Para systems EN400 User manual

User's Manual
Enspire
Series UPS

1
© Copyright 2006
1. Introduction 2
2. Controls and Indicators 6
3. Installation 7
4. Operation 10
5. Troubleshooting 12
6. Replacing the Battery 13
7. Obtaining Service 16
8. Specifications 17
9. Limited Product Warranty 18
A1. Declaration of Conformity 19
English

2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
English
Thankyouforpurchasingthispowerprotectionproduct. Ithasbeendesigned
andmanufacturedtoprovidemanyyearsof trouble freeservice.
Please read this manual before installing your Enspire Series UPS, models
EN400, EN600 as it provides important information that should be followed
during installation and maintenance of the UPS and batteries allowing you to
correctly set up your system for the maximum safety and performance. In-
cludedis informationoncustomer supportandfactory serviceifit isrequired. If
you experience a problem with the UPS please refer to the Troubleshooting
guide in this manual to correct the problem or collect enough information so
that theTechnical Support Department can rapidly assist you.
Thissymbol indicates "ATTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply"
This symbol indicates "Alternating Current Supply Phase"

3
WARNING: Risk of Electrical Shock. Hazardous live partsinside
these power supplies are energized from the battery even when the
AC input is disconnected.
CAUTION! Tode-energize the outputsofthe UPS:
1. If the UPS is on press and release the On/Off Button.
2. Disconnect the UPS from theAC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
theUPS fromtheACwall outletbeforeinstallingacomputer interface
cable. Reconnectthe power cordonlyafterall signaling connections
aremade.
CAUTION! Connect the UPS to a two pole, three wire grounding
ACwall outlet. The receptacle must beconnectedtotheappropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electricalcodes. Do notuseextension cords,adapterplugs, orsurge
strips.
English
CAUTION! Toreduce the risk of electrical shockwith the installa-
tion of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
WARNING: ThisUninterruptiblePowerSupplycontainspotentially
hazardousvoltages. Do not attempt todisassembletheUPS beyond
the battery replacement procedure. This UPS contains no user ser-
viceableparts. RepairsandBatteryreplacementmustbeperformed
byQUALIFIED SERVICEPERSONNELONLY.
CAUTION! To reduce the risk of fire, connect only to a circuit
providedwith20amperesmaximum branch circuit over-current pro-
tection in accordance with the National Electric Code, ANSI/NFPA
70.

4
English
AfterremovingyourUPS fromitscarton, itshouldbeinspectedfor damagethat
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrierwillnotbe honored. The packing materials that your UPS was shipped
in are carefully designed to minimize any shipping damage. In the unlikely
case that the UPS needs to be returned to the manufacturer, please use the
original packing material. Since the manufacturer is not responsible for ship-
pingdamageincurredwhenthesystemis returned, the original packing mate-
rialis inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!
Receiving Inspection
NOTICE: Thisequipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Sub-
partJof Part 15 of FCC Rules and theClassB limits for radio noise emissions
fromdigital apparatussetoutintheRadioInterferenceoftheCanadianDepart-
ment of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equip-
mentgeneratesandusesradiofrequencyandifnotinstalledand usedproperly,
that is, in strict accordance with the manufacturer's instructions, this equip-
ment may cause interference to radio and television reception. If this equip-
ment does cause interference to radio or television reception, which can be
determinedbyturningtheequipmentoff andon,theuseris encouragedto tryto
correcttheinterferencebyoneormoreofthefollowingmeasures:
Re-orientthereceivingantenna.
Relocatethecomputerwithrespect to the receiver.
Movethe computerawayfromthe receiver.
Plugthecomputerintoadifferent outlet so that the computer and receiver
areondifferent branch circuits.
Shieldedcommunications interface cables mustbeusedwith this product.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's
authoritytooperatetheequipment.
NOTE: TheseUPSsareshippedwiththebatteriesdisconnected. Thebatter-
ies must be connected before putting these UPSs into service. Refer to Sec-
tion 3 "Installation" for connecting the batteries.

5
English
Life Support Policy
Asa general policy, wedonotrecommendtheuseofany of our productsin life
supportapplications where failureormalfunction of theproductcanbe reason-
ablyexpected to cause failure of thelifesupportdeviceor to significantly affect
its safety or effectiveness. We do not recommend the use of any of our prod-
ucts in direct patient care. We will not knowingly sell our products for use in
such applications unless it receives in writing assurances satisfactory to us
that (a) the risks of injury or damage have been minimized, (b) the customer
assumes all such risks, and (c) our liability is adequately protected under the
circumstances.
Examplesofdevicesconsidered tobelife supportdevicesare neonataloxygen
analyzers,nerve stimulators (whether used for anesthesia, pain relief,orother
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectorsandalarms,pacemakers,hemodialysissystems,peritonealdialysis
systems,neonatal ventilator incubators, ventilators for both adultsandinfants,
anesthesiaventilators, and infusion pumpsaswellasany other devices desig-
nated as “critical” by the United States FDA.
Hospitalgrade wiring devices and leakage current may be orderedas options
onmanyof our UPS systems. We do not claim that units with this modification
arecertified orlistedasHospital Grade byusor any otherorganization. There-
fore, these units do not meet the requirements for use in direct patient care.

6
English
1. The Battery Backup and Surge output power receptacles.
2. TheLow Battery/Overload/Fault (Red)LED. TheLowBattery/Overload/
Fault (Red) LED illuminates in a steady state when the UPS has an inter-
nal fault and the audible alarm will be continously beeping. The Low Batt-
ery/Overload/Fault (Red) LED blinks when the UPS is Overloaded and the
audible alarm will sound one beep every half second. The Low Battery/
Overload/Fault (Red) LED blinks when the UPS reaches a Low Battery
Warning and the audible alarm will sound two beeps every five seconds.
TheLow Battery/Overload/Fault (Red) LED blinks when the battery is weak
or needs to be replaced and the audible alarm sounds three beeps
every thirty seconds.
3. The input circuit breaker will trip in the event the output load exceeds the
UPS’s power rating.
4. On/Off Button.
5. Theinput power cord.
6. The On Utility/On Battery (Green) LED. The On Utility/On Battery (green)
LED illuminates in a steady state when the UPS is on and operating in the
AC normal mode. The On Utility/On Battery LED blinks when the UPS is
operating in the Battery mode and the audible alarm will sound one beep
every five seconds.
7. TheSurge Only output power receptacles.
8. TheRJ11/45 modularconnectorsareusedfor single linephone/fax/modem
protection.
9. TheRJ45 connectorisfor theUSBcommunications portforUPS monitoring
and control.
Output Power Receptacles
EN400 NEMA5-15PW/6 ft cord
Model #
EN600 3-NEMA 5-15R Surge Only
3-NEMA 5-15R Battery Backup & Surge
Input Power Plug

7
English
INSTALLATION PLACEMENT
This UPS series is intended to be install in a temperature controlled environment
that is free of conductive contaminants. Select a location which will provide good air
circulation for the UPS at all times. Avoid locations near heating devices, water or
excessive humidity, or where the UPS is exposed to direct sunlight. Route power
cords so they cannot be walked on or damaged.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing the
UPS. Place the UPS in the final desired location and complete the rest of the
installation procedure. These UPSs are shipped with the internal batteries discon-
nected. The batteries must be connected before putting these UPSs into service.
See the Connecting The Batteries procedure to connect the batteries.
ENVIRONMENTAL
Operating/Storage Humidity: 95% Non-Condensing
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
Storage Temperature: -15 to +45°C (+5 to +113°F)
Audible Noise at 1 m (3 ft.): <45 dBA
Operating Temperature: 0 to 40 degrees C (+32 to +104 degrees F) at
Operating Elevation: 0 to 1,500m (0 to +5,000 ft)
Operating Temperature: 0 to 35 degrees C (+32 to +95 degrees F) at
Operating Elevation: 1501 to 3,000m (0 to +10,000 ft)
WALLMOUNTING
The wallmount configuration allows the user to mount the UPS on the wall. The
UPS's back panel has keyed mounting holes for attaching the UPS to the wall.
1. Once the location and position of the UPS has been determined, use the temp-
late to mark the screw hole position on the wall. CAUTION, you should always
were protective gear for your hands and eyes when operating power tools.
2. Attach the two retaining screws (provided) to the wall and make sure that the
retaining screws are screwed into structural material. Then clean the area of any
loose material. Do not tighten the retaining screws all the way in, leave approxi-
mately 3/16" of the retaining screws sticking out.
3. Position the UPS, so that the keyed mounting holes line up with the two retaining
screws. Slide the UPS down until it is resting securely on the retaining screws.
4. The Wallmount Configuration is complete. See Connecting your Equipment.

8
English
CONNECTINGTHEBATTERIES
(QUALIFIEDSERVICEPERSONNELONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to con-
nect the batteries.
1. RemovetheUPSfrom the shipping box and set on the floor orabenchtop.
2. Place the UPS receptacle side down.
3. Removethe battery compartmentretainingscrews. (FIG.1)
4. Removethebatterycompartmentcover.(FIG. 2)
5. Verify proper polarity. Connect the batterypositive(Red)wiretothebattery
positive (Red) terminal. (FIG. 3)
NOTE: Some sparking might occur, this is normal.
6. Re-install the battery compartment cover onto the UPS.
WARNING: DO NOTpinch the battery wires with battery compartmentcover.
7. Re-install the battery compartment retaining screws.
8. Continue with the rest of the Installation.
FIG. 3
FIG. 1
FIG. 2

9
English
CHARGINGTHEBATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
anACsourceandthereis anacceptableACvoltagepresent(100-140VAC). It
isrecommended that the UPS's batteriesbechargedforaminimum of 4 hours
before use. The UPS may be used immediately, however, the “On Battery”
runtimemaybelessthan normally expected. NOTE: If the UPS is going tobe
out of service or stored for a prolonged period of time, the batteries must be
rechargedforat least twenty-four hours every ninety days.
RJ45USBCOMMUNICATIONSPORT CONNECTION (OPTIONAL)
ThePowerMonitoring Software can be used with the UPS. Use only the inter-
facecable that comeswiththeUPS. Connect the USBcable(RJ45end) to the
RJ45USBcommunicationsportontheside oftheUPS. Connect theotherend
of the USB cable to the device that will be monitoring/controlling the UPS.
NOTE: Connecting to the communications port is optional. The UPS works
properlywithoutthisconnection.
CONNECTINGTHE UPSTO ANAC SOURCE
CAUTION - Toreducetherisk of fire, connect only to a circuit provided with 20
amperes maximum branch circuit over-current protection in accordance with
theNational Electric Code,ANSI/NFPA70. Plug the UPSintoatwo pole, three
wire,groundedreceptacleonly. Donot use extension cords, adapter plugs, or
surge strips.
PHONE/FAX/MODEMPROTECTIONCONNECTION(OPTIONAL)
Connect a single line phone, fax or modem line to the RJ-11/45 modular con-
nectors on the side of the UPS. This connection will require another length of
telephone cable (provided). The cable coming from the telephone service is
connected to the port marked “IN”. The equipment to be protected is con-
nectedtotheport marked"OUT". NOTE: Connectingtothephone/fax/modem
modularconnectorsisoptional. TheUPSworks properly without this connec-
tion.
CONNECTINGYOUREQUIPMENT
Plugthe critical equipment intotheBatteryBackup& Surge output receptacles
onthe UPS. Plug the non-critical equipment into the Surge Only output recep-
tacles on the UPS. Do not use extension cords, adapter plugs or surge strips
ontheoutputoftheUPS. Ensurethatyoudonotexceedthemaximumoutput
ratingof theUPS(refer to theinformationlabel ortheelectricalspecifications in
thismanual).
CAUTION! DO NOT connectalaserprinterto theoutputreceptacles on the
UPS.

10
English
SYSTEMOVERVIEW
This UPS protects computers, internetworking, security, and telecommunica-
tionsequipment from blackouts, brownouts,overvoltages,andsurges. During
normalAC operation, theUPS will quietly and confidentlyprotect your system
frompoweranomalies.
The UPS will charge the batteries with the UPS in the on or off position when
the UPS is plugged into the wall outlet and there is an acceptableAC voltage
present(100 - 140VAC). When a blackout, brownout, or anovervoltagecondi-
tionoccurs;the UPS will transfer to the battery mode,theOn Battery indicator
willilluminate andtheaudiblealarm willsoundonce every fivesecondsindicat-
ing that the commercial power is lost or unacceptable. When the commercial
power returns or is at an acceptable level, the UPS will automatically transfer
back to the AC normal mode and start recharging the batteries. During an
extended outage when there is approximately two minutes of backup time re-
maining the audible alarm will sound twice every five seconds. This Low Bat-
tery Warning is letting the user know that they should save all open files and
turn off their computer. When the batteries reach the predetermined level the
UPS will automatically shutdown protecting the batteries from over discharg-
ing. Once the commercial power returns the UPS will automatically restart,
providingsafeusablepower to the connected equipment and start recharging
thebatteries.
TURNING THE UNIT ON/OFF
On / Off Button
PressandholdtheOn/OffButtonforonebeepthenrelease the On/Off Button
to turn the UPS on and supply power to the load. The load is immediately
powered while the UPS runs a five second self test. Press the On/Off Button
forat least onesecondthenreleasethe On/Off Buttontoturnthe UPS off. The
UPS will continue to charge the batteries whenever it is plugged into a wall
outletand there is an acceptableAC voltagepresent.

11
English
RJ-45USB COMMUNICATIONS PORT
The USB communications protocol is HID. The HID USB driver comes stan-
dard in the Windows OS. Simply plug the USB cable into the UPS and the
computerthen follow the prompts on thescreen.
WEAK/BADBATTERY
TheUPSautomaticallyteststhebattery’sconditionandwillilluminatetheLow
Battery/Overload/FaultLEDandsoundthealarm. Thisalarmwillberepeated
until the batteries pass a self test. If the battery is weak, bad or disconnected,
theLowBattery/Overload/FaultLEDwill illuminateand thealarm willbeepthree
times every thirty seconds until the battery is reconnected or replaced. It is
recommendedthattheUPSbe allowedtochargeovernightbeforeperforminga
battery test to confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
LowBattery/Overload/FaultLEDwillilluminateandthe UPS will sound 1 beep
everyhalfsecond(AC and Battery modes). This alarm will remain on untilthe
excess load is removed or the UPS’s self protection circuit shuts the UPS
down.
POWERMONITORINGSOFTWARE
TheUPScomeswithpowermonitoringsoftware. Seethe software CD for the
installationof the power monitoring software.
ALARMS
ONBATTERY
WhentheUPSis operating on the batteries, the On Battery LED will illuminate
andthe audible alarm will sound onceevery five seconds. The alarm will stop
once the UPS returns to theAC normal mode.
LOWBATTERYWARNING
TheUPSwillsoundtwobeepseveryfivesecondswhenthebatteryreserveruns
low. This condition will continue untilAC returns or the UPS shuts down from
batteryexhaustion.
UPSFAULT
When the UPS detects a hardware fault, the Low Battery/Overload/Fault LED
willilluminateandthe UPS will sound a constant alarm. The fault condition,in
some instances, may be reset by turning the UPS off and then on.

12
English
PossibleCause
Symptom What To Do
Pressandreleasethe On/Off
button to start UPS
On/Off/button not pressed
UPSwill not turn on
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS
UPS operates in
battery mode only,
even though there
is normal AC
present
InputACcircuitbreakeris
tripped
UPS has detected an
internalfault Call for service
Fault LED is
illuminated
TheOnUtilityLED
is illuminated, but
there is no output
Disconnect the computer
cablefromtheUPSandpress
the On button. If UPS works
normally, the software has
control of the UPS
The UPS is being
controlledvia its
communicationsport
Thebatteriesmaybeweak
or at the end of useful
servicelife
Charge the batteries for 8-
hoursandretest. Iftheruntime
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated
UPS does not
provideexpected
runtime
LowBatteryLEDis
illuminated
Overload LED is
illuminated
Loose connections at the
batteries, Weak batteries,
Badbatteries
Theloadhasexceededthe
UPS's capacity
Checkbattery connections,
chargethebatteriesfor8-
hours,replacethebatteries
Checkthespecifications(see
section 8). Remove part of
theload

13
English
REPLACING THE BATTERY
WARNING! This UPS contains potentially hazardous voltages. Do not at-
tempt to disassemble the UPS beyond the battery replacement
procedure. This UPS contains no user serviceable parts. Re-
pairsandbatteryreplacement mustbeperformed by QUALIFIED
SERVICEPERSONNELONLY.
Donot openormutilate batteries. Releasedelectrolyteis harmful
to the skin and eyes and may be toxic.
CAUTION:
(QUALIFIEDSERVICEPERSONNELONLY)
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batter-
iesproperly. The batteries containlead and pose a hazardtothe
environmentand human healthifnotdisposed of properly. Refer
to local codes for proper disposal requirements or return the
battery to the supplier.
Although the battery system voltage is only 12VDC the battery
system can still present a risk of electrical shock. These batter-
ies produce sufficient current to burn wire or tools very rapidly,
producing molten metal. Observe these precautions when re-
placingthebatteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wearprotectiveeyegear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco-
nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the bat-
teryis, remove the source ofthegrounding. Contact with any
part of a grounded battery can result in an electrical shock.
The likelihood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
CAUTION:
PleasereadalloftheWARNINGSandCAUTIONSbeforeattemptingtoservice
thebatteries.

14
English
BATTERYREPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONSAND WARNINGS BEFOREATTEMPTING
TOREPLACETHEBATTERIES
1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press the On/Off Button for at least one second then release the On/Off
Button to turn the UPS off.
3. Unplug the UPS's power cord from theAC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the the UPS.
6. Turn the UPS over and lay it face down.
7. Removethe battery compartmentretaining screws. (FIG. 1)
8. Removethebatterycompartmentcover. (FIG. 2)
9. Graspthebattery and gently pull it out farenoughto disconnect the battery
wires.
10. Disconnect the battery positive (Red) wire. (FIG. 3)
11. Disconnect the battery negative (Black) wire. (FIG. 3)
NOTE: DONOTshortthe battery wires together.
12. Remove the battery and set aside.
NOTE: Orient the new battery in the same direction as the original battery.
13. Place the new battery close enough to connect the battery wires.
14. Connectthebatterynegative(Black)wiretothebatterynegativeterminal.
15. Connectthe battery positive (Red)wire to the battery positive terminal.
NOTE: Some sparking might occur, this is normal.
16. Install the new battery into the UPS.
17.Re-install the battery compartmentcover onto the UPS.
WARNING: DO NOTpinch the battery wires with battery compartmentcover.
Battery
Qty/Rating
EN600
1-12V5.0Ah
Model#
Replace batteries with the same number and type as originally
installedintheUPS. Thesebatterieshavepressureoperatedvents.
These UPSs contain sealed non-spillable maintenance-free lead
acidbatteries.
CAUTION:
CSB
Part #
RitarPower
Part #
HR1221W
RT1250
EN400
1-12V4.5Ah
GP1245
RT1245
Typical Recharge Time: 8-hoursfromtotaldischarge.
Typical Battery Life: 2-5 years, depending on discharge cycles and ambient
temperature.

15
English
FIG. 3
FIG. 1
FIG. 2
18. Re-install the battery compartment retaining screws.
19. Properly dispose of the old batteries at an appropriate recycling facility or
return them to the supplier in the packing material for the new batteries.
20. TheUPSis now ready for normal operation.

16
English
IF THE UPS REQUIRES SERVICE
1.UsetheTROUBLESHOOTING sectiontoeliminateobviouscauses.
2. Verify there are no circuit breakers tripped. Atripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax the Technical Support department at
thefollowingnumbers;Voicephone(972)446-7363,FAXline(972)446-9011
or visit our Web site at www.minutemanups.com the "Discussion Board".
Pleasehave the following informationavailableBEFOREcallingtheTechni-
cal Support Department.
A.Your name and address.
B. Where and when the unit was purchased.
C.All of the model information about your UPS.
D.Any information on the failure, including LEDs that may be illuminated.
E.Adescription of the protected equipment, including model numbers if
possible.
F.Atechnician will ask you for the above information and, if possible, help
solveyourproblemoverthephone. Intheeventthattheunitrequires
factory service, the technician will issue you a Return MaterialAuthoriza-
tionNumber(RMA#).
G. If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be acharge for repair.
4.Pack the UPS in its original packaging. If the original packagingisnolonger
available, ask theTechnical Support Technician about obtaining a new set.
It is important to pack the UPS properly in order to avoid damage in transit.
NeveruseStyrofoam beads for a packingmaterial.
A. Include a letter with your name, address, day time phone number, RMA
number,acopy of youroriginalsales receipt, andabriefdescription of the
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMANUPS
1455LeMayDrive
Carrollton,TX75007
ATTN: RMA#_______

17
English
120VAC
400VA / 200W 600VA / 300W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Simulated Sine Wave
Frequency 50/60Hz, +/-0.5Hz (unless synchronized to utility)
NominalVoltage
Maximum Power Capacity
6-8 ms Typical
>90% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-5Hz, autosensing
0 - 160VAC
100 - 140VAC
120VAC: 100 - 140VAC
Transfer Time
Efficiency (Normal Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
EN400
ModelNumber SYSTEM SPECIFICATIONS
Voltage Range
OUTPUTNON-BATTERYOPERATION
INPUT
Number of Phase Single (1∅2W +G)
NominalVoltage 120VAC
Low Voltage Transfer Point 96V(+/-3%) resets to Utility Power at 101V(+/-3%) or higher
High Voltage Transfer Point 146V(+/-3%) resets to Utility Power at 140V(+/-3%) or lower
Frequency Range 60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
OUTPUTBATTERYOPERATION
Voltage Regulation Nominal +/-5% (until Low Battery Warning)
Overload Capacity 105% for 10-seconds, 115% Shutdown Immediately
EN600
Runtime: Full Load (minutes)
Runtime: Half Load (minutes) 10
2
Surge Energy Rating 320 J
PHYSICAL
Weight - Net
Size - Net L X W X H
Size - Shipping L X W X H
Weight - Shipping
6.44 lbs (2.92 Kgs)
11.97 x 4.84 x 3.35" (304 x 123 x 85 mm)
15.0 x 8.20 x 5.43" (380 x 208 x 138 mm)
8.0 lbs (3.3 Kgs)
7.05 lbs (3.20 Kgs)
8.0 lbs (3.6 Kgs)
Safety Approvals, EMC REGULATORYCOMPLIANCE
UL1778, cUL (CSA 22.2 no. 107.1), FCC Class B

18
English
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied
and operated within specified conditions, against faulty materials (excluding the
batteries) or workmanship for a period of three years from the date of purchase.
Para Systems Inc. (Para Systems) warrants the batteries for a period of two years
from the date of purchase. For equipment sites within the United States and Canada,
this warranty covers repair or replacement of defective equipment at the discretion of
Para Systems. Repair will be from the nearest authorized service center. Replace-
ment parts and warranty labor will be borne by Para Systems. For equipment lo-
cated outside of the United States and Canada, Para Systems only covers faulty
parts. Para Systems products repaired or replaced pursuant to this warranty shall
be warranted for the unexpired portion of the warranty applying to the original prod-
uct. This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is
improperly used, is subjected to an adverse operating environment, or is operated
outside the limits of its electrical specifications; (b) the equipment is repaired or
modified by anyone other than Para Systems or Para Systems approved personnel;
or (c) has been used in a manner contrary to the product’s User's Manual or other
written instructions.
Any technical advice furnished before or after delivery in regard to use or application
of Para Systems’s equipment is furnished without charge and on the basis that it
represents Para Systems’s best judgment under the circumstances, but it is used
at the recipient’s sole risk.
EXCEPTASPROVIDEDHEREIN,PARASYSTEMS MAKES NO WARRANTIES,EX-
PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITYAND
FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of
implied warranties; therefore, the aforesaid limitation(s) may not apply to the pur-
chaser.
EXCEPTAS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE
FORDIRECT,INDIRECT, SPECIAL,INCIDENTAL,ORCONSEQUENTIALDAMAGES
ARISINGOUTOFTHE USEOFTHIS PRODUCT,EVENIFADVISEDOFTHEPOSSI-
BILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs,
such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of
software, loss of data, cost of substitutes, claims by third parties, or otherwise. The
sole and exclusive remedy for breach of any warranty, expressed or implied, con-
cerning Para Systems’s products and the only obligation of Para Systems hereun-
der, shall be the repair or replacement of defective equipment, components, or
parts; or, at Para Systems’s option, refund of the purchase price or substitution with
an equivalent replacement product. This warranty gives you specific legal rights and
you may also have other rights which vary from state to state.

19
English
A1. DECLARATION OF CONFORMITY
ApplicationofCouncil Directive(s): UL 1778
Standard(s)towhichConformityisdeclared:
Manufacturer’sName: ParaSystems, Inc. (MINUTEMAN UPS)
Manufacturer’sAddress: 1455LeMayDrive
Carrollton,Texas 75007 USA
Type of Equipment: Uninterruptible Power Supplies(UPS)
Model No: EN400, EN600
I hereby declare that the equipment specified above conforms to the above
Directive(s).
Place: Carrollton,Texas, USA Date:November1,2006
RobertCalhoun
(Name) ManagerEngineering
(Position)
Yearof Manufacture: Beginning November 1,2006
FCC Class B
This manual suits for next models
1
Table of contents
Other Para systems UPS manuals

Para systems
Para systems Minuteman Encompass EC1000RT2U User manual

Para systems
Para systems E750RT2U User manual

Para systems
Para systems Minuteman Enspire Series User manual

Para systems
Para systems ED1000RM2U User manual

Para systems
Para systems Minuteman PRO-RT 2U Series User manual

Para systems
Para systems Minuteman ED10000T User manual

Para systems
Para systems Minuteman On-Line RT Series User manual

Para systems
Para systems E750RTXL2U User manual

Para systems
Para systems MM450 User manual

Para systems
Para systems ETR500 User manual