Para systems ETR500 User manual

User's Manual
Entrust
Series UPS

1
© Copyright 2007
1. Introduction 2
2. Controls and Indicators 6
3. Installation 7
4. Operation 10
5. Troubleshooting 12
6. Replacing the Battery 13
7. Obtaining Service 16
8. Specifications 17
9. Limited Product Warranty 19
A1. Declaration of Conformity 20
English

2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
English
Thankyouforpurchasingthispowerprotectionproduct. Ithasbeendesigned
andmanufacturedtoprovidemanyyearsof trouble freeservice.
Please read this manual before installing your Entrust Series UPS, models
ETR500, ETR700, ETR1000, ETR1500, ETR700p15, ETR1500p15 as it pro-
videsimportantinformationthatshouldbefollowedduringinstallationandmain-
tenanceofthe UPS and batteries allowing you to correctlysetup your system
forthe maximumsafetyand performance. Includedisinformation oncustomer
supportandfactoryserviceifit isrequired. Ifyouexperienceaproblemwith the
UPS please refer to the Troubleshooting guide in this manual to correct the
problem or collect enough information so that the Technical Support Depart-
ment can rapidly assist you.
Thissymbol indicates "ATTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply"
This symbol indicates "Alternating Current Supply Phase"

3
WARNING: Risk of Electrical Shock. Hazardous live partsinside
these power supplies are energized from the battery even when the
AC input is disconnected.
CAUTION! To de-energize the outputsof the UPS:
1. If the UPS is on press and release the On/Off Button.
2. Disconnect the UPS from theAC wall outlet.
3. To de-energize the UPS completely, disconnect the battery.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
theUPS fromtheACwall outletbeforeinstallingacomputer interface
cable. Reconnectthe power cordonlyafterall signaling connections
aremade.
CAUTION! Connect the UPS to a two pole, three wire grounding
ACwall outlet. The receptacle must beconnectedtotheappropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electricalcodes. Do notuseextension cords,adapterplugs, orsurge
strips.
English
CAUTION! To reduce therisk of electrical shock with theinstalla-
tion of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
WARNING: ThisUninterruptiblePowerSupplycontainspotentially
hazardousvoltages. Do not attempt todisassembletheUPS beyond
the battery replacement procedure. This UPS contains no user ser-
viceableparts. RepairsandBatteryreplacementmustbeperformed
byQUALIFIED SERVICEPERSONNELONLY.
CAUTION! To reduce the risk of fire, connect only to a circuit
providedwith20amperesmaximumbranchcircuitover-currentpro-
tection in accordance with the National Electric Code, ANSI/NFPA
70.

4
English
AfterremovingyourUPS fromitscarton, itshouldbeinspectedfor damagethat
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrierwillnotbe honored. The packing materials that your UPS was shipped
in are carefully designed to minimize any shipping damage. In the unlikely
case that the UPS needs to be returned to the manufacturer, please use the
original packing material. Since the manufacturer is not responsible for ship-
pingdamageincurredwhenthesystemis returned, the original packing mate-
rialis inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!
Receiving Inspection
NOTICE: Thisequipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Sub-
partJof Part 15 of FCC Rules and theClassB limits for radio noise emissions
fromdigital apparatussetoutintheRadioInterferenceoftheCanadianDepart-
ment of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equip-
mentgeneratesandusesradiofrequencyandifnotinstalledand usedproperly,
that is, in strict accordance with the manufacturer's instructions, this equip-
ment may cause interference to radio and television reception. If this equip-
ment does cause interference to radio or television reception, which can be
determinedbyturningtheequipmentoff andon,theuseris encouragedto tryto
correcttheinterferencebyoneormoreofthefollowingmeasures:
Re-orientthereceivingantenna.
Relocatethecomputerwithrespect to the receiver.
Movethe computerawayfromthe receiver.
Plugthecomputerintoadifferent outlet so that the computer and receiver
areondifferent branch circuits.
Shieldedcommunications interface cables mustbeusedwith this product.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's
authoritytooperatetheequipment.
NOTE: TheseUPSsareshippedwiththebatteriesdisconnected. Thebatter-
ies must be connected before putting these UPSs into service. Refer to Sec-
tion 3 "Installation" for connecting the batteries.

5
English
Life Support Policy
Asa general policy, wedonotrecommendtheuseofany of our productsin life
supportapplications where failureormalfunction of theproductcanbe reason-
ablyexpected to cause failure of thelifesupportdeviceor to significantly affect
its safety or effectiveness. We do not recommend the use of any of our prod-
ucts in direct patient care. We will not knowingly sell our products for use in
such applications unless it receives in writing assurances satisfactory to us
that (a) the risks of injury or damage have been minimized, (b) the customer
assumes all such risks, and (c) our liability is adequately protected under the
circumstances.
Examplesofdevicesconsidered tobelife supportdevicesare neonataloxygen
analyzers,nerve stimulators (whether used for anesthesia, pain relief,orother
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectorsandalarms,pacemakers,hemodialysissystems,peritonealdialysis
systems,neonatal ventilator incubators, ventilators for both adultsandinfants,
anesthesiaventilators, and infusion pumpsaswellasany other devices desig-
nated as “critical” by the United States FDA.
Hospitalgrade wiring devices and leakage current may be ordered as options
onmanyof our UPS systems. We do not claim that units with this modification
arecertified orlistedasHospital Grade byusor any otherorganization. There-
fore, these units do not meet the requirements for use in direct patient care.

6
English
1. On/Off Button.
2. ACMode (Green) LED.
3. On Battery (Yellow) LED.
4. BadBattery/Overload/Fault (Red) LED.
5. Inputpower cord.
6. Surge Only output power receptacles.
7. The USB communications port is for UPS monitoring and control.
8. TheRJ11/45 are used forphone/fax/modemandnetworkprotection.
9. Battery Backup and Surge output power receptacles.
10.Inputcircuitbreaker.
Output Power Receptacles
ETR500
NEMA5-15PW/6 ft cord
Model #
ETR700 4-NEMA 5-15R Surge Only
4-NEMA 5-15R Battery Backup & Surge
Input Power Plug
ETR1000
ETR1500
ETR700p15
ETR1500p15 NEMA 5-15P W/15 ft cord

7
English
INSTALLATION PLACEMENT
This UPS series is intended to be install in a temperature controlled environment
that is free of conductive contaminants. Avoid locations near heating devices, water
or excessive humidity, or where the UPS is exposed to direct sunlight. Select a
location which will provide good air circulation for the UPS at all times. Route power
cords so they cannot be walked on or damaged.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing the
UPS. Place the UPS in the final desired location and complete the rest of the
installation procedure. These UPSs are shipped with the internal batteries discon-
nected. The batteries must be connected before putting these UPSs into service.
See the Connecting The Batteries procedure to connect the batteries.
Low Battery
Green LED
Short/FaultMode
Overload
ACMode
Over-Bat/Bat Fault
Off
Overload
Normal
Self low Battery
Buck
Boost
Normal
Self-Test
UPS Status
Status LED and Alarm Table
BatteryMode
Yellow LED Red LED Alarm
Off
Off
Off
Off
OffOff
Off
Off Off
Off
Off
Off
Off
Off
Off
Off
Off Off
Off
On
On
On Continuous
On
On
On
1-Beep/5-sec
1-Blink/1.5sec
2-Blinks/sec
2-Blinks/sec
2-Blinks/sec
2-Blinks/sec
2-Blinks/sec
2-Blinks/sec
1-Beep/5-sec
3-Beeps/30-sec
2-Beeps/sec
2-Beeps/5-sec
2-Beeps/sec
3-Beeps/5-sec
All LEDs cycle (each LED Blinks 1/1.5seconds)

8
English
CONNECTINGTHEBATTERIES
(QUALIFIEDSERVICEPERSONNELONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to connect the
batteries.
1. Remove the UPS from the shipping box and set on a table or a bench top.
2. Remove the retaining screws from the bottom of the front panel of the UPS.
(FIG. 1)
3. Gently push the top of the battery compartment cover inward and then slide the
battery compartment cover off the UPS. (FIG. 2)
4. For the ETR500/700: Grasp the battery pull tab and gently pull the battery out far
enough to connect the battery positive (Red) wire. (FIG. 3)
NOTE: The ETR1000/1500 have Red Anderson connectors to connect the battery.
5. Verify proper polarity. For the ETR500/700: Connect the battery positive (Red)
wire to the battery positive (Red) terminal. For the ETR1000/1500: Connect the
two Red Anderson connectors together. (FIG. 3)
NOTE: Some sparking might occur, this is normal.
6. Re-install the battery compartment cover onto the UPS.
WARNING: DO NOT pinch the battery wires with battery compartment cover.
7. Re-install the battery compartment cover retaining screws.
8. Continue with the rest of the Installation.
FIG. 3: ETR500
FIG. 1 FIG. 2

9
English
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source and there is an acceptable AC voltage present (90 - 150VAC). It
is recommended that the UPS's batteries be charged for a minimum of 4 hours
before use. The UPS may be used immediately, however, the “On Battery”
runtime maybe less than normally expected. NOTE: If the UPS is going to be
out of service or stored for a prolonged period of time, the batteries must be
recharged for at least twenty-four hours every ninety days.
USB COMMUNICATIONS PORT CONNECTION (OPTIONAL)
The Power Monitoring Software can be used with the UPS. Use the interface
cable that comes with the UPS. Connect one end of the USB cable to the USB
communications port on the rear panel of the UPS. Connect the other end of
the USB cable to the device that will be monitoring/controlling the UPS. NOTE:
Connecting to the communications port is optional. The UPS works properly
without this connection.
CONNECTING THE UPS TO AN AC SOURCE
CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20
amperes maximum branch circuit over-current protection in accordance with
the National Electric Code, ANSI/NFPA 70. Plug the UPS into a two pole, three
wire, grounded receptacle only. Do not use extension cords, adapter plugs, or
surge strips.
CONNECTING YOUR EQUIPMENT
Plug the mission critical equipment into the Battery Backup & Surge output
receptacles on the rear panel of the UPS. Plug the non-critical equipment into
the Surge Only output receptacles on the rear panel of the UPS. Do not use
extension cords, adapter plugs or surge strips on the output of the UPS. En-
sure that you do not exceed the maximum output rating of the UPS (refer to the
information label or the electrical specifications in this manual).
CAUTION! DO NOT connect a laser printer to the output recep-
tacles on the UPS.
FIG. 3: ETR700 FIG.3: ETR1000/1500

10
English
SYSTEMOVERVIEW
This Line-Interactive UPS protects computers, internetworking, and telecom-
municationsequipmentfrom blackouts, brownouts, overvoltages, and surges.
TheAVR functioncontinuouslycorrectsthe voltages,in-betweenthebrownout
andovervoltagetransferpoints(90-150VAC),to asafe usablelevel. Whenthe
UPS is operating in theAVR mode the audible alarm will remain silent and the
ACModeindicatorwillblink. DuringnormalACoperation, the UPS will quietly
andconfidentlyprotectyoursystem from power anomalies.
The UPS will charge the batteries with the UPS in the on or off position when
the UPS is plugged into the wall outlet and there is an acceptableAC voltage
present(90-150VAC). Whenablackout,brownout,oranovervoltagecondition
occurs; the UPS will transfer to the battery mode, the On Battery indicator will
illuminateandtheaudible alarm will sound once every five secondsindicating
that the commercial power is lost or unacceptable. When the commercial
power returns or is at an acceptable level, the UPS will automatically transfer
back to the AC normal mode and start recharging the batteries. During an
extended outage when there is approximately two minutes of backup time re-
maining the audible alarm will sound twice every five seconds. This Low Bat-
tery Warning is letting the user know that they should save all open files and
turn off their computer. When the batteries reach the predetermined level the
UPS will automatically shutdown protecting the batteries from over discharg-
ing. Once the commercial power returns the UPS will automatically restart,
providingsafeusablepower to the connected equipment and start recharging
thebatteries.
PHONE/FAX/MODEM/NETWORKPROTECTIONCONNECTION(OPTIONAL)
Connecta10/100Base-Tnetwork,singlelinephone, fax or modem line to the
RJ-11/45 modular connectors on the rear panel of the UPS. This connection
willrequire another lengthoftelephonecable (provided) ornetworkcable. The
cablecoming fromthetelephone serviceornetwork systemisconnected tothe
port marked “IN”. The equipment to be protected is connected to the port
marked"OUT". NOTE: Connecting tothephone/fax/modem/network modular
connectors is optional. The UPS works properly without this connection.

11
English
USBCOMMUNICATIONS PORT
The USB communications protocol is HID. The HID USB driver comes stan-
dard in the Windows OS. Simply plug the USB cable into the UPS and the
computerthen follow the prompts on thescreen.
WEAK/BADBATTERY
TheUPSautomaticallyteststhebattery’sconditionandwillilluminatethe Bad
Battery/Overload/FaultLEDandsoundthealarm. Thisalarmwillberepeated
until the batteries pass a self test. If the battery is weak, bad or disconnected,
theBadBattery/Overload/FaultLEDwillilluminateandthealarmwillbeepthree
times every thirty seconds until the battery is reconnected or replaced. It is
recommendedthattheUPSbe allowedtochargeovernightbeforeperforminga
battery test to confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the
BadBattery/Overload/FaultLEDwillilluminateandtheUPSwillsound1 beep
everyhalfsecond(AC and Battery modes). This alarm will remain on untilthe
excess load is removed or the UPS’s self protection circuit shuts the UPS
down.
POWERMONITORINGSOFTWARE
TheUPScomeswithpowermonitoringsoftware. Seethe software CD for the
installationof the power monitoring software.
ALARMS
ONBATTERY
WhentheUPSis operating on the batteries, the On Battery LED will illuminate
andthe audible alarm will sound onceevery five seconds. The alarm will stop
once the UPS returns to theAC normal mode.
LOWBATTERYWARNING
TheUPSwillsoundtwobeepseveryfivesecondswhenthebatteryreserveruns
low. This condition will continue untilAC returns or the UPS shuts down from
batteryexhaustion.
UPSFAULT
When the UPS detects a hardware fault, the Bad Battery/Overload/Fault LED
willilluminateandthe UPS will sound a constant alarm. The fault condition,in
some instances, may be reset by turning the UPS off and then on.
TURNING THE UNIT ON/OFF
On / Off Button
PressandreleasetheOn/OffButtontoturntheUPSon. Thealarmwillsound
onebeepandthe LEDswillcyclewhiletheUPSperforms afivesecondinternal
self-test. Once the UPS has passed its internal self-test the UPS will provide
an output and the load will be powered. Press and release the On/Off Button
toturnthe UPS off. The UPS will continue tochargethe batteries whenever it
is plugged into a wall outlet and there is an acceptableAC voltage present.

12
English
PossibleCause
Symptom What To Do
Pressandreleasethe On/Off
button to start UPS
On/Off/buttonnotpressed
UPSwill not turn on
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS
UPS operates in
battery mode only,
even though there
is normal AC
present
InputACcircuitbreakeris
tripped
UPS has detected an
internalfault Call for service
Fault LED is
illuminated
TheACModeLED
is illuminated, but
there is no output
Disconnect the computer
cablefromtheUPSandpress
the On button. If UPS works
normally, the software has
control of the UPS
The UPS is being
controlledvia its
communicationsport
The batteries may be
weakor at the end of use-
ful service life
Charge the batteries for 8-
hoursandretest. Iftheruntime
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated
UPS does not
provideexpected
runtime
BadBatteryLEDis
illuminated
Overload LED is
illuminated
Loose connections at the
batteries, Weak batteries,
Badbatteries
Theloadhasexceededthe
UPS's capacity
Checkbattery connections,
chargethebatteriesfor8-
hours,replacethebatteries
Checkthespecifications(see
section 8). Remove part of
theload
The AC Mode LED is
blinking once every
secondand theaudible
alarmissilent
The AC Mode LED is
blinking twice every
secondand theaudible
alarmissilent
The UPS is operating in
the Boost Mode
The UPS is operating in
the Buck Mode
The UPS is performing its
intendedfunction
The UPS is performing its
intendedfunction

13
English
REPLACING THE BATTERY
WARNING! This UPS contains potentially hazardous voltages. Do not at-
tempt to disassemble the UPS beyond the battery replacement
procedure. This UPS contains no user serviceable parts. Re-
pairsandbatteryreplacement mustbeperformed by QUALIFIED
SERVICEPERSONNELONLY.
Donot openormutilate batteries. Releasedelectrolyteis harmful
to the skin and eyes and may be toxic.
CAUTION:
(QUALIFIEDSERVICEPERSONNELONLY)
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batter-
iesproperly. The batteries containlead and pose a hazardtothe
environmentand human healthifnotdisposed of properly. Refer
to local codes for proper disposal requirements or return the
battery to the supplier.
Although the battery system voltage is only 12VDC and 24VDC
the battery system can still present a risk of electrical shock.
These batteries produce sufficient current to burn wire or tools
veryrapidly,producing moltenmetal. Observetheseprecautions
whenreplacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wearprotectiveeyegear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco-
nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the bat-
teryis, remove the sourceofthe grounding. Contact with any
part of a grounded battery can result in an electrical shock.
The likelihood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
CAUTION:
PleasereadalloftheWARNINGSandCAUTIONSbeforeattemptingtoservice
thebatteries.

14
English
BATTERYREPLACEMENTPROCEDURE
PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERIES
Hot-swappable batteries mean that the batteries can be replaced without powering
down the whole UPS system.
NOTE: If there is a power interruption while replacing the hot-swappable batteries,
with the UPS on, the load will not be backed up. To hot-swap the batteries start with
step number 6.
1. Turn off the equipment that is plugged into the output receptacles of the UPS.
2. Press and release the On/Off Button to turn the UPS off.
3. Unplug the UPS's power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the the UPS.
6. Remove the retaining screws from the bottom of the front panel of the UPS.
(FIG. 1)
7. Gently push the top of the battery compartment cover inward and then slide the
battery compartment cover off the UPS. (FIG. 2)
8. For the ETR500/700: Grasp the battery pull tab and gently pull the battery out far
enough to disconnect the battery positive (Red) wire. (FIG. 3)
NOTE: The ETR1000/1500 have Red Anderson connectors to connect the battery.
9. Disconnect the battery negative (Black) wire. (FIG. 3)
NOTE: DO NOT short the battery wires together.
10. Remove the battery and set aside.
NOTE: Orient the new battery in the same direction as the original battery.
11. Place the new battery close enough to connect the battery wires.
12. Connect the battery negative (Black) wire to the battery negative terminal.
13. For the ETR500/700: Connect the battery positive (Red) wire to the battery posi-
tive terminal. For the ETR1000/1500: Connect the Red Anderson connectors
together
NOTE: Some sparking might occur, this is normal.
14. Install the new battery into the UPS.
15. Re-install the battery compartment cover onto the UPS.
WARNING: DO NOT pinch the battery wires with battery compartment cover.
16. Re-install the battery compartment cover retaining screws.
17. Properly dispose of the old batteries at an appropriate recycling facility or return
them to the supplier in the packing material for the new batteries.
18. The UPS is now ready for normal operation.
BatteryQty/Rating
ETR1500
ETR1500p15
2-12V9Ah
Model#
Replace batteries with the same number and type as originally in-
stalled in the UPS. These batteries have pressure operated vents.
These UPSs contain sealed non-spillable maintenance-free lead acid
batteries.
CAUTION:
CSB Part #
First Power Part # HR1234W
FP1290
ETR500
1-12V5Ah
HR1221W
FP1245
ETR700
ETR700p15
1-12V7Ah
GP1272
FP1270
ETR1000
2-12V7Ah
GP1272
FP1270

15
English
FIG. 1 FIG. 2
FIG. 3: ETR500
FIG. 3: ETR700 FIG.3:ETR1000/1500

16
English
IF THE UPS REQUIRES SERVICE
1.UsetheTROUBLESHOOTING sectiontoeliminateobviouscauses.
2. Verify there are no circuit breakers tripped. Atripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax the Technical Support department at
thefollowingnumbers;Voicephone(972)446-7363,FAXline(972)446-9011
Pleasehavethefollowinginformation available BEFORE callingtheTechni-
cal Support Department.
A.Your name and address.
B. Where and when the unit was purchased.
C.All of the model information about your UPS.
D.Any information on the failure, including LEDs that may be illuminated.
E.Adescription of the protected equipment, including model numbers if
possible.
F.Atechnician will ask you for the above information and, if possible, help
solveyourproblemoverthephone. Intheeventthattheunitrequires
factory service, the technician will issue you a Return MaterialAuthoriza-
tionNumber(RMA#).
G. If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be acharge for repair.
4.Pack the UPS in its original packaging. If the original packagingisnolonger
available, ask theTechnical SupportTechnician about obtaining a new set.
It is important to pack the UPS properly in order to avoid damage in transit.
NeveruseStyrofoam beads for a packingmaterial.
A. Include a letter with your name, address, day time phone number, RMA
number,acopyof youroriginalsalesreceipt, and abriefdescription of the
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMANUPS
1455LeMayDrive
Carrollton,TX75007
ATTN: RMA#_______

17
English
120VAC
500VA
300W 1000VA
600W
700VA
420W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Simulated Sine Wave (Step Wave)
Frequency 50/60Hz, +/-0.5Hz (unless synchronized to utility)
NominalVoltage
Maximum Power Capacity
6 ms Typical
>90% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-5Hz, autosensing
0 - 160VAC
90 - 150VAC
105 - 130VAC
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
ETR1000
ETR700
ETR700p15
ETR500
ModelNumber
SYSTEMSPECIFICATIONS
Voltage Range
Topology Line-Interactive, Simulated Sine Wave
OUTPUTNON-BATTERYOPERATION
INPUT
Number of Phase Single (1∅2W +G)
NominalVoltage 120VAC
Low Voltage Transfer Point 90V resets to Utility Power at 94V or higher
High Voltage Transfer Point 150V resets to Utility Power at 146V or lower
Voltage Regulation 120VAC: -12.5% - +8.4%
Frequency Range 60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
OUTPUTBATTERYOPERATION
Voltage Regulation Nominal +/-6% (until Low Battery Warning)
Overload Capacity 110% for 10-seconds
120% Shutdown Immediately
ETR1500
ETR1500p15
1500VA
900W
REGULATORYCOMPLIANCE
Safety and Approvals
EMCVerification
UL1778, cUL (CSA 22.2 no. 107.1)
FCC Class B, CE certified

18
English
BATTERYSYSTEM
Typical Recharge Time
Typical Battery Life
Battery: Quantity/Rating
3-5 years, depending on discharge cycles and ambient temp
1-12V5Ah 2-12V7Ah
8-hours from total discharge
2-12V9Ah
Battery Type Sealed,Non-Spillable, Maintenance Free, ValueRegulatedLeadAcid
System Voltage 12VDC 24VDC 24VDC
Runtime: Full Load (minutes)
Runtime: Half Load (minutes) 9
2
SURGEPROTECTIONAND FILTERING
Audible Noise at 1 m (3 ft.)
10/100Base-Tsurge protectionlet-through
(asapercentageofanapplied+/-6kV1.2/50
us,500a 8/20uStest)
Telephonelinesurgeprotectionlet-through
(asapercentageofanapplied+/-6kV1.2/50
us,500a8/20uS test)
NoiseFilter
Surgevoltage let-through(as apercentage
ofanappliedANSIC62.41Cat.A +/-6kV)
Surge Response Time
Surge Current Capability
Surge Energy Rating 320 J
0 ns (instantaneous) normal mode; <5 ns common mode
< 5%
normaland commonmode EMI/RFIsuppression
<45 dBA
< 1%
<5%
6500 Amps total
PHYSICAL
Weight - Net
(ETR700p15,ETR1500p15)
Size - Net
L X W X H
Size - Shipping
L X W X H
(ETR700p15,ETR1500p15)
Weight - Shipping
(ETR700p15,ETR1500p15)
13.23 lbs
6.0 Kgs
10.91 x 3.43 x 10.80"
277.2 x 87 x 274.4 mm
16.14 x 7.09 x 15.94"
410 x 180 x 405 mm
(16.04 x 8.19 x 15.94"
410 x 208 x 405 mm)
20.0 lbs
9.0 Kgs
(21.0 lbs
9.32 Kgs)
12VDC
1-12V7Ah
16.4 x 3.43 x 10.80"
412.5 x 87 x 274.4 mm
21.26 x 7.09 x 15.94"
540 x 180 x 405 mm
(21.26 x 8.19 x 15.94"
540 x 208 x 405 mm)
29.33 lbs
13.3 Kgs
(30.12 lbs
13.66 Kgs)
34.0 lbs
15.4 Kgs
(35.0 lbs
15.66 Kgs)
ENVIRONMENTAL
Operating/StorageHumidity 95% Non-Condensing
Storage Elevation 0 to 15,000m (0 to +50,000 ft)
Storage Temperature -15 to +45°C (+5 to +113°F)
Operating Temperature 0 to 40 degrees C (+32 to +104 degrees F) at
OperatingElevation 0 to 1,500m (0 to +5,000 ft)
Operating Temperature 0 to 35 degrees C (+32 to +95 degrees F) at
OperatingElevation 1501 to 3,000m (0 to +10,000 ft)
28.89 lbs
13.1 Kgs
15.44 lbs
7.0 Kgs
(16.14 lbs
7.32 Kgs)
18.0 lbs
8.0 Kgs 34.0 lbs
15.2 Kgs
11
3
14
4
10
3

19
English
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied
and operated within specified conditions, against faulty materials (excluding the
batteries) or workmanship for a period of three years from the date of purchase.
Para Systems Inc. (Para Systems) warrants the batteries for a period of two years
from the date of purchase. For equipment sites within the United States and Canada,
this warranty covers repair or replacement of defective equipment at the discretion of
Para Systems. Repair will be from the nearest authorized service center. Replace-
ment parts and warranty labor will be borne by Para Systems. For equipment lo-
cated outside of the United States and Canada, Para Systems only covers faulty
parts. Para Systems products repaired or replaced pursuant to this warranty shall
be warranted for the unexpired portion of the warranty applying to the original prod-
uct. This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is
improperly used, is subjected to an adverse operating environment, or is operated
outside the limits of its electrical specifications; (b) the equipment is repaired or
modified by anyone other than Para Systems or Para Systems approved personnel;
or (c) has been used in a manner contrary to the product’s User's Manual or other
written instructions.
Any technical advice furnished before or after delivery in regard to use or application
of Para Systems’s equipment is furnished without charge and on the basis that it
represents Para Systems’s best judgment under the circumstances, but it is used
at the recipient’s sole risk.
EXCEPTAS PROVIDED HEREIN, PARASYSTEMS MAKES NO WARRANTIES, EX-
PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITYAND
FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of
implied warranties; therefore, the aforesaid limitation(s) may not apply to the pur-
chaser.
EXCEPTAS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE
FORDIRECT, INDIRECT,SPECIAL,INCIDENTAL,ORCONSEQUENTIALDAMAGES
ARISINGOUTOFTHE USEOFTHIS PRODUCT,EVENIFADVISEDOFTHEPOSSI-
BILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs,
such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of
software, loss of data, cost of substitutes, claims by third parties, or otherwise. The
sole and exclusive remedy for breach of any warranty, expressed or implied, con-
cerning Para Systems’s products and the only obligation of Para Systems hereun-
der, shall be the repair or replacement of defective equipment, components, or
parts; or, at Para Systems’s option, refund of the purchase price or substitution with
an equivalent replacement product. This warranty gives you specific legal rights and
you may also have other rights which vary from state to state.
This manual suits for next models
5
Table of contents
Other Para systems UPS manuals

Para systems
Para systems E750RTXL2U User manual

Para systems
Para systems EN400 User manual

Para systems
Para systems ED1000RM2U User manual

Para systems
Para systems MM450 User manual

Para systems
Para systems Minuteman Enspire Series User manual

Para systems
Para systems Minuteman On-Line RT Series User manual

Para systems
Para systems Minuteman ED10000T User manual

Para systems
Para systems PRO500LCD User manual

Para systems
Para systems E750RT2U User manual

Para systems
Para systems Minuteman Encompass EC1000RT2U User manual