Para systems PRO500LCD User manual

User's Manual
PRO-LCD
Series UPS
Para Systems, Inc.
1455 Lemay Dr.
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011
Internet: minutemanups.com
UPS Sizing: sizemyups.com
PN - 34000407 R2

1
© Copyright 2011
All rights reserved. All MINUTEMAN trademarks are property of Para Systems, Inc.
Other trademarks are property of their respective owners.
1. Introduction 2
2. Controls and Indicators 6
3. Installation 8
4. Operation 11
5. Troubleshooting 14
6. Replacing the Battery 15
7. Obtaining Service 19
8. Specifications 20
9. Limited Product Warranty 22
A1. Declaration of Conformity 23
English

3
2
WARNING: Riskof ElectricalShock. Hazardouslive parts inside
these power supplies are energized from the battery even when the
AC input is disconnected.
CAUTION! Tode-energizethe outputsof theUPS:
1. If the UPS is on press and release the On/Off/Test Button.
2. Disconnect the UPS from theAC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
theUPS fromtheACwall outletbeforeinstallinga computerinterface
cable. Reconnectthe powercord onlyafter allsignalingconnections
aremade.
CAUTION! Connect the UPS to a two pole, three wire grounding
ACwall outlet. Thereceptacle mustbe connectedto theappropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electricalcodes. Do notuse extensioncords,adapter plugs,or surge
strips.
English
CAUTION! Toreducethe riskof electricalshock withtheinstalla-
tion of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
WARNING: ThisUninterruptible PowerSupplycontainspotentially
hazardousvoltages. Do notattempt todisassemble theUPS beyond
the battery replacement procedure. This UPS contains no user ser-
viceableparts. Repairs andBatteryreplacementmustbeperformed
byQUALIFIED SERVICEPERSONNELONLY.
CAUTION! To reduce the risk of fire, connect only to a circuit
providedwith20amperesmaximumbranchcircuit over-currentpro-
tection in accordance with the National Electric Code, ANSI/NFPA
70.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
English
Thankyou forpurchasingthispowerprotectionproduct. Ithasbeendesigned
andmanufactured toprovide manyyears oftroublefreeservice.
Please read this manual before installing your PRO-LCD Tower Series UPS,
models PRO500LCD, PRO700LCD, PRO1100LCD, PRO1500LCD as it pro-
videsimportant informationthatshouldbefollowedduringinstallationandmain-
tenanceofthe UPSand batteriesallowing youto correctlyset upyoursystem
forthe maximumsafety andperformance. Includedis informationon customer
supportand factoryserviceif itisrequired. Ifyouexperience aproblemwith the
UPS please refer to the Troubleshooting guide in this manual to correct the
problem or collect enough information so that the Technical Support Depart-
ment can rapidly assist you.
Thissymbol indicates"ATTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply"
This symbol indicates "Alternating Current Supply Phase"

5
4
English
English
Life Support Policy
Asa generalpolicy,wedonotrecommendtheuseofanyof ourproducts inlife
supportapplications wherefailure ormalfunction oftheproductcanbe reason-
ablyexpected tocause failureof thelife supportdevice orto significantlyaffect
its safety or effectiveness. We do not recommend the use of any of our prod-
ucts in direct patient care. We will not knowingly sell our products for use in
such applications unless it receives in writing assurances satisfactory to us
that (a) the risks of injury or damage have been minimized, (b) the customer
assumes all such risks, and (c) our liability is adequately protected under the
circumstances.
Examplesof devicesconsideredtobelife supportdevicesareneonataloxygen
analyzers,nerve stimulators(whether usedfor anesthesia,pain relief,or other
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectorsandalarms,pacemakers,hemodialysissystems,peritoneal dialysis
systems,neonatal ventilatorincubators, ventilatorsfor bothadults andinfants,
anesthesiaventilators, andinfusion pumpsas wellas anyother devicesdesig-
nated as “critical” by the United States FDA.
Hospitalgradewiring devicesand leakagecurrentmay beordered asoptions
onmany ofour UPSsystems. We donot claimthat unitswith thismodification
arecertified orlisted asHospitalGradebyus orany otherorganization. There-
fore, these units do not meet the requirements for use in direct patient care.
Afterremoving yourUPSfromitscarton, itshouldbe inspectedfor damagethat
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrierwillnotbehonored. The packingmaterials thatyour UPSwas shipped
in are carefully designed to minimize any shipping damage. In the unlikely
case that the UPS needs to be returned to the manufacturer, please use the
original packing material. Since the manufacturer is not responsible for ship-
pingdamage incurredwhenthesystemisreturned,theoriginalpackingmate-
rialis inexpensiveinsurance. PLEASE SAVE THE PACKING MATERIALS!
Receiving Inspection
NOTE: TheseUPSs areshippedwiththebatteriesdisconnected. Thebatter-
ies must be connected before putting these UPSs into service. Refer to Sec-
tion 3 "Installation" for connecting the batteries.
NOTICE: Thisequipment hasbeen testedand foundto complywith thelimits
for a Class B computing device in accordance with the specifications in Sub-
partJof Part15 ofFCC Rulesand theClass Blimitsfor radionoise emissions
fromdigital apparatussetoutinthe RadioInterferenceoftheCanadian Depart-
ment of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equip-
mentgenerates andusesradio frequencyandifnotinstalledand usedproperly,
that is, in strict accordance with the manufacturer's instructions, this equip-
ment may cause interference to radio and television reception. If this equip-
ment does cause interference to radio or television reception, which can be
determinedby turningtheequipment offandon,theuser isencouragedto tryto
correcttheinterferencebyoneormore ofthe followingmeasures:
Re-orientthe receivingantenna.
Relocatethecomputerwithrespect tothe receiver.
Movethe computeraway fromthereceiver.
Plugthecomputerintoa differentoutlet sothat thecomputer andreceiver
areon differentbranch circuits.
Shieldedcommunications interfacecables mustbe usedwith thisproduct.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's
authorityto operatetheequipment.
CAUTION! ThisUPS seriesis onlyintended tobeinstallinan indoor
temperature controlled environment that is free of conductive con-
taminants.
CAUTION! The Maximum ambient operating temperature for this
UPSseriesis 40°C(“0 ~40°C” forAmbientOperation).
ON / OFF / TEST BUTTON: To turn the UPS on: press and hold the
On/Off/TestButtonuntil thealarm soundsonebeep andthen release.
The UPS will perform a five second self-test. Once the UPS has
passedits self-testthe UPSwill provideanoutput andthe loadwill be
powered. ToturntheUPS off: pressand holdthe On/Off/Test Button
untilthealarmsoundsone beepand thenrelease. To performaten-
second battery test: With the UPS in the AC mode, press and hold
the On/Off/Test Button until the alarm sounds four beeps, and then
release. Duringthe test,the UPSwill switchto theBattery mode,the
On-Battery icon will illuminate and the alarm will sound.
NOTICE! The output of this device is not sinusoidal. It has a total
harmonicdistortionandmaximumsingle harmonicas below:
PRO500LCD Total harmonic57.3% Single harmonic43.0%
PRO700LCD Total harmonic47.7% Single harmonic39.5%
PRO1100LCD Total harmonic 52.0% Singleharmonic 43.0%
PRO1500LCD Total harmonic 57.1% Singleharmonic 43.0%

7
6
English
Output Power Receptacles
NEMA 5-15P W/10 ft cord
Model # Input Power Plug
PRO500LCD
PRO700LCD
PRO1100LCD
PRO1500LCD
6-NEMA 5-15R Battery Backup & Surge
2-NEMA 5-15R Surge Only
REAR PANEL
1. Input power cord: Connecting to the Utility Power.
2. Surge-only output receptacles: Non-critical equipment.
3. TheRJ11/45: Phone/fax/network protection.
4. USB Communications Port: UPS monitoring and control.
5. Battery Backup & Surge output receptacles: Mission critical equipment.
6. Input circuit breaker: Protection against an excessive overload.
English
1. Scroll Button: To scroll through the UPS parameters.
2. Battery Capacity Bar Graph: Displays the amount of Battery Capacity
available in theAC and Battery mode.
3. Load Capacity Bar Graph: Displays the amount of load connected to the
UPS in theAC and Battery mode.
4. AC normal and Boost/Buck mode Icon: Illuminates when the UPS is in the
AC normal mode and flashs when the UPS is in the Boost or the Buck
mode.
5. On-BatteryIcon: Illuminateswhen theUPSis operatingin theBatterymode.
6. OverloadIcon:Illuminates whenthe amount ofload attachedto the UPS
exceeds its power rating,
7. UPS Parameters and Error codes:
Input - Voltage and Frequency.
Output - Voltage and Frequency.
Estimated Runtime (minutes) -AC normal and Battery mode.
S.L.F -Asite wiring fault has been detected.
FAL -An internal fault has been detected.
8. On/Off/Test Button: To turn the UPS On/Off and to perform a ten-second
battery test.
CONTROL PANEL

9
8
English
English
CONNECTINGTHEBATTERIES
(QUALIFIEDSERVICEPERSONNELONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to con-
nect the batteries.
1. RemovetheUPSfromthe shippingbox andset onthe flooror abenchtop.
2. Remove the front panel retaining screws on the bottom side of the front
panel. (FIG. 1)
3. Slidethefront paneldownward, thenoutward, andthen moveit totheside.
4. Verify proper polarity. Connect the battery positive (red) wire to the battery
positive (red) terminal. (FIG. 2)
NOTE: Some sparking might occur, this is normal.
5. Re-install the front panel onto the UPS.
6. Re-install the front panel retaining screws.
7. Continue with the rest of the Installation.
INSTALLATION
Besure toread theinstallation placementand allthe cautionsbeforeinstalling
the UPS. Place the UPS in the final desired location and complete the rest of
theinstallationprocedure. TheseUPSs areshipped withthe internalbatteries
disconnected.The batteriesmust beconnectedbefore puttingthese UPSsinto
service. See Connecting the Batteries to connect the batteries.
INSTALLATIONPLACEMENT
This UPS series is only intended to be install in an indoor temperature con-
trolledenvironmentthat isfree ofconductive contaminants. DONOT operate
the UPS in: extremely dusty and/or unclean areas, locations near heating de-
vices, water or excessive humidity, or where the UPS is exposed to direct
sunlight. Selecta location,which willprovidegood aircirculation fortheUPSat
all times.
Routepowercords sothey cannot bewalked onor damaged. Typi-
calbattery lifeis 3to 5years. Environmental factorsdo affectbatterylife. High
temperatures,poor utilitypower,andfrequent, shortdurationdischarges havea
negativeimpact onbatterylife.
FIG.1
FIG.2
CONNECTINGYOUREQUIPMENT
Plug the mission critical equipment into the Battery Backup & Surge output
receptaclesontherearpanel ofthe UPS. Plugthe non-criticalequipment into
the Surge Only output receptacles on the rear panel of the UPS. Ensure that
the connected equipment does not exceed the maximum output rating of the
UPS(refer tothe informationlabel onthe UPSortheelectrical specificationsin
thismanual). DONOTPLUGEXTENSIONCORDS,ADAPTERPLUGS,SURGE
STRIPS OR POWER STRIPS INTOTHE OUTPUT RECEPTACLES OFTHE
UPS. NOTE: Risk of damaging the UPS and/or connected equipment.
CONNECTINGTHE UPSTO AN ACSOURCE
CAUTION - Toreducethe riskof fire,connect onlyto acircuit providedwith 20
amperes maximum branch circuit over-current protection in accordance with
theNational ElectricCode,ANSI/NFPA70. PlugtheUPSinto atwo pole,three
wire,grounded receptacleonly. DONOT PLUGTHE UPSINTOEXTENSION
CORDS,ADAPTERPLUGS, SURGESTRIPSORPOWER STRIPS.DO NOT
CUTTHE INPUTPLUGOFFANDATTEMPTTOHARDWIRETHIS UPS,DO-
INGSO WILLVOID THEWARRANTY.
CAUTION! DO NOT connect alaser printerto theoutput ofthe UPS.

11
10
English
PHONE/FAX/NETWORKPROTECTION CONNECTION(OPTIONAL)
Connecta 10/100Base-Tnetwork,singleline phone,or faxline tothe RJ11/45
modularconnectors onthe rearpanel oftheUPS. Thisconnectionwillrequire
anotherlength oftelephone ornetwork cable. Thecable comingfrom thetele-
phoneserviceornetworkedsystem isconnected tothe portmarked “IN”. The
equipment to be protected is connected to the port marked "OUT". NOTE:
Connecting to the Phone/Fax/Network modular connectors is optional. The
UPS works properly without this connection.
SYSTEM OVERVIEW
This Line-Interactive UPS protects computers, servers, telecom systems, VoIP
systems, security systems, and a variety of electronic equipment from black-
outs, brownouts, overvoltages, and surges. The AVR function continuously
correctsthe voltages,in-between thebrownoutandovervoltage transferpoints
(90 - 150VAC), to a safe usable level. When the UPS is operating in theAVR
modethe audiblealarm willremainsilent andtheACnormalmodeindicator will
blink. DuringnormalACoperation,theUPSwillquietly andconfidently protect
yoursystemfrompoweranomalies.
The UPS will charge the batteries with the UPS in the on or off position when
the UPS is plugged into the wall outlet and there is an acceptableAC voltage
present(90 -150VAC). When ablackout, brownout,oran overvoltagecondition
occurs; the UPS will transfer to the battery mode, the On Battery indicator will
illuminateandthe audiblealarm willsound onceevery fiveseconds indicating
that the commercial power is lost or unacceptable. When the commercial
power returns or is at an acceptable level, the UPS will automatically transfer
back to the AC normal mode and start recharging the batteries. During an
extended outage when there is approximately two minutes of backup time re-
maining the audible alarm will sound twice every five seconds. This Low Bat-
teryWarningis informingthe userthat theyshould saveallopen filesand turn
offtheir computer. Whenthe batteriesreach thepredetermined levelthe UPS
willautomaticallyshutdownprotectingthebatteries fromover discharging. Once
thecommercial powerreturns theUPSwill automaticallyrestart, providingsafe
usablepowertotheconnected equipmentand startrecharging thebatteries.
English
CHARGINGTHEBATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
anAC sourceand thereis anacceptableAC voltagepresent(90- 150VAC). It
isrecommended thatthe UPS'sbatteries becharged fora minimumof 4hours
before use. The UPS may be used immediately, however, the “On Battery”
runtime may be less than normally expected. Typical battery life is 3 to 5
years. Environmental factors do affect battery life. High temperatures, poor
utilitypower, andfrequent,short durationdischargeshaveanegative impacton
battery life. NOTE: If the UPS is going to be out of service or stored for a
prolonged period of time, the batteries must be recharged for at least twenty-
fourhours everyninety days.
USBCOMMUNICATIONSPORT CONNECTION (OPTIONAL)
This UPS series supports USB communications. The power monitoring soft-
ware and interface cable can be used with the UPS. Use only the interface
cable that come with these UPSs. The USB communications protocol is HID.
The HID USB driver comes standard in the Windows OS. Simply connect the
USB cable to the USB communications port on the rear panel of the UPS.
Connect the other end of the USB cable to the device that will be monitoring/
controlling the UPS and then follow the prompts on the screen. NOTE: Con-
nectingto theCommunications Portis optional. TheUPS worksproperly with-
out this connection.
CHECKINGTHE SITEWIRING FAULT
After plugging the UPS into the wall outlet, check the LCD screen on the front
panel of the UPS for a Site Wiring Fault (S.L.F). If the S.L.F is illuminated, the
UPSis pluggedinto animproperly wiredwall outlet. Ifthe UPSindicatesaSite
WiringFault(S.L.F), havea QualifiedElectrician correctthe problem.
CAUTION! TheTNVconnector shalluse thesame typeof RJ45.
POWERMONITORINGSOFTWARE
TheUPScomeswithpower monitoringsoftware. See thesoftware CDfor the
installationof thepower monitoringsoftware.
TURNING THE UPS ON / OFF
To turn the UPS on: press and hold the On/Off/Test Button until the alarm
soundsone beepandthen release. TheUPSwill performafive secondinternal
self-test. Once the UPS has passed its internal self-test the UPS will provide
anoutput andthe loadwillbe powered. Toturn theUPS off: pressand holdthe
On/Off/TestButton untilthe alarmsoundsone beepand thenrelease.
TESTBUTTON
To perform a ten-second user invoked battery test: With the UPS in the AC
normalmode, pressandhold theOn/Off/TestButton untilthealarmsounds four
beeps, and then release. During the test, the UPS will switch to the Battery
mode, the On-Battery icon will illuminate and the alarm will sound.

13
12
English
WEAK/BADBATTERY
TheUPS automaticallytests thebattery’s condition. Ifthe batteryis weak,bad
or disconnected, the Battery Capacity Bar Graph will flash and the alarm will
soundthreebeepseveryfive minutesuntil thebattery iseither reconnectedor
replaced. This alarm will be repeated until the batteries pass a self-test. It is
recommendedthat theUPSbe allowedtocharge overnightbeforeperforming a
battery test to confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
Overload icon will illuminate and the alarm will sound continuously (AC and
Battery modes). This alarm will remain on until the excess load is removed or
the UPS’s self protection circuit shuts the UPS down.
Toclearthe overloadalarm whenthe UPShasshutdown requiresthatthe UPS
performabatterytest. Firstremove partof theload, thenturn theUPS on,the
Overload icon and the alarm will be on. Second either use theTest Button or
unplug the input power cord to perfom the battery test.
ALARMS
ONBATTERY
Whenthe UPSis operatingon thebatteries,theACnormalicon willextinguish,
theOn-Battery iconwill illuminateand thealarm willsoundonebeepeveryfive
seconds. Once the UPS returns to the normal AC mode, the alarm will stop,
the On-Battery icon will extinguish and theAC normal icon will illuminate.
LOWBATTERYWARNING
When the batteries reach the predetermined level, the alarm will sound two
beepsevery fiveseconds andthe BatteryBar Graphwill displaythe remaining
battery capacity. This condition will continue until either AC returns or the
UPS’s self protection circuit shuts the UPS down to protect the battery from
overdischarging.
UPSFAULT
When the UPS detects an internal fault, "FAL" will be displayed on the LCD
screen, thealarm willsoundcontinuouslyandthe outputwill beturnedoff. The
fault condition, in some instances, may be reset by turning the UPS off and
then on. If the fault condition does not clear the UPS must be sent in for
service.
English
SELF-TEST
Theself-test featureis usefulto verifythe correctoperation ofthe UPSand the
conditionof thebatteries. The lengthofthetestthat isautomatically performed
everytwo weeksislongerthanthe start-uporuserinvokedtest. This everytwo
week test will run for approximately fifteen-seconds to measure the battery’s
capabilityto supportthe outputload. Thestart-up anduser invokedtestwillrun
for approximately ten-seconds. If the UPS fails one of these tests, one of the
iconsor theinformation displayedon theLCDwillremainilluminated indicating
thetypeofproblem. NOTE: TheUPSwillautomatically performa self-teston
start-upand everytwo weeks.
SCROLLBUTTON
Press the Scroll Button to scroll through the UPS parameters. The UPS pa-
rametersaredisplayedonthe LCDscreen.
LCDSCREEN
TheLCD providesthe userwith avariety ofuseful information. TheLCD hasa
real-timemeterto display,in numericfashion, thefollowingdata:
InputVoltageand Frequency
OutputVoltageand Frequency
ConnectedLoad Capacity
Battery Capacity
Estimated runtime in theAC and DC mode
TheLCD willinclude dedicatedicons forthe followinginformation:
ACNormal
On Battery
AVR Mode (Boost and Buck) –TheAC Normal icon will flash
Overload
Weak/Bad Battery (Battery Capacity Bar Graph will flash)
Site Wiring Fault (S.L.F. will be displayed)
UPS Fault (FALwill be displayed)
The LCD does have a backlight that will turn on when the UPS is turned on.
After approximately 20-seconds the backlight will turn off to conserve energy.
When an event (alarm) occurs, such as going to the battery mode, the back-
light will turn on for approximately 20-seconds to alert the user that an event
has occurred and then the backlight will turn off. While the Scroll button is in
use the backlight will remain on. Approximately 20-seconds after the Scroll
buttonhasstopped beingused thebacklight will turnoff toconserve energy.
BATTERYOVERCHARGE PROTECTION
If the charger is providing too much voltage to the battery the UPS will turn off
thechargertoprotectthe battery. When thecharger voltageexceeds 14.52V/
battery the charger will turn off. The alarm will sound three beeps every five
secondsand theBattery CapacityBar Graphwill flash. Insome instances,the
charger may be reset by turning the UPS off and then on. When the charger
voltage exceeds 15.0V/battery the charger will turn off. The alarm will sound
threebeepsevery fiveseconds andtheBattery CapacityBar Graphwill flash.
The UPS will automatically transfer to the battery mode and operate until the
UPS shuts down due to battery exhaustion. The UPS must be sent in for
service.

15
14
English
REPLACING THE BATTERY
WARNING! This UPS contains potentially hazardous voltages. Do not at-
tempt to disassemble the UPS beyond the battery replacement
procedure. This UPS contains no user serviceable parts. Re-
pairsand batteryreplacementmustbe performedby QUALIFIED
SERVICEPERSONNELONLY.
Donot openor mutilatebatteries. Releasedelectrolyte isharmful
to the skin and eyes and may be toxic.
CAUTION:
(QUALIFIEDSERVICE PERSONNELONLY)
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batter-
iesproperly. Thebatteriescontainlead andpose ahazard tothe
environmentand humanhealth ifnot disposedofproperly. Refer
to local codes for proper disposal requirements or return the
battery to the supplier.
Thebatterysystem canpresent arisk ofelectrical shock. These
batteriesproduce sufficientcurrent toburnwireortoolsveryrap-
idly, producing molten metal. Observe these precautions when
replacingthe batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wearprotective eyegear (goggles),rubber glovesandboots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco-
nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the bat-
tery is,remove thesource ofthegrounding. Contact withany
part of a grounded battery can result in an electrical shock.
The likelihood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
CAUTION:
Pleaseread allofthe WARNINGSandCAUTIONS beforeattempting toservice
the batteries. Typical battery life is 3 to 5 years. Environmental factors do
affect battery life. High temperatures, poor utility power, and frequent, short
durationdischarges havea negativeimpact onbattery life.
English
PossibleCause
Symptom What To Do
Press, hold and then release
the On/Off button to start UPS
On/Off/Test button not
pressed
UPSwill notturn on
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS
UPS operates in
battery mode only,
even though there
is normal AC
present
InputACcircuit breakeris
tripped
UPShas detectedaninter-
nalfault Callfor service
"FAL" is displayed
ontheLCD
TheACmode icon
is illuminated, but
there is no output
Disconnect the computer
cablefromthe UPSand press
the On button. If UPS works
normally, the software has
control of the UPS
The UPS is being con-
trolledviaits communica-
tions port
The batteries may be
weakor atthe endof their
usefulservice life
Charge the batteries for 8-
hoursandretest. If theruntime
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated
UPS does not
provideexpected
runtime
TheBattery Capac-
ity Bar Graph is
flashing
TheOverloadicon
isilluminated
Loose connections at the
batteries, Weak batteries,
Badbatteries
The output load has ex-
ceededtheUPS'scapac-
ity
Checkbatteryconnections,
chargethe batteriesfor8-
hours,replace thebatteries
Checkthespecifications(see
section 8). Remove part of
theload
The AC mode icon
is flashing and the
alarm is silent
The UPS is operating in
the Boost or the Buck
mode
TheUPShasdetectedan
improperly wired wall out-
let
The UPS is performing its in-
tendedfunction
ContactaQualifiedElectrician
tocorrectthe problem
"S.L.F" is dis-
playedonthe LCD

17
16
English
FIG. 2
FIG. 3
7. Slidethefrontpaneldownward,thenoutward, andthen moveto theside or
lay it on the top of the unit. (FIG. 2)
8. Disconnect the Battery positive (red) wire.
9. Disconnect the Battery negative (black) wire.
Caution: Do not short the Battery positive wire to the Battery negative wire.
10. Remove the two screws for the battery retaining bracket.
11. Slidethe batteryretainingbracket upwardsand thenremove fromthe unit.
English
BATTERYREPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TOREPLACETHE BATTERIES
Hot-swappablebatteries meanthat thebatteries canbe replacedwithout pow-
ering down the whole UPS system.
NOTE: Ifthere isapower interruptionwhilereplacing thehot-swappablebatter-
ies,withtheUPSon, theload willnot bebacked up. Tohot-swapthe batteries
start with step number 6.
1. Turn off the equipment that is plugged into the output of the UPS.
2. Turn off the UPS.
3. Unplug the UPS'sAC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Remove the front panel retaining screws on the bottom side of the front
panel. (FIG. 1)
Replace batteries with the same number and type as originally
installedinthe UPS. Thesebatteries havepressure operatedvents.
These UPSs contain sealed non-spillable maintenance-free lead
acidbatteries.
CAUTION:
FIG. 1
12. Graspthe batterypull tabandgentlypull thebattery moduleout oftheUPS
and set aside. (FIG. 3)
Caution: DO NOT pull the battery module out by pulling on the battery wires.
BatteryModule
Part #
PRO1500LCD
BM0051
Model# PRO500LCD
BM0048
PRO700LCD
BM0049
PRO1100LCD
BM0050

19
18
English
IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING sectionto eliminateobvious causes.
2. Verify there are no circuit breakers tripped. Atripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax the Technical Support department at
thefollowingnumbers; Voicephone (972)446-7363,FAXline (972)446-9011
Pleasehave thefollowing informationavailable BEFOREcalling theTechni-
cal Support Department.
A. Your name and address.
B. Where and when the unit was purchased.
C.All of the model information about your UPS.
D.Any information on the failure, including LEDs that may be illuminated.
E.Adescription of the protected equipment, including model numbers if
possible.
F.Atechnician will ask you for the above information and, if possible, help
solveyour problemoverthephone. Intheeventthat theunit requires
factory service, the technician will issue you a Return MaterialAuthoriza-
tion Number(RMA#).
G. If the UPS is under warranty, the repairs will be done at no charge. If not,
therewill bea chargeforrepair.
4.Pack theUPS inits originalpackaging. If theoriginal packagingis nolonger
available, ask the Technical Support Technician about obtaining a new set.
It is important to pack the UPS properly in order to avoid damage in transit.
NeveruseStyrofoambeads fora packing material.
A. Include a letter with your name, address, day time phone number, RMA
number,a copyof youroriginal salesreceipt,anda briefdescription ofthe
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMANUPS
1455LeMayDrive
Carrollton,TX75007
ATTN:RMA#_______
English
13. Slide the new battery module into the UPS.
14. Re-install the battery retaining bracket.
15. Re-install the two screws for the battery retaining bracket.
16. Verify proper polarity. Reconnect the battery negative (black) wire to the
battery negative (black) terminal.
17. Verify proper polarity. Reconnect the battery positive (red) wire to the
battery positive (red) terminal.
NOTE: Some sparking might occur, this is normal.
18. Re-install the front panel on the UPS.
19. Re-installthefront panelretaining screws.
20. Properly dispose of the old batteries at an appropriate recycling facility or
return them to the supplier in the packing material for the new batteries.
21. The UPS is now ready for the normal operation.
NOTE: If the UPS has a Weak/Bad BatteryAlarm after replacing the battery
module,auser invokedbattery testmust beperformed toclear theWeak/Bad
Battery Alarm. To initiate a user invoked battery test see section 4 "TEST
BUTTON".

21
20
English
BATTERYSYSTEM
Typical Recharge Time
Typical Battery Life 3 to 5 years. Environmental factors do affect battery life.
High temperatures, poor utility power, and frequent, short
duration discharges have a negative impact on battery life.
From Full load dishcarge: 4-hours to 80%, 8-hours to 90%
Battery Type Sealed,Non-Spillable,MaintenanceFree,ValueRegulatedLeadAcid
Runtime: Half Load (minutes)
Runtime: Full Load (minutes)
SURGEPROTECTIONAND FILTERING
Audible Noise at 1 m (3 ft.)
10/100Base-Tsurgeprotection let-through
(asapercentageofanapplied+/-6kV1.2/50
us,500 a8/20 uStest)
Telephoneline surgeprotectionlet-through
(asapercentage ofanapplied+/-6 kV1.2/50
us,500a 8/20uS test)
NoiseFilter
Surgevoltage let-through(asa percentage
ofan appliedANSI C62.41Cat.A+/-6kV)
Surge Response Time
Surge Current Capability
Surge Energy Rating 760 J
0 ns (instantaneous) normal mode; <5 ns common mode
< 11%
>45db normal and common mode EMI/RFI suppression
<45 dBA
< 1%
<5%
10000 Amps total(one time 8 to 20us waveform)
PHYSICAL
Weight - Net
Size - Net
L X W X H
Size - Shipping
L X W X H
Weight - Shipping
11.81 x 6.69 x 7.87"
300 x 170 x 200 mm
15.16 x 9.84 x 11.22"
385 x 250 x 285 mm
34.2 lbs
15.5 Kgs
36.4 lbs
16.5 Kgs
ENVIRONMENTAL
Operating/Storage Humidity 95% Non-Condensing
Storage Elevation 0 to 15,000m (0 to +50,000 ft)
Storage Temperature -15 to +45°C (+5 to +113°F)
Operating Temperature 0 to 40 degrees C (+32 to +104 degrees F) at
OperatingElevation 0 to 1,500m (0 to +5,000 ft)
Operating Temperature 0 to 35 degrees C (+32 to +95 degrees F) at
OperatingElevation 1501 to 3,000m (0 to +10,000 ft)
17.6 lbs
8.0 Kgs
19.8 lbs
9.0 Kgs
5
17
7
21
English
120VAC
1100VA
770W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Simulated Sine Wave (Step Wave)
Frequency 50/60Hz, +/-0.5Hz (unless synchronized to utility)
NominalVoltage
Maximum Power Capacity
6 ms Typical
>90% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-5Hz, autosensing
0 - 160VAC
90 - 150VAC
104 - 132VAC
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
PRO1100LCD
ModelNumber
SYSTEMSPECIFICATIONS
Voltage Range
Topology Line-Interactive, Simulated Sine Wave
OUTPUTNON-BATTERYOPERATION
INPUT
Number of Phase Single (1∅2W +G)
NominalVoltage 120VAC
Low Voltage Transfer Point 90V resets to Utility Power at 94V or higher
High Voltage Transfer Point 150V resets to Utility Power at 146V or lower
Voltage Regulation 120VAC: -13.3% - +10.0%
Frequency Range 60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
OUTPUTBATTERYOPERATION
Voltage Regulation Nominal +/-5% (until Low Battery Warning)
Overload Capacity ACMode: 110%for5-seconds thenfault,120%ShutdownImmediately
PRO1500LCD
1500VA
1050W
REGULATORYCOMPLIANCE
Safety and Approvals
EMCVerification
cTUVus(conforms toUL1778, CSA22.2standards)
FCC Class B, CE certified
23.8 lbs
10.8 Kgs 39.2 lbs
17.8 Kgs
41.4 lbs
18.8 Kgs
26.0 lbs
11.8 Kgs
7
21
5
17
14.56 x 6.69 x 7.87"
370 x 170 x 200 mm
18.11 x 10.24 x 11.22"
460 x 260 x 285 mm
PRO500LCD PRO700LCD
500VA
350W 700VA
490W
DCMode: 110%for10-secondsthenshutdown,120% ShutdownImmediately
Battery Module Part # BM0051BM0048 BM0049 BM0050

23
22
English
A1. DECLARATION OF CONFORMITY
Applicationof CouncilDirective(s): 2004/108/EC, 2006/95/EC,cTUVus (for
UL1778)
Standard(s)to whichConformity isdeclared: EN55022, EN55024,EN61000-
3-2,EN61000-3-3,EN61000-4-2,EN61000-4-3, EN61000-4-4,EN61000-4-5,
EN61000-4-6,EN61000-4-8, EN61000-4-11, UL1778,FCCClassB
Manufacturer’sName: ParaSystems, Inc. (MINUTEMANUPS)
Manufacturer’sAddress: 1455LeMayDrive
Carrollton,Texas 75007 USA
TypeofEquipment: UninterruptiblePower Supplies(UPS)
ModelNo: PRO500LCD, PRO700LCD,PRO1100LCD,PRO1500LCD
I hereby declare that the equipment specified above conforms to the above
Directive(s).
Place: Carrollton,Texas, USA Date: March 1, 2011
RobertCalhoun
(Name) ManagerEngineering
(Position)
Year ofManufacture: BeginningMarch 1,2011
English
ParaSystems, Inc. (Para Systems)warrantsthis equipment, when properlyappliedand oper-
atedwithin specified conditions, against faulty materials or workmanship for a period of three
yearsfrom thedate of purchase. Forequipment siteswithinthe UnitedStatesand Canada,this
warrantycovers repair or replacement of defective equipment at thediscretion of Para Sys-
tems. Repair will be from the nearest authorized service center. The customer pays for
shippingtheunitto ParaSystems. Para Systemspaysgroundfreightto shipthe unitbacktothe
customer. Replacementpartsand warranty labor will be borne by Para Systems. For equip-
mentlocated outsideof the UnitedStates andCanada,Para Systems only coversfaultyparts.
ParaSystemsproductsrepairedorreplacedpursuanttothiswarrantyshallbewarrantedfor
theunexpiredportion of the warranty applying to the original product. Thiswarranty applies
onlyto the original purchaser whomusthave properly registered the productwithin10days of
purchase.
Thewarranty shallbe void if(a) theequipmentis damagedbythe customer,isimproperlyused,
is subjected to an adverse operating environment, or is operated outside the limits of its
electricalspecifications;(b) the equipment is repaired or modified by anyone other than Para
SystemsorParaSystems approved personnel; or (c) has been used in a manner contrary to
theproduct’sUser'sManualorotherwritteninstructions.
Anytechnicaladvicefurnishedbefore or after delivery in regard to use or application of Para
Systems’s equipment is furnished without charge and on the basis that it represents Para
Systems’sbest judgment under the circumstances, but it is used at the recipient’s sole risk.
EXCEPTASPROVIDEDHEREIN,PARASYSTEMSMAKESNOWARRANTIES,EXPRESSEDOR
IMPLIED,INCLUDINGWARRANTIESOFMERCHANTABILITYANDFITNESSFORAPARTICULAR
PURPOSE. Somestates donotpermit limitationofimplied warranties;therefore,the aforesaid
limitation(s)may notapplytothe purchaser.
EXCEPTASPROVIDEDABOVE,INNOEVENTWILLPARASYSTEMSBELIABLEFORDIRECT,
INDIRECT,SPECIAL,INCIDENTAL,ORCONSEQUENTIALDAMAGESARISINGOUTOFTHEUSE
OFTHISPRODUCT,EVENIFADVISEDOFTHEPOSSIBILITYOFSUCHDAMAGE. Specifically,
ParaSystems isnotliable for anycosts,such as lostprofitsor revenue, lossof equipment, loss
ofuseofequipment,loss of software, loss of data, cost of substitutes, claims by third parties,
or otherwise. The sole and exclusive remedy for breach of any warranty, expressed or
implied,concerning Para Systems’sproductsand the onlyobligation of ParaSystemshereun-
der,shallbe therepair orreplacementof defectiveequipment, components,or parts;or,atPara
Systems’soption, refund of the purchase priceorsubstitutionwith an equivalent replacement
product. This warranty gives you specific legal rights and you may also have other rights
which vary from state to state.
Noemployee, salesman, or agent ofParaSystems is authorized to addtoor vary the terms of
this warranty.

25
24
Notes: Notes:
English
English
This manual suits for next models
3
Table of contents
Other Para systems UPS manuals

Para systems
Para systems ED1000RM2U User manual

Para systems
Para systems Minuteman ED10000T User manual

Para systems
Para systems E750RT2U User manual

Para systems
Para systems ETR500 User manual

Para systems
Para systems EN400 User manual

Para systems
Para systems Minuteman Encompass EC1000RT2U User manual

Para systems
Para systems Minuteman Enspire Series User manual

Para systems
Para systems E750RTXL2U User manual

Para systems
Para systems Minuteman On-Line RT Series User manual

Para systems
Para systems MM450 User manual