Para systems Minuteman Encompass EC1000RT2U User manual

User's Manual
Encompass RT
On-Line UPS Series
Para Systems, Inc.
1455 Lemay Dr.
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011
Internet: minutemanups.com
UPS Sizing: sizemyups.com
PN - 34000519 R3

1
1. Introduction 2
2. Controls and Indicators 6
3. Installation 9
4. Operation 14
5. Configurable Parameters & Settings 19
6. Obtaining Service 20
7. Troubleshooting 21
8. Replacing the Battery 22
9. Specifications 25
10. Limited Product Warranty 27
A1. Declaration of Conformity 28
Table Of Contents

3
2
Thankyouforpurchasingthispowerprotectionproduct. Ithasbeendesigned
and manufactured to provide many years of trouble free service. Please read
this manual before installing your Encompass On-Line Series UPS, models
EC1000RT2U, EC1500RT2U,EC2000RT2U,EC3000RT2Uasitprovidesim-
portantinformation thatshouldbefollowed duringtheinstallationand themain-
tenance of the UPS system allowing you to correctly set up your system for
the maximum safety and performance. Included is information on customer
support and factory service, if it is required. If you experience a problem with
the UPS system please refer to the Troubleshooting guide in this manual to
correct the problem or collect enough information so that the Technical Sup-
port Department can assist you.
CAUTION! Themaximumambientoperatingtemperaturefor this UPS series
is 40°C (“0 ~ 40°C” for Ambient Operation).
Theexternalventsandopeningson the UPS are provided for ventilation.
ToensurereliableoperationoftheUPSandtoprotecttheUPSfromover-
heating,these vents andopeningsmustnot be blocked orcovered.Do not
insert any object into any of the vents or openings that may hinder the ve-
ntilation.
Installthe UPS system in awellventilatedarea, away from excess moistu-
re,heat,dust,flammablegasorexplosives.
Leave adequate space (at least 20cm) in the front and at the rear of the
UPSsystemfor proper ventilation.
Do not mount the UPS system with its front or rear panel facing down at
any angle.
Before usage, you must allow the UPS system to adjust to room temper-
ature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture
condensing inside the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
CONSIGNES DE SÉCURITÉ IMPORTANTES
SAUVEGARDEZ CES CONSIGNES!
Veuillezlire cemanuelavant l'installationde l'onduleurmodèlesEC1000RT2U,
EC1500RT2U, EC2000RT2U, EC3000RT2U. Il contient de l'information
importantequi doit être respectée aucours de l'installation et del'entretien de
l'onduleur et des batteries. Cette information vous permettra de correctement
installerle système pour atteindre son rendement maximum en toute sécurité.
Chapter 1: Introduction
WARNING: Risk of Electrical Shock. Hazardous live parts inside these
power supplies are energized from the battery even when the AC input is
disconnected.
CAUTION! To reduce the risk of electrical shock in conditions where the
load equipment grounding cannot be verified, disconnect the UPS from the
AC wall outlet before installing a computer interface cable. Reconnect the
power cord only after all signaling connections are made.
CAUTION! Connect the UPS to a two pole, three wire grounded AC wall
outlet. The receptacle must be connected to the appropriate branch protec-
tion (circuit breaker or fuse). Connection to any other type of receptacle may
result in a shock hazard and violate local electrical codes. Do not plug the
UPS into extension cords, adapter plugs or surge strips.
CAUTION! To reduce the risk of electrical shock with the installation of this
UPS equipment and the connected equipment, the user must ensure that the
combined sum of theAC leakage current does not exceed 3.5mA.
WARNING: ThisUninterruptible Power Supply containspotentially hazard-
ous voltages. Do not attempt to disassemble the UPS beyond the battery
replacement procedure. This UPS contains no user serviceable parts. Re-
pairs and Battery replacement must be performed by QUALIFIED SERVICE
PERSONNELONLY.
CAUTION! To reduce the risk of fire, connect only to a utility powered
circuit provided with 20 / 30 amperes maximum branch circuit over-current
protection in accordance with the National Electric Code,ANSI/NFPA70.
WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these UPS systems. MINUTEMAN accepts no liabilities
and is not limited to: injury to the Service Personnel, or damages to; the UPS,
or the connected equipment caused by the incorrect installation or servicing
of the UPS system.
CAUTION! This UPS series is ONLYintended to be installed in an indoor
temperature controlled environment that is free of conductive contaminants.
This UPS series is not intended for use in a computer room as defined in the
Standard for the Protection of Electronic Computer/Data Processing Equip-
mentANSI/NFPA75.
NOTE: TheseUPSsareshippedwiththebatteriesdisconnected. Thebatter-
ies must be connected before putting these UPSs into service. Refer to Sec-
tion 3 "Installation" for connecting the batteries.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE
UPS. The mounting brackets are ONLYfor securing the UPS to the rack.

5
4
NOTICE: Thisequipment has been tested and found to comply with the limits
for a ClassAand/or B computing device in accordance with the specifications
in Subpart J of Part 15 of FCC Rules and the ClassAand/or B limits for radio
noiseemissions from digital apparatus set outin the Radio Interference of the
Canadian Department of Communications. These limits are designed to pro-
vide reasonable protection against such interference in a residential installa-
tion. This equipment generates and uses radio frequency and if not installed
and used properly, that is, in strict accordance with the manufacturer's in-
structions, this equipment may cause interference to radio and television re-
ception. If this equipment does cause interference to radio or television re-
ception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the
followingmeasures:
Re-orientthereceivingantenna.
Relocatethecomputerwithrespect to the receiver.
Movethe computer awayfromthereceiver.
Plugthecomputerintoadifferent outlet so that the computer and receiver
areon different branch circuits.
Shieldedcommunications interface cables must beusedwiththis product.
WARNING: Changes or modifications to this unit not expressly approved
by the party responsible for compliance could void the user's authority to
operatethe equipment.
ON BUTTON: When the UPS is connected to an AC source and
there is an acceptableAC voltage present; Press and then release
theONbutton after the audible alarm beeps twice to turn theUPS
on and power the load.
DC START:Press and then release the ON button after the au-
dible alarm beeps twice. Then within 10-seconds press and then
release the ON button after the audible alarm beeps twice to DC
start the UPS and power the load.
OFF BUTTON: When the UPS is in theAC normal mode; Press
and then release the OFF button after the audible alarm beeps
twice to turn the UPS off. The UPS will continue to charge the
batteries whenever it is plugged into a wall outlet and there is ac-
ceptableACvoltage present.
CAUTION! To de-energize the outputs of the UPS:
1. If the UPS is on press and then release the OFF button after the audible
alarm beeps twice to turn the UPS off.
2. Disconnect the UPS from theAC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
Life Support Policy
As a general policy, we do not recommend the use of any of our products in
life support applications where failure or malfunction of the product can be
reasonably expected to cause failure of the life support device or to signifi-
cantly affect its safety or effectiveness. We do not recommend the use of any
of our products in direct patient care. We will not knowingly sell our products
for use in such applications unless it receives in writing assurances satisfac-
tory to us that (a) the risks of injury or damage have been minimized, (b) the
customer assumes all such risks, and (c) our liability is adequately protected
under the circumstances.
Receiving Inspection
After removing your UPS from its carton, it should be inspected for damage
that may have occurred in shipping. Immediately notify the carrier and place
of purchase if any damage is found. Warranty claims for damage caused by
the carrier will not be honored. The packing materials that your UPS was
shipped in are carefully designed to minimize any shipping damage. In the
unlikely case that the UPS needs to be returned to the manufacturer, please
use the original packing material. Since the manufacturer is not responsible
for shipping damage incurred when the system is returned, the original pack-
ingmaterial is inexpensive insurance. PLEASE SAVE THE PACKING MATE-
RIALS!
© COPYRIGHT 2017 BY PARASYSTEMS, INC.
All Rights Reserved.All rights of this User's Manual (“Manual”), including but
not limited to the content, information, and figures are solely owned and re-
served by Para Systems, Inc. (“Para Systems”). The Manual can only be
applied to the operation or the use of this product. Any disposition, duplica-
tion, dissemination, reproduction, modification, translation, extraction, or us-
age of this Manual in whole or in part is prohibited without the prior written
permission of Para Systems. Given that Para Systems will continuously im-
prove and develop the product, changes may be made to the information in
thisManual at any time without obligation to notify any person of such revision
or changes. Para Systems will make all possible efforts to secure the accu-
racy and the integrity of this Manual. Para Systems disclaims any kinds or
forms of warranty, guarantee, or undertaking, either expressly or implicitly,
including but not limited to the completeness, faultlessness, accuracy, non-
infringement,merchantability or fitness for a particular purpose of the Manual.

7
6
NOTE: The LCD backlight will illuminate for 20-seconds when the UPS is con-
nectedtoutilitypower,whentheUPS isturnedON/OFF, whenanyof the buttonson
theLCDpanel are touchedandwhen the UPSswitchesto theBatterymode. When
the UPS has an event and/or an error code the LCD backlight will turn on and re-
mainon to alert the userthat an event has occurred.
Chapter 2: Controls and Indicators
1. The ON button is to turn the UPS on. Pressing the ON button during the
Batterymodewillsilence the alarm.
2. The OFF button is to turn the UPS off.
3. The Utility Power (Green) LED illuminates when Utility Power ispresent
andextinguishesduring the Battery mode.
4. The Load Bank 1 (Green) LED is illuminated when the Load Bank is on.
5. The Load Bank 2 (Green) LED is illuminated when the Load Bank is on.
6. The BypassActive(Yellow)LED illuminates when theUPSisintheBypass
mode.
7. The Weak/Bad Battery (Red) LED illuminates when the UPS detects a weak
battery, bad battery or if the battery is disconnected. The Weak/Bad Battery
iconis extinguished when the battery's condition isgood.
8. The LCD displays the status of the UPS.
9. Pressing the Enter button saves the changes made totheUPS settings.
10.Pressing the Page Up button goes to the previous page or will change the
UPSsettings.
11.Pressing the Page Down button goes to the next page.
12.PressingtheFunctionbuttonandthenthe Page Up button will initiate a 10-
secondbatterytest.
1. Displays the power flow of the UPS:
The UPS reports the following parameters on the LCD screen:
Input: Voltage, Frequency
Output: Voltage,Frequency,Current, Percentageof load
Battery: Voltage
Runtime: Thetime operating on the Battery mode in minutes
Temperature: The internal temperature of the UPS in degress C
2. TheSiteWiring Fault iconilluminates when the UPS detectsa site wiringprob-
lem. The SWF icon is extinguished when the UPS is connected to properly
wiredwall outlet.
3. TheAlarmSilencericon illuminates when the audible alarm hasbeen silenced.
4. TheOverloadicon will illuminatewhen the amount of loadattached to the UPS
is >106% of its power rating.
5. TheService icon illuminates when the UPS requires service.
6. TheAlarm(Fault)icon illuminates when the UPSdetectsaninternal fault.
7. Numerical values of the UPS parameters and error codes.
ACModePowerFlow
BatteryMode Power Flow
BypassMode Power Flow

9
8
INSTALLATION PLACEMENT
This UPS series is ONLYintended to be installed in an indoor temperature con-
trolled environment that is free of conductive contaminants. DO NOT operate the
UPSin: extremely dustyand/or uncleanareas, locationsnear heatingdevices, wa-
teror excessive humidity, or wherethe UPS is exposed todirect sunlight. Select a
location, which will provide good air circulation for the UPS at all times.
Route
power cords so they cannot be walked on or damaged. This UPS series is not
intendedforuse ina computer roomas definedin the Standardfor theProtection of
ElectronicComputer/Data ProcessingEquipmentANSI/NFPA75. Typicalbattery
lifeis 3to 5years. Environmental factors do affect battery life. High temperatures,
poorutility power, and frequent,short duration discharges have a negative impact
onbattery life.
Operating Temperature (Maximum): 0 to 40°C (+32 to +104°F)
Operating Elevation: 0 to 3,000m (0 to +10,000 ft)
Operatingand Storage Relative Humidity: 10%to 90%, non-condensing
Storage Temperature: -15 to +45°C (+5 to +113°F)
Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
REAR PANEL
1. The USB Communications Port is for UPS monitoring and control.
2. The RS232 Communications Port is for UPS monitoring and control.
3. The EPO (Emergency Power Off) Port is for UPS control.
4. TheR-J11/R-J45modularconnectors areused for 10/100/1000Base-T Netw-
ork/singleline Phone/Fax/Modemprotection.
5. Theinput power cord is for connecting to utility power.
6. The option slot is for option cords.
7. The BatteryBackup output receptacles. The output receptacles are electrically
wiredinto twosegments tosupport the"Load SheddingFunction" (Labeled 1 &
2). The 3KVAhas a locking receptacle (Always On) that does not support the
"LoadShedding Function". NOTE:The locking receptacle is not on all models.
8. Therackmountbrackets.
9. Theinputcircuit breakerwill trip in the event the loadexceeds theUPS’s power
rating.
10.The fanis forventilation.
11. Theoutputcircuit breaker willtripin the eventtheload exceeds theUPS’spower
rating. NOTE: The output circuit breaker is not on all models.
OutputPower Receptacles
NEMA5-15P
Model#
EC1500RT2U
EC2000RT2U
EC1000RT2U
EC3000RT2U
NEMA5-15P
NEMA5-20P
NEMAL5-30P
6-NEMA5-15R(Controllable)
6-NEMA5-15R(Controllable)
6-NEMA5-15/20R(Controllable)
6-NEMA5-15/20R(Controllable)
1-NEMAL5-30R (Always On)
INSTALLATION
Besure to read the installation placement and all the cautions before installing the
UPS. Place the UPS in the final desired location and complete the rest of the
installationprocedure. These UPSsare shippedwith theinternal batteries discon-
nected. The batteries must be connected before putting these UPSs into service.
Seethe "Connecting theBatteries" procedureto connect thebatteries andthen the
"Rackmount Configuration" to install the UPS into the rack. USE CAUTION: The
UPSis heavy. Usethe appropriate number of personnel when installingthe UPS.
InputPower Plug
(Allpower cordsare 10ft)
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS.
The mounting brackets are ONLYfor securing the UPS to the rack.
Chapter 3: Installation

11
10
RACKMOUNT CONFIGURATION
ThisUPS series comes with mounting brackets for the standard 19" (46.5cm)
rack pre-installed on the UPS. There are optional Rail Kits for the 4-post
racks and cabinets available. The screws for mounting the UPS to the rack
are included. NOTE: The Rail Kit for a 4-post rack and/or cabinet is included
withtheEC3000RT2U.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE
UPS. The mounting brackets are ONLYfor securing the UPS to the rack.
1. Mount the UPS into the rack and secure with the retaining screws (provid-
ed). WARNING: Use two or more people when installing the UPS, the
UPS is extremely heavy. Do not move the rack after the units have been
installed. The rack may become unstable due to the weight distribution.
2. The Rackmount Configuration is complete. See Connecting your Equipm-
ent.
CONNECTING THE BATTERIES
(QUALIFIEDSERVICEPERSONNELONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to con-
nectthebatteries.
WARNING: Use two or more people when installing the UPS, the UPS is
extremelyheavy.
1. Remove the UPS from the shipping box and place on a flat surface.
2. Grasp the battery door on the left hand side, pull it outward and then set it
aside (FIG. 1).
3. Press down to unlock the battery connector holder. Verify proper polarity.
Connect the battery connectors (red and black) together. Place the batt-
ery connectors in the battery connector holder and then relock the battery
connector holder (FIG. 2).
NOTE: Some sparking may occur this is normal.
4. Re-install the battery door on the UPS.
5. Connecting the Batteries is complete. See the Rackmount Configuration.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE
UPS. The mounting brackets are ONLYfor securing the UPS to the rack.
FIG. 1
FIG. 2

13
12
TOWER CONFIGURATION
The tower configuration allows the user to install the UPS in the up-right posi-
tion. The tower brackets are provided with the UPS. WARNING: Use two or
morepeoplewheninstallingthe UPS, the UPS is extremely heavy.
1. Once the locationoftheUPShas been determined, place the UPS on a flat
surface,removetherackmountbracketsfromtheUPSandthenattachthe
four (4) tower brakects as shown below.
2. Stand the UPS in the up-right position and place it in the desired location.
Make sure that the UPS is stable.
3. The LCD panel can be rotated to read in the up-right position. There are
twosmallslots,oneoneachsideoftheLCDpanel. Insertasmallflatscre-
wdriver into the slot to pop out the LCD panel. Position the LCD panel so
that it reads in the up-right position. Press the LCD panel back into the fr-
ontpanel.
WARNING: The UPS must be installed in the proper up-right position. If the
UPS is not installed in the proper up-right position the Batteries will be dam-
aged. OncetheUPSisplacedinthetowerbrackets,lookingat the front panel
theYELLOW Battery disconnected labelonthe top cover oftheUPSMUST be
on your left hand side.
4. The Tower Configuration is complete. See Connecting your Equipment.
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source and there is an acceptable AC voltage present (55V (load de-
pendent) - 150VAC). It is recommended that the UPS's batteries be charged
for a minimum of 4 hours before use. The UPS may be used immediately,
however,the“On-Battery”runtimemaybe lessthannormallyexpected. NOTE:
If the UPS is going to be out of service or stored for a prolonged period of
time, the batteries must be recharged for at least twenty-four hours every
ninety days.
CHECKING THE SITE WIRING FAULT
Afterplugging the UPS into theAC wall outlet, checkthe Site WiringFault icon
on the front panel of the UPS. If the Site Wiring Fault icon is illuminated and
error code Er16 is displayed, the UPS is plugged into an improperly wiredAC
wall outlet. If the UPS indicates a Site Wiring Fault have a Qualified Electri-
cian correct the problem.
CONNECTING THE UPS TO AN AC SOURCE
Plugthe UPS into a two pole, three wire, groundedAC walloutlet. TheACwall
outlet shall be near the UPS and shall be easily accessible. The plug on the
input power cord on this UPS series is intended to serve as a disconnect
device. DO NOT PLUG THE UPS INTO EXTENSION CORDS, ADAPTER
PLUGS OR SURGE STRIPS. DO NOT CUT THE INPUT PLUG OFF AND
ATTEMPT TO HARDWIRE THIS UPS, DOING SO WILL VOID THE WAR-
RANTY.
NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OP-
TIONAL)
Connecta 10/100/1000 Base-T network, single line phone, Fax orModemline
to the RJ11/45 modular connectors on the rear panel of the UPS. This con-
nection will require another length of telephone or network cable. The cable
coming from the telephone service or networked system is connected to the
port marked “IN”. The equipment to be protected is connected to the port
marked"OUT". NOTE: Connecting to the Network/Phone/Fax/Modemmodu-
lar connectors is optional. The UPS works properly without this connection.
CONNECTING YOUR EQUIPMENT
Plug the equipment into the output receptacles on the rear panel of the UPS.
Ensurethatyoudonotexceed the maximum output rating of the UPS (refer to
the information label or the Electrical Specifications in this manual). DO NOT
PLUG EXTENSION CORDS,ADAPTER PLUGS OR SURGE STRIPS INTO
THEOUTPUTRECEPTACLESOFTHEUPS.
CAUTION! DO NOT connect a laser printer to the output receptacles on the
UPS, unless the UPS is rated 2000VAor greater. Alaser printer draws signifi-
cantly more power when printing than at idle and may overload the UPS.

15
14
EMERGENCY POWER OFF (EPO) FUNCTION
Connect one end of a two (2) wire cable to the EPO port on the rear panel of
the UPS and the other end of the two (2) wire cable to an EPO switch. To
shutdown the UPS in the AC or the Battery mode short pin1 to pin2 for ap-
proximately 0.5-seconds. In the AC mode; the UPS must be turned off and
then back on again to restart the UPS. In the Battery mode; once the utility
power returns the UPS must be turned on to restart the UPS. The LCD will
display EPo for this function.
Chapter 4: Operation
The UPS will charge the batteries when the UPS is in the on or off position as
long as the UPS is plugged into the wall outlet and there is an acceptableAC
voltage present (55V (load dependent) - 150VAC). When a blackout, brown-
out, or an overvoltage condition occurs while the UPS is in the On-Line mode
or the Economy mode; the UPS will transfer to the battery mode, the On-
Battery indicator will illuminate and the audible alarm will sound once every
ten-secondsindicatingthattheutilitypowerislostor unacceptable. When the
utility power returns or is at an acceptable level, the UPS will automatically
transferbacktotheOn-Line mode or the Economy mode and start recharging
the batteries. During an extended outage when there is approximately two-
minutes of backup time remaining the audible alarm will sound twice every
five-seconds. This Low Battery Warning is letting the user know that they
should save all open files and turn off their equipment. When the batteries
reachthepredeterminedleveltheUPSwillautomatically shutdown protecting
the batteries from over discharging. Once the utility power returns the UPS
will automatically restart providing safe usable power to the connected equip-
ment and start recharging the batteries.
The Economy mode operation: The input utility power 'bypasses' the inverter
circuit and is connected directly to the output of the UPS powering the con-
nectedequipment while simultaneously charging the batteries. When a black-
out, brownout, or an overvoltage condition occurs the UPS will transfer to the
batterymode,the inverter will turn on powering the connectedequipment, the
On-Batteryindicator will illuminate andtheaudible alarm will sound onceevery
ten-secondsindicatingthattheutilitypowerislostor unacceptable. When the
utility power returns or is at an acceptable level, the UPS will automatically
transfer back to the Economy mode and start recharging the batteries.
COMMUNICATIONS PORT CONNECTION (OPTIONAL)
The Power Monitoring Software and interface cables can be used with the
UPS. Use only the interface cables that come with these UPSs. Connect the
interface cable (Serial or USB) to the appropriate communications port on the
rear panel of the UPS. Connect the other end of the cable to the device that
will be monitoring/controlling the UPS. NOTE: Connecting to the Communi-
cations Port is optional. The UPS works properly without this connection.
OPTION SLOT (OPTIONAL)
The option slot on the rear panel of the UPS is for the SNMP and the Relay
cards. Removethe cover plates from the option slot. Install the SNMP card or
the Relay card. Connect the appropriate interface cable to the SNMP card or
the Relay card on the rear panel of the UPS. Connect the other end of the
cable to the device that will be monitoring/controlling the UPS. NOTE: Using
the Option Slot optional. The UPS works properly without this connection.
SYSTEM OVERVIEW
This double conversion On-Line UPS protects computers, servers, telecom-
munications, security and other electronic equipment from blackouts, brown-
outs, overvoltages, and surges. This On-Line UPS converts the input AC to
DCandthen back to a true sine waveACoutput. The true sine wave output is
regulated within 2% of the nominal output voltage. The Power Factor Correc-
tion (PFC) circuitry corrects the input power factor to within 99% of unity and
blocks the load generated harmonic distortion from getting back on the input
AC line. This On-Line UPS provides a continuous true sine wave output with
zero transfer time and great regulation to protect your mission critical equip-
ment. The UPS will quietly and confidently protect your system from power
anomalies.
Block Diagram of the Basic Wiring and Internal Circuit Configuration

17
16
COMMUNICATIONS PORTS (RS232andUSB)
The RS232 communication port is a standard DB9 female. The pinout for the
port is below:
Pin 2: /TXD
Pin 3: /RXD
Pin 5: Ground
TheUSB protocol is HID. The HID USB driver is the standard fortheWindows
OS. Simplyplug the USB cable into the UPS and the computer then follow the
prompts on the screen. NOTE: When using the UPS's USB port with
Windows XP, 7,8 or 10 the Power Options in the Control Panel may need
to be configured.
LOAD SHEDDING FUNCTION
Theoutputreceptaclesare electrically wiredintotwo segments tosupportthe "Load
Shedding Function" (Labeled 1 & 2). The user can control the two segments indi-
vidually or both at the same time. The Load Shedding Function is controllable by
thePower Monitoring Software or the SNMP card. NOTE: The locking receptacle
(AlwaysOn) does notsupport the "Load Shedding Function".
TURNING THE UNIT ON/OFF
Turning the unit On
When the UPS is connected to anAC source and there is an accept-
ableAC voltage present; Press and then release the ON button after
theaudible alarmbeeps twiceto turnthe UPSOn andpower theload.
DC START:Press and then release the ON button after the audible
alarm beeps twice. Then within 10-seconds press and then release
theON button after the audible alarm beeps twice to DC start the UPS
andpower the load.
Turning the unit Off
When the UPS is in theAC normal mode; Press and then release the
OFF button after the audible alarm beeps twice to turn the UPS Off.
The UPS will continue to charge the batteries whenever it is plugged
into a wall outlet and there is acceptableAC voltage present.
EMERGENCY POWER OFF (EPO) FUNCTION
Connect one end of a two (2) wire cable to the EPO port on the rear panel of
the UPS and the other end of the two (2) wire cable to an EPO switch. To
shutdown the UPS in the AC or the Battery mode short pin1 to pin2 for ap-
proximately 0.5-seconds. In the AC mode; the UPS must be turned off and
then back on again to restart the UPS. In the Battery mode; once the utility
power returns the UPS must be turned on to restart the UPS. The LCD will
display EPo for this function.
ECONOMY MODE (ECO) FUNCTION
The UPS must be turned on and in the normal AC mode. The Economy mode
optionmust beEnabled throughthe SNMPcard orthe PowerMonitoring software.
Once the Economy mode has been Enabled the LCD will display ECO and the
Bypass(Yellow) LED will be illuminate. Turn on theconnected equipmentone at a
time.
OPTION SLOT
The option slot on the rear panel of the UPS is for option cards. Contact your
local dealer or visit our Web site at www.minutemanups.com for the available
option cards for this series.
POWER MONITORING SOFTWARE
The UPS comes with a Power Monitoring Software CD or you can go to our
website atwww.minutemanups.com/support,then lookunderDownloads, and
thenSoftware Download Center. Please download (Free ofCharge)thelatest
version of the Minuteman SentryHD software. See the software CD for the
installationofthePowerMonitoringSoftware.
USER INVOKED BATTERYTEST
Theuser invoked batterytest feature is useful to verify the correct operation of the
UPS and the condition of the batteries. With the UPS in the AC normal mode;
Press the Function button and then the Page Up button. The UPS will perform a
ten-secondbatterytestto measurethebattery’scapability tosupporttheconnected
load. During the battery test, the UPS will switch to the battery mode, the Battery
modepower flowwill illuminate and the audible alarm willsound. If the UPS fails a
battery test, one of the icons and/or error codes will remain illuminated indicating
thetype ofproblem.
ALARM SILENCER
Whenthe UPS is operating in the Battery modepress the ONbutton to silence the
audible alarm. Once the UPS reaches the Low Battery Warning (LBW) threshold
theaudible alarmwill startbeepingagain. When the UPS returns to the normalAC
modethe audiblealarm will reset to default. Theaudible alarm cannot be silenced
duringthe LBWor anyFault/error event.
CHANGING THE OUTPUT VOLTAGE
The output voltage can to configured for 110V, 120V, or 127V. The default
setting for the output voltage is 120V. To change the output voltage follow the
stepsbelow:
1. Connect the UPS to utility power. DO NOT turn on the UPS.
2. Press theONbutton andthePage Down buttonsimultaneouslyuntil theau-
dible alarm beeps once and then release.
3. Use thePage Upbuttonto selectthedesired outputvoltage settingandthen
presstheEnter button.
4. Disconnect the UPS fromutilitypowerandallowtheUPStocompletelysh-
utdownto save the changes.
4. Reconnect theUPSto utility powerandthenpress the ONbuttonto turn the
UPSonandverifytheoutputvoltage. Changingtheoutputvoltageiscom-
plete. The UPS is ready for normal operation.

19
18
WEAK/BAD/DISCONNECTED BATTERY
TheUPS automatically tests the battery’s condition. If thebatteryisweak,bad
or disconnected, the Weak/Bad/Disconnected Battery icon will illuminate, er-
ror code Er15 will be displayed and the audible alarm will beep three times
every five-minutes until the battery is reconnected, replaced or passes a self
test. It is recommended that the UPS be allowed to charge overnight before
performing a battery test to confirm a Weak/Bad Battery condition. NOTE:
The audible alarm cannot be silenced during this condition.
OVERLOAD
When the amount of load attached to the UPS is > 106% of its power rating;
the Overload icon will illuminate, the error code Er02 will be displayed and the
audiblealarm will beepcontinuously. Thisalarm will remainonuntil the excess
loadisremovedortheUPS’sselfprotectioncircuitshutstheUPSdown. Ifthe
UPSshutsdownbecauseof an Overload condition, the UPS must perform an
Inverter function or a Self Test to clear the Overload Alarm. NOTE: The
audible alarm cannot be silenced during this condition.
ALARMS
ON BATTERY
When the UPS is operating on the batteries, the On-Battery icon will illumi-
nate, the Utility power LED (Green) will extinguish and the audible alarm will
sound one beep every ten-seconds. The audible alarm can be silenced dur-
ing this condition. The alarm will stop once the UPS returns to theAC normal
mode.
LOW BATTERYWARNING
WhentheUPS is operating on the batteries and the battery reserveisrunning
low,the audible alarm will sound two beepsevery five-seconds and error code
Er17willbedisplayed. ThisconditionwillcontinueuntilACreturns or the UPS
shuts down from battery exhaustion. NOTE: The audible alarm cannot be
silenced during this condition.
UPS FAULT
When the UPS detects a hardware and/or internal fault, the Fault icon will
illuminateandtheaudible alarm will beep continuously. Thefault condition, in
some instances, may be reset by turning the UPS off and then on again.
NOTE: The audible alarm cannot be silenced during this condition.
(These items may require optional software or hardware)
Function Factory
Default Description
User Choices
Set
inverter
output
voltage
Shut-
down
Type
Set
audible
alarm
state
Enable/
Disable
auto
restart
Battery
replace
date
Battery
install
date
Date of
manufac-
ture
5yearsfrom
the install
date
Enabled
Enabled
EntireUPS
120VAC
Date of battery
replacement-
month/day/year
XX/XX/XXXX
Dateofthenext
battery re-
placement-
month/day/year
XX/XX/XXXX
Enable
or
Disable
Enabled,at
lowbattery,
disabled
Entire UPS or
UPSoutput
110, 120,
127VAC
Enter the date of the next battery
replacement.
Enterthe currentdatewhen
replacingbatteries.
Changesthe outputvoltage.
Enabled-theUPSwillemitashort
beep when in the battery mode.
AtLowBattery theUPSwill emit
twobeeps fromlowbattery warn-
inguntil shutdown.
Disabled - Use only when soft-
ware is controlling the UPS or to
silencethealarm.
When enabled, the UPS will
automatically restart from a low
batteryshutdownwhennormalAC
returns.
Enable/
Disable
ECO
Disabled Enable
or
Disable
Enabled- the UPS willoperatein
theEconomy mode.
EntireUPS-Turnsoffthe entire UPS.
UPS Output - Turns off the UPS's
outputreceptaclesonly.
Chapter 5: Configurable Parameters
and Settings
Enable/
Disable
Load
Shed-
ding
Disabled Enable,
Disable or
Configure
Enabled - the specified outlet
bank will turn off.
Configure - the specified outlet
bank will turn on or off based on
theselected event.
SITE WIRING FAULT
If the Site Wiring Fault icon is illuminated and error code Er16 is displayed,
the UPS is plugged into an improperly wired AC wall outlet. If the UPS indi-
cates a Site Wiring Fault have a Qualified Electrician correct the problem.

21
20
Chapter 6: Obtaining Service
IF THE UPS REQUIRES SERVICE
1. Use theTroubleshootingsection to eliminate obvious causes.
2. Verify there are no tripped circuit breakers and that the batteries are good.
A tripped circuit breaker and defective batteries are the most common iss-
ues.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannotresolve the issue callorfaxtheTechnicalSupport departmentat the
following numbers; Voice phone (972) 446-7363, FAX line (972) 446-9011
or visit our Web site at www.minutemanups.com the "Discussion Board".
Before calling the Technical Support Department have the following infor-
mationavailable:
a) Contact name and address.
b) Where and when the unit was purchased.
c) All of the model information about your unit.
d) The serial number of your unit.
e) Any information on the failure, including LEDs that may be illuminated
or error codes displayed.
f) A description of the protected equipment including model numbers, if
possible.
g) A technician will ask you for the above information and if possible,
helpsolve the issue over the phone. In the event thattheunitrequires
factoryservice,theTechnical Support Representativewill issueyoua
Return MaterialAuthorization Number (RMA#). NOTE: We must
have the model number and the serial number of the product to
issue an RMA #.
h) If the unit is under warranty, the repairs will be done at no charge. If
the unit is not under warranty there will be a charge for the repair.
4. Pack the unit in its original packaging. If the original packaging is no lon-
geravailable,asktheTechnicalSupport Representative about obtaininga
new set. It is important to pack the unit properly in order to avoid damage
in transit. Never use Styrofoam beads for a packing material.
a) Include a letter with your name, address, day time phone number,
RMAnumber, a copy of your original sales receipt, and a brief desc-
ription of the problem.
5. MarktheRMA# on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside of the package.
6. Return the unit by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMANUPS
1809 W. Frankford Road, Suite 150
Carrollton,TX 75007
ATTN:RMA#_______
Er01: UPS is shutdown.
Symptom / Error Code Cause / What To Do
The UPS has not been turned on. Press the On button and re-
leaseafter the audible alarm beepstwice.
Only the AC normal LED is
illuminated. Reset the input circuit breaker by pressing the plunger back in. If
the input circuit breaker trips after UPS restarts, reduce the load
on the UPS.
UPSonly operatesin battery
mode, even though there is
ACpresent.
The AC normal icon is illumi-
nated, but there is no output. Disconnect the computer cable from the UPS, press the On but-
ton. If UPS works normally, the software has control of the UPS.
Charge the batteries for 8-hours and retest. If the runtime is still
less than expected, the batteries may need to be replaced.
UPSdoes notprovide the
expectedruntime.
TheUPS hasan internalproblem. Call for service.
The Fault icon is illuminated
and a constant alarm.
Er02: TheOverload iconisil-
luminated and a constant
alarm.
Check the specifications and remove part of the load. If the UPS
shuts down because of an Overload, the UPS must perform an
Inverter function or a Self Test to clear the Overload Alarm.
The UPS has detected a short-circuit on its output. Check the at-
tachedload.
Er03: UPSOverTemperature. The internal temperature has exceeded the safe operating range
for the UPS. Check the specifications.
Er08: DCBUSvoltageabnor-
mal(High). Turn the UPS off, unplug the power cord, wait for 5-minutes and
then restart the UPS. If the error did not clear call for service.
Er11: Inverter/OutputFailure
Shutdown. TheUPS has an internal fault.Call forservice.
Er13: Fan Failure. The fan haseitherfailedor hasstopped dueto exessivedirt. Ifthe
fanhasfailed,callforservice.Ifthe fan isdirty,useacanof"Canned
Air" to clean the fan.
Er14: ChargerFailure. Thecharger hasfailed, callfor service.
Er16: Site Wiring Fault. Havea qualifiedelectrician correctthe servicewiring.
Er15: Weak/BadBattery icon
is illuminated. Checkthe battery connections,charge the batteries for 8-hours
and retest. The batteries may need to be replaced.
Er17: Low Battery Warning. TheUPS's battery reserveis low. This conditionwill continueuntil
AC returns or the UPS shuts down from battery exhaustion.
Er26: InputOver Current.
Er09: DCBUSvoltageabnor-
mal(Low). Turn the UPS off, unplug the power cord, wait for 5-minutes and
then restart the UPS. If the error did not clear call for service.
Er10: InverterOverCurrent. Check the specifications and remove part of the load.
Check the specifications and remove part of the load. If the error
did not clear call for service.
Chapter 7: Troubleshooting
Er28: BypassmodeOverload.
Er29: Charger overcharges
the battery. TheUPS has an internal fault.Call forservice.
Check the specifications and remove part of the load. If the error
did not clear call for service.
Er38: Failed to synchronize
with utility input. Turn the UPS off, unplug the power cord, wait for 5-minutes and
then restart the UPS. If the error did not clear call for service.
Er39: Low Battery Capacity. The UPS's battery capacity is low. Charge the batteries for 24-
hours. If the error does not clear call for service.
Er12: DCBUSPre-chargeab-
normal. Turn the UPS off, unplug the power cord, wait for 5-minutes and
then restart the UPS. If the error did not clear call for service.
Er18: EEPROM data error. TurntheUPS off,unplugthe powercord,wait for 1-minuteand then
restart the UPS. If the error does not clear call for service.

23
22
BATTERYREPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONSAND WARNINGS BEFORE ATTEMPTING
TOREPLACETHEBATTERYMODULE
Hot-swappablebatteriesmeanthatthebatterymodulescanbereplacedwith-
outpowering down the whole UPS system.
NOTE: If there is a power interruption while replacing the hot-swappable bat-
terymodule, with the UPS on,the load will not bebacked up. To hot-swap the
batterymodulestartwith step number 6.
1. Turn off the equipment that is plugged into the output receptacles of the
UPS.
2. Press and release the OFF button on the front panel to turn the UPS Off.
3. Unplug the UPS'sAC power cord from theAC wall outlet.
4. Unplug the equipment from the output receptacles of theUPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Grasp the battery door on the left hand side, pull it outward and then set it
aside (FIG. 1).
7. Press down to unlock the battery connector holder. Disconnect the Battery
connectors (red and black). (FIG. 2)
8. Remove the two retaining screws for the battery retaining bracket. (FIG. 2)
9. Remove the battery retaining bracket.
EC1000RT2U EC2000RT2U
Internal
Battery
Module
Part# BM0069
EC3000RT2U
BM0071
Model# EC1500RT2U
BM0070
Chapter 8: Replacing the Battery
WARNING! This UPS contains potentially hazardous voltages. Do not at-
tempt to disassemble the UPS beyond the battery replacement procedure.
This UPS contains no user serviceable parts. Repairs and battery replace-
ment must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
CAUTION: Donotopenormutilatebatteries. Released electrolyte is harmful
to the skin and eyes and may be toxic.
QUALIFIED SERVICE PERSONNELONLY
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batteries properly.
The batteries contain lead and pose a hazard to the environment and human
health if not disposed of properly. Refer to local codes for proper disposal
requirements or return the battery to the supplier.
CAUTION: The battery system can present a risk of electrical shock. These
batteries produce sufficient current to burn wire or tools very rapidly, produc-
ingmoltenmetal. Observetheseprecautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use handtoolswithinsulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the
batteryterminals.
6. Determineif the battery is inadvertently grounded. If the battery is, remove
the source of the grounding. Contact with any part of a grounded battery
can result in an electrical shock. The likelihood of such shock will be redu-
ced, if such grounds are removed during installation and maintenance.
Please read all of the WARNINGS and CAUTIONS before attempting to ser-
vice the batteries. Typical battery life is 3 to 5 years. Environmental factors
do affect battery life. High temperatures, poor utility power, and frequent,
short duration discharges have a negative impact on battery life.
CAUTION: Replace batteries with the same number and type as originally
installed in the UPS. These batteries have pressure operated vents. These
UPSscontainsealednon-spillablemaintenance-freelead acid batteries.
FIG. 1
FIG. 2
BM0070

25
24
10.Graspthebatterypulltab and gently pull the battery module out of the UPS
and set it aside. (FIG. 3)
NOTE: Use Caution, the battery module is heavy.
11.Slide the new battery module into the UPS.
12.Re-installthebatteryretaining bracket.
13.Re-install the two retaining screws for the battery retaining bracket.
14.Verify proper polarity. Reconnect the battery connectors (red and black).
(FIG. 4)
NOTE: Some sparking may occur this is normal.
15.Place the battery connectors in the holder and then lock in place. (FIG. 4)
16.Re-install the battery door on the UPS.
17.The UPS is now ready for the normal operation.
18.Properly dispose of the old battery module at an appropriate recycling fac-
ility or return them to the supplier in the packing material that the new batt-
ery module came in.
NOTE: If the UPS has a Weak/Bad BatteryAlarm after replacing the battery
module, the user must initiate a battery test to clear the Weak/Bad Battery
Alarm. To initiateaself test see section4"USER INVOKED BATTERYTEST".
FIG. 3
FIG. 4
120VAC(110,127VAC)
1500VA
1350W
1000VA
900W
Protection
WaveformType
Over-Current, Short-Circuit Protected and Latching Shutdown
TrueSineWave
Frequency 50/60Hz, +/-0.2Hz (unless synchronized to utility)
NominalVoltage(Adjustable)
MaximumPower Capacity
0 ms Typical
>90%(Full Load)
ResettableCircuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0- 160VAC
55V(load dependent) -150VAC
Nominal+/-2%
TransferTime
Efficiency(Line Mode)
InputProtection
FrequencyLimits
VoltageRegulation
AcceptableInput voltage
EC1000RT2U EC1500RT2U
ModelNumber
SYSTEMSPECIFICATIONS
Voltage Range
Topology DoubleConversion On-Line, TrueSineWave
OUTPUT NON-BATTERY OPERATION
INPUT
Numberof Phase Single (1∅2W +G)
NominalVoltage 120VAC
LowVoltageTransferPoint 55V (load dependent) resets to Utility Power at 75V or higher
HighVoltageTransferPoint 150V resets to Utility Power at 145V or lower
FrequencyRange 60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BATTERYOPERATION
VoltageRegulation Nominal +/-2%(until LowBattery Warning)
VoltageT.H.D. <3% (FullLinear Load)
+/-5% @ 100% Load change in 30 ms
DynamicResponse
SlewRate <1Hz / second
OverloadCapacity >106 to <110% for 2-mins; AC mode:Transfer to Bypass, DC Mode: Shutdown
>111 to <125% for 1-min; AC mode: Transfer to Bypass, DC Mode: Shutdown
>126 to <150% for 30-secs; AC mode:Transfer to Bypass, DC Mode: Shutdown
>151% Immediately;AC mode: Transfer to Bypass, DC Mode: Shutdown
EC2000RT2U EC3000RT2U
2000VA
1800W 3000VA
2700W
Chapter 9: Specifications
Switches from Bypass to Inverter +/-10% Of the rated input voltage
Switches from Inverter to Bypass
ECONOMY MODE OPERATION
Transfer Time 8 ms Typical
Resets 5VAC from Switch Point
PowerFactor Correction >99% at Full Load
CrestFactor 3 : 1

27
26
BATTERYSYSTEM
Typical RechargeTime
Typical BatteryLife
BatteryModule 3-5 years, depending on discharge cycles and ambient temp
BM0069
8-hoursto 90%after fullload discharge
BatteryType Sealed,Non-Spillable,MaintenanceFree,ValueRegulatedLeadAcid
Runtime:Full Load(minutes)
Runtime:Half Load(minutes) 10
10 3
2
SURGE PROTECTIONAND FILTERING
Audible Noise at 1 m (3 ft.)
10/100/1000 Base-T surge protec-
tion let-through (as a percentage
of an applied +/-2 kV 1.2/50 us,
500 a 8/20 uS test)
Telephone line surge protection
let-through (as a percentage of an
applied +/-2 kV 1.2/50 us, 500a 8/
20 uS test)
NoiseFilter
Surgevoltagelet-through(asa
percentage of an applied +/-2
kV)
SurgeResponseTime
SurgeCurrent Capability
SurgeEnergy Rating 254Joules
0 ns (instantaneous) normal mode; <5 ns common mode
<5%
normaland commonmode EMI/RFIsuppression
<55 dBA
<1%
<5%
6500Amps total
ENVIRONMENTAL
OperatingTemperature(max)
Operating/Storage Humidity
OperatingElevation
0to 40°C(+32to +104°F)
10%to 90% Non-Condensing
0 to 3,000m (0 to +10,000 ft)
PHYSICAL
Weight - Net
Size - Net L X W X H
(rackmountbrackets installed)
Size - Shipping
L X W X H
Weight- Shipping
16.0 x 18.9 x 3.5"
407x479x88mm
22.4 x 21.4 x 9.0"
570x544x228mm
REGULATORYCOMPLIANCE
SafetyandApprovals cTUVus (Conforms toUL17785thEdition&CSA22.2no.107.3-14/
R: 2014), FCC Class A, CE certified, Energy Star certified, RoHS2
(EUDirective2011/65/EU)
StorageElevation 0 to 15,000m (0 to +50,000 ft)
StorageTemperature -10to+50°C (+14to +122°F)
BM0070 BM0071
10
3
15
5
23.7 x 18.9 x 3.5"
602x479x88mm
30.9 x 23.2 x 9.0"
785x590x228mm
59.5 lbs
27.0 Kgs
65.7 lbs
29.8 Kgs
44.1 lbs
20.0 Kgs
49.6 lbs
22.5 Kgs
24.3 lbs
11.0 Kgs
29.5 lbs
13.4 Kgs
44.1 lbs
20.0 Kgs
49.6 lbs
22.5 Kgs
19.2 x 18.9 x 3.5"
487 x 479 x 88mm
25.6 x 21.4 x 9.0"
650 x 544 x 228mm
ParaSystems,Inc.(ParaSystems)warrantsthisequipment,whenproperlyapplied and
operated within specified conditions, against faulty materials or workmanship for a pe-
riod of three years from the date of purchase. For equipment sites within the United
Statesand Canada, this warranty covers depot repairorreplacement of defective equip-
mentatthediscretionofParaSystems. Depotrepairwillbe from the nearest authorized
service center. The customer pays for shipping the product to Para Systems. Para
Systems pays ground freight to ship the product back to the customer. Replacement
partsandwarrantylaborwillbebornebyParaSystems. Forequipmentlocated outside
oftheUnitedStatesand Canada, ParaSystemsonlycoversfaultyparts. ParaSystems
products that are depot repaired or replaced pursuant to this warranty shall only be
warrantedfortheunexpiredportionof the warranty applying to the original product. This
warranty applies only to the original purchaser who must have properly registered the
productwithin 10 days ofpurchase.
Thewarranty shall be voidif (a) the equipment is damaged bythe customer, is improp-
erlyused, is subjected to anadverse operating environment, or is operated outside the
limitsofitselectricalspecifications; (b) the equipment is repaired ormodifiedbyanyone
otherthanParaSystems or Para Systems approved personnel; or(c)has been used in
amanner contrary to the product’s User's Manual or other written instructions.
Anytechnical advice furnished before orafter delivery in regardto use or application of
ParaSystems’equipmentisfurnishedwithoutchargeandonthebasis that it represents
Para Systems’ best judgment under the circumstances, but it is used at the recipient’s
solerisk.
EXCEPTAS PROVIDED HEREIN,PARASYSTEMSMAKESNO WARRANTIES, EX-
PRESSEDORIMPLIED,INCLUDINGWARRANTIESOFMERCHANTABILITYANDFIT-
NESSFORAPARTICULARPURPOSE. Somestatesdo notpermitlimitationof implied
warranties;therefore,the aforesaid limitation(s)maynot apply to the purchaser.
EXCEPTAS PROVIDED ABOVE, IN NO EVENT WILL PARASYSTEMS BE LIABLE
FORDIRECT,INDIRECT,SPECIAL,INCIDENTAL,ORCONSEQUENTIALDAMAGES
ARISINGOUTOFTHE USE OFTHISPRODUCT,EVENIFADVISEDOFTHE POSSI-
BILITYOF SUCH DAMAGE. Specifically,Para Systems is not liable for any costs,such
as; labor for on-site installation, on-site maintenance or on-site service, lost profits or
revenue,lossofequipment,lossofuseofequipment,lossofsoftware,lossofdata,cost
ofsubstitutes, claims by third parties, or otherwise. The sole and exclusive remedy for
breachof any warranty, expressed or implied,concerning Para Systems’productsand
theonly obligation of Para Systems hereunder, shallbe depot repairor replacement of
defective equipment, components, or parts; or, at Para Systems’ option, refund of the
purchase price or substitution with an equivalent replacement product. This warranty
givesyouspecific legal rights and youmay also have other rightswhich vary from state
tostate.
No employee, salesman, or agent of Para Systems is authorized to add to or vary the
terms of this warranty.
Chapter 10: Limited Product Warranty
140Joules

29
28
A1. DECLARATION OF CONFORMITY
Application of Council Directive(s): 2014/30/EU
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS)
Manufacturer’sAddress: 1455LeMayDrive
Carrollton,Texas75007 USA
Type of Equipment: Uninterruptible Power Supplies (UPS)
ModelNo: EC1000RT2U(Y), EC1500RT2U (Y), EC2000RT2U (Y),
EC3000RT2U (Y)
I hereby declare that the equipment specified above conforms to the above
Directive(s).
Place:Carrollton,Texas,USA Date: July 10, 2017
RobertCalhoun
(Name) ManagerEngineering
(Position)
Year of Manufacture: Beginning July 2017
Standard(s) to which Conformity is declared: EN62040-2, IEC61000-2-2
IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-
6, IEC61000-4-8, UL1778, CSA22.2 no. 107.3-14, FCC Class A
Notes:
This manual suits for next models
3
Table of contents
Other Para systems UPS manuals

Para systems
Para systems PRO500LCD User manual

Para systems
Para systems Minuteman ED10000T User manual

Para systems
Para systems E750RTXL2U User manual

Para systems
Para systems ED1000RM2U User manual

Para systems
Para systems E750RT2U User manual

Para systems
Para systems Minuteman PRO-RT 2U Series User manual

Para systems
Para systems EN400 User manual

Para systems
Para systems Minuteman Enspire Series User manual

Para systems
Para systems MM450 User manual

Para systems
Para systems ETR500 User manual