
Bulletin TI-N2-04K Installation, Operation and Maintenance Manual
Technical Information Model N2-04 Nitrogen Generator
Parker Hannin Corporation
Industrial Gas Filtration and Generation Division
Lancaster, NY • 1-800-343-4048
4
w
Maintenance
If the N2-04 Nitrogen Generator is being used to deliver nitrogen at an elevated pressure
(>10 psig/0.7 barg), use the following procedure for start-up and adjustment of the system. (Note:
in elevated pressure applications, the customer should install a flow controller downstream from
the Nitrogen Generator, as detailed in the Installation section of this manual).
1Open the (customer installed) inlet air gate valve.
2Adjust the (customer installed) inlet air pressure regulator until the Operating Pressure
Gauge shows the operating pressure reading necessary to provide the purity and flow de-
manded by the application, as shown in the table on page 6.
3Set the Outlet Pressure Regulator (see Figure 1) to the desired outlet nitrogen pressure.
4Allow the system to reach equilibrium at the desired flow rate, pressure, and purity param-
eters. This should take approximately 5 minutes.
If the temperature of the inlet air to the Balston Nitrogen Generator differs from the tempera-
ture of the module (i.e. ambient temperature), the system must be allowed to reach temperature
equilibrium before a constant purity of nitrogen is delivered from the system. If the temperature
difference is 10°F-20°F (5°C-11°C), this equilibrium period may be as long as 60 minutes. The
inlet air temperature and, more importantly, inlet air dewpoint, should not be higher than the
temperature of the system, or condensation of water within the system may occur, resulting in
inefficient performance of the system and/or damage to the membrane.
Performance of the Nitrogen Generator is highly dependent on the temperature of the inlet air.
The data on purity and flow rate presented in this bulletin is based on an inlet air temperature of
68°F (20°C). If the temperature of the inlet air at the point of use for this system varies from 68°F
(20°C) by more than 5°F (3°C), consult the factory for flow and purity information.
The performance and operating conditions of the N2-04 Nitrogen Generator should be checked
at least once per week. This routine system check should include confirming pressure gauge
reading stability and operating pressure setting, and checking the downstream flowmeter (if ap-
plicable) to ensure flows are consistent with the required nitrogen purity level.
The optimum performance of the Balston Nitrogen Generator is dependent on system param-
eters remaining stable and accurate; as such, the use of an oxygen analyzer to monitor system
performance is highly recommended.
System upsets relative to pressure or flow rate will result in variations in purity of the outlet gas.
System upsets relative to temperature, dewpoint, or hydrocarbon content of the inlet compressed
air may result in variations of the system performance. These types of upsets should be elimi-
nated from the compressed air delivery system to assure consistent performance of the Balston
Nitrogen Generator.
Proper shutdown of the Balston Nitrogen Generator can be accomplished by simply closing the
inlet air gate valve. If this valve is left open, the system will continue to consume inlet com-
pressed air. Closing the outlet flow control valve will not prevent air consumption because the
membrane module permeate ports are open to atmosphere.
Shutting Down
Evaluation
System Upsets
Temperature
Equilibrium
To avoid system damage and/or personal harm , isolate the nitrogen generator from the com-
pressed air supply and fully depressurize the system.
All maintenance activities for the N2-04 Nitrogen Generator should be performed by suitable
personnel using reasonable care. Safety risks that may affect the service personnel are
identified with protective measures that apply. The service personnel will verify the system
is safe after the maintenance is completed.
Required maintenance for the nitrogen generator consists of changing the prefilter and final
filter cartridges, and calibrating the performance of the system. The prefilters and final filter are
located behind the filtration access panel. The recommended service schedule and replacement
part numbers are outlined at the end of this section.
Elevated Pressure
Applications
(>10 psig/0.7 barg)