Single phase 50A
5: 3-phase 20A 6: 3-phase 50A
(Heater burnout alarm is not available for the DC current output type.)
(If Heating/Cooling control is selected, Heater burnout alarm cannot
be added.)
(8) Serial communication/Contact input - Blank: Not available 1: Serial communication 2: Contact input
1.2 How to read the rated label
The rated label is attached to the case.
(1)
(2)
(Fig.1.2-1)
(Example)
Supply voltage: 100 to 240V AC
Input type: Multi-input
Control output (OUT1): Relay contact
Alarm output: 1 point (1a)
Heating/Cooling control (OUT2) is not added.
Heater burnout alarm is not added.
Serial communication/Contact input is not added.
(1): Model number, supply voltage, input type, output type, etc. are entered.
(2): Lot number is entered.
(3): Safety standard markings
(3)

6
2. Name and functions of the sections
Bottom view
(Fig. 2-1)
Display
(1) Action indicators
: Lights respectively when temperature unit / is selected.
T/R : Lights during Serial communication (optional) TX output.
AT : Flashes during auto-tuning or auto-reset.
OUT1 : Lights when control output is ON or Heating output (optional) is ON.
For DC current output type, it flashes corresponding to the manipulated variable in 0.25 second cycles.
OUT2 : Lights when Cooling output (optional) is ON.
EVT1 : Lights when Alarm 1 output is ON.
EVT2 : Lights when Alarm 2 output (optional) is ON or Heater burnout alarm (optional) is ON.
LOCK: Lights when Lock 1, Lock 2 or Lock 3 is selected.
(2) MEMO display : Indicates the set value memory number.
(3) PV display : Indicates the PV (process variable).
(4) SV display : Indicates the SV (set value).
Operations
(5) Mode key : Selects the setting mode, and registers the set value.
(6) OUT/OFF key : The control output ON/OFF or Auto/Manual control can be switched.
(7) Increase key : Increases the numeric value.
(8) Decrease key : Decreases the numeric value.
(9) Tool connector : By connecting the tool cable (AKT4H820, sold separately), the following operations can
be conducted from the external computer using the exclusive tool software.
(1) Reading and setting of SV, PID and various set values from external computer
(2) Reading of PV and action status
(3) Function change
Cannot be used with Serial communication option.
Please download the exclusive tool software from our website.
(9)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
Model
KT4H or KT4B

7
3. External dimensions
3.1 External dimensions (Unit: mm) Common to KT4H/B
(Fig. 3.1-1)
3.2 Tool cable (AKT4H820) external dimensions (Unit: mm)
(Fig. 3.2-1)
3.3 CT (current transformer) external dimensions (Unit: mm)
AKT4815 (for 20A) AKT4816 (for 50A)
(Fig. 3.3-1)
Mounting frame
M3 screw
Rubber gasket Terminal cover (sold separately)
ø2.5 Plug 3-Pole type USB Plug

8
3.4 Terminal cover (AKT4H801) external dimensions (Unit: mm)
(Fig. 3.4-1)
Note when using a Terminal cover (AKT4H801)
When using a Terminal cover (AKT4H801), pass terminal wires numbered 7 to 12 into the holes of the
terminal cover. See (Fig. 3.4-2).
(Fig. 3.4-2)
Terminal cover

9
4. Mounting to the control panel
4.1 Panel cutout (Unit: mm)
Caution
If lateral close mounting is used for the controller, IP66 specification (Dust-proof/Drip-proof) may
be compromised, and all warranties will be invalidated.
Lateral close mounting
n: Number of units mounted
(Fig. 4.1-1)
4.2 Mounting and removal to/from the control panel
Caution
As the mounting frame is made of resin, do not use excessive force while tightening screws,
or the mounting frame could be damaged.
Tighten screws with one rotation upon the screw tips touching the panel.
The torque is approximately 0.05 to 0.06 N•m.
How to mount the KT4H
Mount the controller vertically to the flat, rigid panel to ensure it adheres to the Dust-proof/Drip-proof specification (IP66).
Mountable panel thickness: 1 to 5mm
(1) Insert the controller from the front side of the panel. (Fig. 4.2-1)
(2) Insert the mounting frame until the frame tips come into contact with the panel, and fasten with screws.
Tighten screws with one rotation upon the screw tips touching the panel.
The torque is approximately 0.05 to 0.06 N•m. (Fig. 4.2-2)
How to remove the mounting frame (Fig. 4.2-3)
(1) Turn the power to the unit OFF, and disconnect all wires before removing the mounting frame.
(2) Insert a flat blade screwdriver between the screw frame and unit 1.
(3) Slowly push the frame upward using the screwdriver 2, while pushing the unit toward the panel 3.
(4) Repeat step (2) and slowly push the frame downward using the screwdriver for the other side.
The frame can be removed little by little by repeating these steps.
(Fig. 4.2-1) (Fig. 4.2-2) (Fig. 4.2-3)
75
45+0.5
0
45+0.5
0
45+0.5
0
n×48-3+0.5
0
Rubber gasket
Mounting frame

10
5. Wiring
Warning
Turn the power supply to the instrument off before wiring.
Working on or touching the terminal with the power switched on may result in severe injury
or death due to Electric Shock.
5.1 Terminal arrangement •EVT1 :Alarm 1 output
•EVT2 : Alarm 2 output (option) or
Heater burnout alarm output (option)
(Utilize common output terminals.)
• OUT1 : Control output or Heating output (option)
•OUT2 : Cooling output (option)
•TC : Thermocouple input
•RTD : Resistance temperature detector input
•DC : DC current, DC voltage input
(For DC voltage input, + side
terminal number differs depending
on the voltage.)
For DC current input, 50 shunt resistor
(AKT4810, sold separately) must be
connected between input terminals.
•CT1 : Current transformer input 1
(Option: Single phase, 3-phase)
•CT2 : Current transformer input 2
(Fig. 5.1-1) (Option: 3-phase)
•DI : Contact input (option)
•RS-485: Serial communication RS-485 (option)
When using a Terminal cover (AKT4H801), refer to Section “3.4 Note when using a Terminal cover (AKT4H801)” on p.8.
5.2 Lead wire solderless terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown below.
The torque is approximately 0.63N•m.
Solderless
terminal Manufacturer Model Tightening torque
Nichifu Terminal Industries CO.,LTD. TMEV1.25Y-3
Y type Japan Solderless Terminal MFG CO.,LTD. VD1.25-B3A
Nichifu Terminal Industries CO.,LTD. TMEV1.25-3
Round type Japan Solderless Terminal MFG CO.,LTD. V1.25-3
0.63N•m
(Fig. 5.2-1)
5.3 Wiring of Heater burnout alarm (Option: Single phase, 3-phase)
This alarm is not usable for detecting heater current under phase control.
Use the current transformer (CT) provided, and pass one lead wire of the heater circuit into the hole of
the CT. (Fig. 5.3-1)
When wiring, keep the CT wire away from AC sources or load wires to avoid the external interference.
In the case of 3-phase, pass any 2 lead wires of R, S, T into the CT, and connect them with CT1 (13, 14)
and CT2 terminals (14, 15). (Fig. 5.3-2)
Solder the CT and wires connected to the CT input terminals. (There is no polarity.)
(Fig. 5.3-1) (Fig. 5.3-2)
(13)
CT
(14)
R
S
T
Pass any 2 wires of R, S and T
into CT.
CT1 input terminals
Heater
Power
supply
ø3.2mm 3.2mm
5.8mm or less
5.8mm or less
Solder the CT and wires connected
to the CT input terminals. (There
is no polarity.)

11
6. Settings
Characters used in this manual
Number -1 0 1 2 3 4 5 6 7 8 9
Indication
Alphabet A B C D E F G H I J K L M
Indication
Alphabet N O P Q R S T U V W X Y Z
Indication
6.1 Setting procedures
(1) Setup : Set the Input type,Alarm type, etc. in the Setup mode.
(If the users’ specification is the same as the default value of the KT4H/B, it is not
necessary to set.)
(2) Main setting mode : Set SV in the Main setting mode.
(3) Sub setting mode : Set PID, A1 value, etc.
(If the users’ PID values are the same as the default value of the KT4H/B, it is not
necessary to set.)
(4) Auxiliary function setting mode:
Select the lock function, communication conditions (serial communication option), etc.
(If the users’ specifications are the same as the default value of the KT4H/B, it is not
necessary to set.)
Power ON
Run
6.2 Setup
Setup should occur before using this controller, to set the Input type, Alarm action, Control action, etc.
according to the users’ conditions.
Default values: Input (K, -200 to 1370 ),Alarm 1 type (No alarm action), Reverse (Heating) action
If the users’ specifications are the same as the default value of the KT4H/B, it is not necessary to set up the
controller.
6.3 Basic operation of settings
To proceed to each setting mode, refer to instructions of each mode’s section.
To set or select each setting item, use the or key, then register the value with the key.

12
6.4 Operation flowchart
This instrument has been classified into the following modes and setting items.
Power ON For 3 seconds after power on, the PV display indicates the
input type, and the SV display indicates input range high limit
value (thermocouple, RTD input) or scaling high limit value
(DC voltage, current input).
Control output OFF/Manual control Control output OFF
(Approx. 1sec)
Auto/Manual control
PV/SV display mode (Automatic control) (Approx. 3sec) Output MV indication
+ + (Approx. 3sec) + (Approx. 3sec)
[Main setting mode](p.13) [Sub setting mode](p.14) [Auxiliary function setting mode](p.16) [Setup mode] (p.18)
SV
[1]
Auto-tuning/
Auto-reset
[5]
Set value
lock
[17]
Input type
[25]
Alarm 2
Energized/
Deenergized [41]
SV2
[2]
OUT1
proportional
band [6]
Sensor
correction
[18]
Scaling high
limit
[26]
Alarm 1
hysteresis
[42]
SV3
[3]
OUT2
proportional
band [7]
Communication
protocol
[19]
Scaling low
limit
[27]
Alarm 2
hysteresis
[43]
SV4
[4]
Integral time
[8]
Instrument
number
[20]
Decimal point
place
[28]
Alarm 1 action
delayed timer
[44]
Derivative time
[9]
Communication
speed [21]
PV filter time
constant [29]
Alarm 2 action
delayed timer
[45]
ARW
[10]
Data bit/Parity
[22]
OUT1 high limit
[30]
SV rise rate
[46]
OUT1
proportional
cycle [11]
Stop bit
[23]
OUT1 low limit
[31]
SV fall rate
[47]
OUT2
proportional
cycle [12]
Communication
response time
[24]
OUT1 ON/OFF
action hysteresis
[32]
Direct/Reverse
control action
[48]
Alarm 1 value
[13]
OUT2 action
mode
[33]
AT bias
[49]
Alarm 2 value
[14]
OUT2 high limit
[34]
Contact input
function
[50]
Heater burnout
alarm value
[15]
OUT2 low limit
[35]
Output status
selection when
input abnormal
[51]
Heater burnout
alarm 2 value
[16]
Overlap/Dead
band
[36]
OUT/OFF key
function
[52]
OUT2 ON/OFF
action hysteresis
[37]
Backlight
[53]
Alarm 1 type
[38]
PV color
[54]
Alarm 2 type
[39]
PV color
range
[55]
Alarm 1
Energized/
Deenergized [40]
Backlight time
[56]
[Key operation]
•
+ : Press key while pressing key.
•
+ (Approx.3sec) : Press key for 3 seconds while pressing key.
•
+ ( Approx.3sec) : Press key for 3 seconds while pressing key.
•
: This means that if key is pressed, the set value is saved,
and the controller proceeds to the next setting item.
•
Setting items with dotted lines are optional, and they appear only when the options are added.
•
Numbers such as [1], [2], etc. are setting item numbers.

13
6.5 Main setting mode
To enter the Main setting mode, press key in the PV/SV display mode.
To set or select each setting item, use or key, then register the value with key.
Setting item numbers such as [1], [2], etc. are the same as those on the “6.4 Operation flowchart” (p.12).
Character Name, Function, Setting range Default value
SV setting 0
[1] • Sets SV.
• Setting range: Scaling low limit to Scaling high limit
SV2 setting 0
[2] • Sets SV2.
Not available if the Contact input option is not applied, if Serial communication option is
applied, or if OUT/OFF external selection 2 is selected during Contact input function
selection.
• Setting range: Scaling low limit to Scaling high limit
SV3 setting 0
[3] • Sets SV3.
Not available if the Contact input option is not applied, if Serial communication option is
applied, or if OUT/OFF external selection 1 or 2 is selected during Contact input
function selection.
• Setting range: Scaling low limit to Scaling high limit
SV4 setting 0
[4] • Sets SV4.
Not available if the Contact input option is not applied, if Serial communication option is
applied, or if OUT/OFF external selection 1 or 2 is selected during Contact input
function selection.
• Setting range: Scaling low limit to Scaling high limit

14
6.6 Sub setting mode
To enter the Sub setting mode, press key while pressing key in the PV/SV display mode.
To set or select each setting item, use or key, then register the value with key.
Setting item numbers such as [5], [6], etc. are the same as those on the “6.4 Operation flowchart” (p.12).
Character Name, Function, Setting range Default value
Auto-tuning/Auto-reset selection
[5] • SelectsAuto-tuning Perform/Cancel (PID) or Auto-reset Perform/Cancel (P, PD action).
Not available for ON/OFF and PI actions.
• If the auto-tuning is cancelled during the process, P, I and D values revert to the previous
values before auto-tuning was performed.
• If the auto-tuning is not finished after 4 hours, it is cancelled automatically.
• Auto-reset is cancelled in approximately 4 minutes. It cannot be released while performing
this function.
• : Auto-tuning/Auto-reset Cancel
/ :Auto-tuning/Auto-reset Perform
OUT1 proportional band setting 10
[6] • Sets the proportional band for OUT1.
OUT1 becomes ON/OFF action when set to 0 or 0.0
• Setting range: 0 to 1000 (2000 ),TCorRTD input with adecimalpoint: 0.0 to 1000.0 ( )
DC input: 0.0 to 100.0%
[Percentage of the scaling span (scaling high limit - scaling low limit)]
OUT2 proportional band setting 1.0 times
[7] • Sets the proportional band for OUT2.
OUT2 becomes ON/OFF action when set to 0.0.
Not available if Heating/Cooling control option is not added, or if OUT1 is ON/OFF action.
• Setting range: 0.0 to 10.0 times (multiplying factor to OUT1 proportional band)
Integral time setting 200 seconds
[8] • Sets integral time for OUT1.
Off when set to 0.
Not available if OUT1 is ON/OFF action.
Auto-reset can be performed when PD is control action (I=0).
• Setting range: 0 to 1000 seconds
Derivative time setting 50 seconds
[9] • Sets derivative time for OUT1.
Off when set to 0.
Not available if OUT1 is ON/OFF action.
• Setting range: 0 to 300 seconds
ARW setting 50%
[10] • Sets ARW (anti-reset windup) for OUT1.
Available only when PID is the control action.
• Setting range: 0 to 100%
OUT1 proportional cycle setting
• Sets proportional cycle for OUT1. Relay contact: 30sec
Non-contact voltage: 3sec
[11]
For relay contact output, if the proportional cycle time is decreased, the frequency of the
relay action increases, and the life of the relay contact is shortened.
Not available if OUT1 is ON/OFF action or DC current output type.
• Setting range: 1 to 120 seconds
OUT2 proportional cycle setting
• Sets proportional cycle for OUT2. Relay contact: 30sec
Non-contact voltage: 3sec
[12]
For relay contact output, if the proportional cycle time is decreased, the frequency of the
relay action increases, and the life of the relay contact is shortened.
Not available if Heating/Cooling control option is not applied, or when OUT2 is ON/OFF
action.
• Setting range: 1 to 120 seconds

15
Character Name, Function, Setting range Default value
Alarm 1 value setting 0
[13] • Sets action point for Alarm 1 output.
Setting the value to 0 or 0.0 disables the function (except Process high and Process low
alarm).
Not available if No alarm action is selected duringAlarm 1 type selection.
• Setting range: Refer to (Table 6.6-1).
Alarm 2 value setting 0
[14] • Sets action point for Alarm 2 output.
Setting the value to 0 or 0.0 disables the function (except Process high and Process low
alarm).
Not available if theAlarm 2 option is not applied, or if No alarm action is selected during
Alarm 2 type selection.
• Setting range: Refer to (Table 6.6-1).
Heater burnout alarm value setting 0.0A
[15]
,
XX.X
alternating
display
• Sets the heater current value for Heater burnout alarm.
CT1 current value is indicated on the PV display.
When OUT1 is ON, the CT1 current value is updated. When OUT1 is OFF, the KT4H/B
memorizes the previous value when OUT1 was ON.
Setting to 0.0 disables the alarm.
Upon returning to set limits, the alarm will stop.
Available only when Heater burnout alarm option (single phase or 3-phase) is added.
• Rated current: 20A(0.0 to 20.0A), 50A (0.0 to 50.0A)
Heater burnout alarm 2 value setting 0.0A
[16]
,
XX.X
alternating
display
• Sets the heater current value for Heater burnout alarm 2.
CT2 current value is indicated on the PV display.
When OUT1 is ON, the CT2 current value is updated. When OUT1 is OFF, the KT4H/B
memorizes the previous value when OUT1 was ON.
Setting to 0.0 disables the alarm.
Upon returning to set limits, the alarm will stop.
Available only when Heater burnout alarm option (3-phase) is added.
• Rated current: 20A(0.0 to 20.0A), 50A (0.0 to 50.0A)
(Table 6.6-1) Alarm type Setting range
High limit alarm - (Input span) to input span ( ) *1
Low limit alarm - (Input span) to input span ( ) *1
High/Low limits alarm 0 to input span ( ) *1
High/Low limit range alarm 0 to input span ( ) *1
Process high alarm Input range low limit value to input range high limit value *2
Process low alarm Input range low limit value to input range high limit value *2
High limit alarm with standby - (Input span) to input span ( ) *1
Low limit alarm with standby - (Input span) to input span ( ) *1
High/Low limits alarm with standby 0 to input span ( ) *1
*1: For DC input, the input span is the same as the scaling span.
*2: For DC input, input range low (or high) limit value is the same as scaling low (or high) limit value.

16
6.7 Auxiliary function setting mode
To enter theAuxiliary function setting mode, press key for approximately 3 seconds while pressing
key in the PV/SV display mode.
To set or select each setting item, use or key, then register the value with key.
Setting item numbers such as [17], [18], etc. are the same as those on the “6.4 Operation flowchart” (p.12).
Character Name, Function, Setting range Default value
Set value lock selection Unlock
[17] • Locks the set values to prevent setting errors.
The setting item to be locked depends on the designation.
If Lock 1 or Lock 2 is selected, PIDAuto- tuning and Auto-reset cannot be carried out.
• (Unlock): All set values can be changed.
(Lock 1): None of the set values can be changed.
(Lock 2): Only main setting mode can be changed.
(Lock 3):All set values can be changed. However, changed values revert to their
previous value after power is turned off because they are not saved in the
non-volatile memory.
Do not change any setting item in Setup mode. If any item in Setup mode
is changed, it will affect other setting items such as the SV and Alarm
value.
Be sure to select Lock 3 when changing the set value frequently via communi-
cation function. (If the value set by the communication function is the same as the
value before the setting, the value will not be written in the non-volatile memory.)
Sensor correction setting 0.0
[18] • Sets the correction value for the sensor.
This corrects the input value from the sensor. When a sensor cannot be set at the exact
location where control is desired, the sensor measured temperature may deviate from the
temperature in the controlled location.
When controlling with plural controllers, sometimes the measured temperatures (input value)
do not concur with the same set value due to difference in sensor accuracy or dispersion
of load capacities. In such a case, the control can be set at the desired temperature by
adjusting the input value of sensors.
PV= Current PV+ Sensor correction value
• Setting range: -100.0 to 100.0 ( ),
DC voltage, current input: -1000 to 1000 (The placement of the decimal point
follows the selection.)
Communication protocol selection Modbus ASCII mode
[19] • Selects the communication protocol.
Not available if the Serial communication option is not added, or if Contact input option is
added.
• : Modbus ASCII mode
: Modbus RTU mode
: MEWTOCOL (slave)
Instrument number setting 1
[20] • Sets the instrument number individually to each instrument when communicating by
connecting plural instruments.
Not available if Serial communication option is not added or if Contact input option is added.
• Setting range: 1 to 99
Communication speed selection 9600bps
[21] • Selects a communication speed equal to that of the host computer.
Not available if Serial communication option is not added or if the Contact input option is
added.
• : 2400bps
: 4800bps
: 9600bps
: 19200bps

17
Character Name, Function, Setting range Default value
Data bit/Parity selection 7 bits/Even parity
[22] • Selects the data bit and parity.
Not available if the Serial communication option is not added or if Contact input option is
added.
• : 8 bits/No parity
: 7 bits/No parity
: 8 bits/Even parity
: 7 bits/Even parity
: 8 bits/Odd parity
: 7 bits/Odd parity
Stop bit selection 1
[23] • Selects the stop bit.
Not available if Serial communication option is not added or if Contact input option is added.
• : 1
: 2
Communication response time setting 5ms
[24] • Sets the minimum response time of communication.
Not available if Serial communication option is not added or if Contact input option is added.
• Setting range: 5 to 99ms

18
6.8 Setup mode
To enter the Setup mode, press key while pressing key for approximately 3 seconds in the PV/SV
display mode.
To set or select each setting item, use or key, then register the value with key.
Setting item numbers such as [25], [26], etc. are the same as those on the “6.4 Operation flowchart” (p.12).
Character Name, Function, Setting range Default value
Input type selection K(-200 to 1370 )
• The input type can be selected from a choice of; thermocouple (10 types), RTD (2 types),
DC current (2 types) and DC voltage (4 types), and the unit / can be selected as well.
• When changing the input from DC voltage to other inputs, remove the sensor connected to
this controller first, then change input type.
•(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC differs from
that of 0 to 1V DC.
(+) side input terminal number of 0 to 5V DC, 1 to 5V DC, 0 to 10V DC: 9
(+) side input terminal number of 0 to 1V DC: 10
K -200 to 1370 K -320 to 2500
K -200.0 to 400.0 K -320.0 to 750.0
J -200 to 1000 J -320 to 1800
R 0 to 1760 R 0 to 3200
S 0 to 1760 S 0 to 3200
B 0 to 1820 B 0 to 3300
E -200 to 800 E -320 to 1500
T -200.0 to 400.0 T -320.0 to 750.0
N -200 to 1300 N -320 to 2300
PL- 0 to 1390 PL- 0 to 2500
C(W/Re5-26) 0 to 2315 C(W/Re5-26) 0 to 4200
Pt100 -200.0 to 850.0 Pt100 -320.0 to 1500.0
JPt100 -200.0 to 500.0 JPt100 -320.0 to 900.0
Pt100 -200 to 850 Pt100 -320 to 1500
JPt100 -200 to 500 JPt100 -320 to 900
4 to 20mA DC -2000 to 10000
0 to 20mA DC -2000 to 10000
0 to 1V DC -2000 to 10000
0 to 5V DC -2000 to 10000
1 to 5V DC -2000 to 10000
[25]
0 to 10V DC -2000 to 10000
Scaling high limit setting 1370
[26] • Sets scaling high limit value.
•Setting range: Scaling low limit value to input range high limit value
DC voltage, current input: -2000 to 10000 (The placement of the decimal
point follows the selection.)
Scaling low limit setting -200
[27] • Sets scaling low limit value.
•Setting range: Input range low limit value to Scaling high limit value
DC voltage, current input: -2000 to 10000 (The placement of the decimal
point follows the selection.)
Decimal point place selection No decimal point
[28] • Selects decimal point place.
Available only for DC input.
• : No decimal point
: 1 digit after the decimal point
: 2 digits after the decimal point
: 3 digits after the decimal point

19
SV setting
OUT2 proportional band
Air cooling
Oil cooling
Water cooling
Character Name, Function, Setting range Default value
PV filter time constant setting 0.0 seconds
[29] • Sets PV filter time constant.
If the value is set too large, it affects control result due to the delay of response.
• Setting range: 0.0 to 10.0 seconds
OUT1 high limit setting 100%
[30] • Sets the high limit value of OUT1.
Not available if OUT1 is ON/OFF action.
• Setting range: OUT1 low limit value to 100%
(DC current output type: OUT1 low limit value to 105%)
OUT1 low limit setting 0%
[31] • Sets the low limit value of OUT1.
Not available if OUT1 is ON/OFF action.
• Setting range: 0% to OUT1 high limit value
(DC current output type: -5% to OUT1 high limit value)
OUT1 ON/OFF action hysteresis setting 1.0
[32] • Sets ON/OFF action hysteresis for OUT1.
Available only when OUT1 is ON/OFF action.
• Setting range: 0.1 to 100.0 ( ),
DC voltage, current input: 1 to 1000 (The placement of the decimal point
follows the selection.)
OUT2 action mode selection Air cooling
[33] • Selects OUT2 action from air, oil and water cooling.
Not available if the Heating/Cooling control option
is not added or if OUT2 is ON/OFF action.
• Air cooling (linear characteristic)
Oil cooling (1.5th power of the linear characteristic)
Water cooling (2nd power of the linear characteristic)
(Fig. 6.8-1)
OUT2 high limit setting 100%
[34] • Sets the high limit value of OUT2.
Not available if Heating/Cooling control option is not added, or if OUT2 is ON/OFF action.
• Setting range: OUT2 low limit value to 100%
OUT2 low limit setting 0%
[35] • Sets the low limit value of OUT2.
Not available if Heating/Cooling control option is not added or if OUT2 is ON/OFF action.
• Setting range: 0% to OUT2 high limit value
Overlap band/Dead band setting 0.0
[36] • Sets the overlap band or dead band for OUT1 and OUT2.
+Set value: Dead band, -Set value: Overlap band
Available only when the Heating/Cooling control option is added.
• Setting range: -100.0 to 100.0 ( )
DC voltage, current input: -1000 to 1000 (The placement of the decimal
point follows the selection.)
OUT2 ON/OFF action hysteresis setting 1.0
[37] • Sets ON/OFF action hysteresis for OUT2.
Available only when Heating/Cooling control option is added and when OUT2 is ON/OFF
action.
• Setting range: 0.1 to 100.0 ( )
DC voltage, current input: 1 to 1000 (The placement of the decimal point
follows the selection.)

20
Character Name, Function, Setting range Default value
Alarm 1 type selection No alarm action
[38] • Selects an action type forAlarm 1. (Refer to Section “11.4 Alarm action” on p.30.)
• : No alarm action
: High limit alarm
: Low limit alarm
: High/Low limits alarm
: High/Low limit range alarm
: Process high alarm
: Process low alarm
: High limit alarm with standby
: Low limit alarm with standby
: High/Low limits alarm with standby
Alarm 2 type selection No alarm action
[39] • Selects an action type forAlarm 2. (Refer to Section “11.4 Alarm action” on p.30.)
Available only when Alarm 2 option is added.
• Selection items are the same as those ofAlarm 1 type selection.
Alarm 1 Energized/Deenergized selection Energized
[40] • Selects Energized/Deenergized status for Alarm 1.
(Refer to “Alarm Energized/Deenergized” on p. 22.)
Not available if No alarm action is selected during Alarm 1 type selection.
• : Energized
: Deenergized
Alarm 2 Energized/Deenergized selection Energized
[41] • Selects Energized/Deenergized status for Alarm 2.
(Refer to “Alarm Energized/Deenergized” on p.22.)
Not available if Alarm 2 option is not added or if No alarm action is selected duringAlarm 2
type selection.
• Selection items are the same as those ofAlarm 1 Energized/Deenergized selection.
Alarm 1 hysteresis setting 1.0
[42] • Sets hysteresis for Alarm 1.
Not available if No alarm action is selected duringAlarm 1 type selection.
• Setting range: 0.1 to 100.0 ( )
DC voltage, current input: 1 to 1000 (The placement of the decimal point
follows the selection.)
Alarm 2 hysteresis setting 1.0
[43] • Sets hysteresis for Alarm 2.
Not available if Alarm 2 option is not added or if No alarm action is selected during Alarm 2
type selection.
• Setting range: 0.1 to 100.0 ( )
DC voltage, current input: 1 to1000 (The placement of the decimal point
follows the selection.)
Alarm 1 action delayed timer setting 0 seconds
[44] • SetsAlarm 1 action delayed timer.
When setting time has elapsed after the input enters the alarm output range, the alarm is
activated.
Not available if No alarm action is selected duringAlarm 1 type selection.
• Setting range: 0 to 10000 seconds
Alarm 2 action delayed timer setting 0 seconds
[45] • SetsAlarm 2 action delayed timer.
When setting time has elapsed after the input enters the alarm output range, the alarm is
activated.
Not available if Alarm 2 option is not added or if No alarm action is selected duringAlarm 2
type selection.
• Setting range: 0 to 10000 seconds
This manual suits for next models
1
Table of contents
Other Panasonic Temperature Controllers manuals

Panasonic
Panasonic KT7 User manual

Panasonic
Panasonic CZ-64ESMC3 User manual

Panasonic
Panasonic CZ-64ESMC3 User manual

Panasonic
Panasonic CZ-64ESMC1U User manual

Panasonic
Panasonic CZ-64ESMC1U User manual

Panasonic
Panasonic KT2 User manual

Panasonic
Panasonic U-8ME1E81 User manual

Panasonic
Panasonic KT2 Use and care manual

Panasonic
Panasonic KT9 User manual

Panasonic
Panasonic KT7 User manual