Parker Sporlan SCS-PB User manual

Bulletin 100-50-11.1 – Page 1
April 2020 / Bulletin 100-50-11.1
SCS-PB / SCS-SB
Installation and Operating Instructions

Page 2 – Bulletin 100-50-11.1
Table of Contents
1. Introduction ............................................................................................................................................. 3
2. Installation ............................................................................................................................................3-4
3. Setup ...................................................................................................................................................4-5
4. Parameters.............................................................................................................................................. 6
5. LED Indicators......................................................................................................................................... 7
6. Alarms..................................................................................................................................................... 7
7. Normal Operation .................................................................................................................................... 8
8. Overrides................................................................................................................................................. 8
9. Firmware Update..................................................................................................................................... 8
10. Data Logs/Graphing ................................................................................................................................ 8
Appendix A: Ordering Information.................................................................................................................... 8
Appendix B: Technical Specifications (pending testing, must verify).................................................................. 9
Appendix C: Sensor Installation ..................................................................................................................... 10
⚠WARNING – USER RESPONSIBILITY
Failure or improper selection or improper use of the products described herein or related items can cause death, personal injury and property damage.
This document and other information from Parker Hannin Corporation, its subsidiaries and authorized distributors provide product or system options for further investigation by users
having technical expertise.
The user, through its own analysis and testing, is solely responsible for making the nal selection of the system and components and assuring that all performance, endurance,
maintenance, safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry standards, and follow the
information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specications provided by the user, the user is responsible
for determining that such data and specications are suitable and sufcient for all applications and reasonably foreseeable uses of the components or systems.

Bulletin 100-50-11.1 – Page 3
1. Introduction
The SCS family is an electronic superheat controller solution that is designed for refrigeration applications using
either a Pulse Width or Stepper type expansion valve. It is designed to be mounted within the refrigerated space
for ease of installation on existing equipment. SCS-PB is designed to operate pulse valves, while the SCS-SB
is designed to operate stepper valves. Each of the controller types include a coil outlet temperature sensor,
and connectors for the valve and pressure sensor compatible with Sporlan valves and pressure sensors and
a 110/120-220/240 VAC power connection.
2. Installation
Tools required:
• Mobile iOS device with Bluetooth LE capability and
either cellular or Wi-Fi connectivity
• Small flat screwdriver (for Pulse Valve connector)
• Wire cutters
• Two #10 (5mm) mounting screws
• Magnet or magnetized screwdriver
• Scotch-Brite™pad
1. The SCS should be mounted in a UV protected
location where the mounting location will be
between -22°F and 120°F (-30°C and 50°C). The
controller and connections should be hermetically
sealed so the controller can be installed in wet
environments. Take care not to mount the unit in
such a way that it would block any air curtains of
a refrigerated display case. Mount the unit in such
a way that the Bluetooth ID on the label is visible
for ease of connecting to the unit via Bluetooth.
The controller MUST be mounted on a flat surface.
Mounting the controller on a surface that is not
flat or bends may cause damage to the controller.
Recommended torque varies by material, 13 to 17
in-lbs (1.47 to 1.92 Nm) should be sufficient.
2. Mount the coil outlet sensor that is included with
the SCS on the outlet of the evaporator coil. See
Appendix C for details.
3. Mount the suction pressure sensor and connect
the transducer cable. See Appendix C for details.
4. Connect the valve. If using a stepper valve, connect
the M12 connection to the valve and tighten to 10-
14 in-lbs. (1.13 to 1.58 Nm). If using a pulse valve,
connect the DIN connector to the pulse valve.
Tighten the DIN connector mounting screw to 3.5
in-lb (0.40 Nm).
5. Connect the power wires. The power connection
does not come with any connectors, so the con-
nection to power must be made in compliance
SCS-PB
Pulse System Control
SCS-SB
Step System Control

Page 4 – Bulletin 100-50-11.1
with local, state and federal regulations. The power
requirements are described below. See Appendix
B for more details on specific power specifications.
• Voltage: 100-240 VAC, 50-60 Hz
• SCS-PB Power Requirement: 1.5W for controller
+ Pulse Valve Power Rating (31W max)
• SCS-SB Power Requirement: 4W
⚠WARNING: Route and secure cables away
from hot surfaces, high voltage lines, and moving
components. Use caution when working around high
voltage components. Safety covers should be used
for personal safety on high voltage panels. Ensure the
wires are not placed close to any sharp or abrasive
objects to avoid any nicking, scraping, or cutting of
the wire insulation. Secure all wires to prevent pulling
or applying tension to the wires.
A. TECH CHECK SETUP
1. Download the Sporlan Tech Check app. Search
for ‘Sporlan Tech Check’ on the app store.
4. Once your email is verified, open the Tech Check
app and either click ‘Reload’ or log in using your
email address and password.
7. Once access is granted, the setup will be
complete. Tap the back button to return to the
home screen of the app.
3. Setup
Setup of the SCS series of controllers is done using the Tech Check app for Apple mobile devices.
You will need a mobile device with Bluetooth LE capability.
2. Click on the ‘Register’ tab
and create an account by
entering the following and
then tapping ‘Register’ in
the top right:
a. Email Address
(will need to be verified)
b. Password
c. Company name
d. Your full name
3. A verification email is sent
to the email address that
you provided. Open your
email application and
click the link in the email
to verify your account.
5. Once you are logged into
the app you will need to
request access to the
various products that the
Tech Check app supports.
To do this, click on the
gear icon at the top right
of the screen.
6. Tap on ‘Request SCS
access’ and wait for the
access to be granted. It
should take less than a
minute with an established
cellular connection.

Bulletin 100-50-11.1 – Page 5
B. SCS SETUP
1. Power up the SCS controller.
2. Activate the Bluetooth Broadcasting on the SCS
controller by briefly placing a magnetic screwdriver,
or other magnet over the controller at the indicated
location. Note that if it is successful, you will see
the blue LED on the controller begin to blink.
3. Open the Tech Check app.
If the blue LED is blinking,
the controller should appear
on the Controller Inventory
screen. The Bluetooth ID
shown on the label of the
controller will be displayed
on the app.
5. Upon connecting, the app
will read the controller case
ID and populate a tab on
the bottom of the screen
with the ID. The controller’s
case ID may be changed
in the app.
6. Touch the upper left
“Options” button and
select the Parameters
page. The key parameters
needed to set up the
controller are visible
here. Change the
parameters as desired
for your application. See
the Parameters section
for more details on the
parameters.
4. Select and connect to the controller. Once the
controller is connected, the blue LED on the
controller will turn solid blue.
TIP: Settings can be
copied and pasted from
one controller to another.
Once you have set up a
controller you can click
the copy icon at the top
right of the parameter
page, connect to another
controller, go to that
controller’s parameter
page and paste it there.

Page 6 – Bulletin 100-50-11.1
4. Parameters
The following tables describes the parameters that are available for this controller. The parameters can be
accessed by connecting to the controller by using a mobile device such as a smart phone. See the Setup
Section for more details on how to connect to the controller.
Parameter Description Range
Date/Time Current date and time Dates/Times
Superheat Target The desired superheat 5°F to 45°F
2.78°C to 25°C
Refrigerant Specifies what refrigerant is being used See list of available refrigerants
Identification - Rack Identifies the compressor rack
the coil is connected to 4 characters, alphanumeric
Identification - Lineup Identifies the lineup the coil is connected to 4 characters, alphanumeric
Identification - Case ID Identifies the specific case/coil being
controlled by the controller 4 characters, alphanumeric
Pressure Transducer - Range Specifies the range of the pressure
transducer being used
0 to 1000 PSI
0 to 68.95 bar
Pressure Transducer - Type Specifies the pressure transducer type Absolute or Gauge
Pressure Transducer - Offset Offset from zero applied to the pressure sensor -20 to 20 PSI
-1.38 to 1.38 bar
Coil Outlet Thermistor - Type Specifies the type of thermistor used
The controller comes with a 10K thermistor
2K
3K
10K (default)
Coil Outlet Thermistor - Offset Offset from zero applied to the thermistor -10°F to 10°F
-5.56°C to 5.56°C
Stepper Type - Number of Steps Specifies the number of steps the stepper
valve has – only applies to SCS-SB 100 to 10,000 steps
Stepper Custom Polarity
Specifies the valve polarity –
only applies if “Custom” is chosen as
the stepper type on the SCS-SB
Unipolar or Bipolar
Stepper Custom Step Rate
Specifies the valve movement rate in steps/
second – only applies if “Custom” is chosen
as the stepper type on the SCS-SB
30 to 400
Refrigerants available to use with the SCS controller:
R-22 R-134a R-402A R-404A R-407A R-407C R-410A R-417A
R-422A R422D R-507A R-744 R-245fa R-438A R-401B R-408A
R-508A R-508B R-407F R-434A R-444B R-448A R-450A R-449A
R-452A R-513A R1336mzz R-427A R-422C
Note: Additional refrigerants may be added over time. If your refrigerant is not listed, a new firmware package with additional refrigerants may be
available. Please contact Sporlan Application Support or your local Sporlan Sales Representative for information.

Bulletin 100-50-11.1 – Page 7
Indicator Action Status
Green/PWR LED On Indicates the unit is powered
Yellow/VLV LED Off Valve is off or at 0% open
Yellow/VLV LED On Valve is on or at 100% open
Yellow/VLV LED blinking periodically Number of blinks indicates % of open. One blink for every ten percent of open.
Only applies to the SCS-SB.
Yellow/VLV LED blinking constantly Fast blinking indicates a valve connection issue.
Blue/BT LED blinking Indicates the unit is advertising for Bluetooth.
The unit is visible to mobile devices at this point.
Blue/BT LED On Indicates the unit is connected to a mobile device through Bluetooth.
Red/ALM LED On Indicates that an alarm is active. See the Alarms Section for more details.
Alarm Description
Transducer Voltage Low Voltage on the pressure transducer is very low, indicating a potential issue with the
connection or sensor.
Transducer Voltage Out of Range Voltage on the pressure transducer is outside the expected range for normal operation.
This may indicate a wiring issue or problem with the sensor.
Transducer Not Connected This indicates the controller is not able to detect the pressure transducer.
This typically points to a connection issue with the pressure transducer.
Coil Outlet Resistance Low This indicates the resistance for the coil outlet thermistor is out of range and is low.
This is typically cause by a short circuit on the thermistor.
Coil Outlet Resistance High This indicates the resistance for the coil outlet thermistor is out of range and is high.
This is typically cause by a connection problem or open circuit with the thermistor.
EEV No Continuity This indicates that there is a connection problem with the stepper valve.
This may also be caused by a damaged/defective valve.
EEV Overcurrent This indicates the current for the pulse or stepper valve exceeds the expected range.
This is typically due to a connection/wiring problem or a damaged/defective valve.
Low Superheat This indicates that the superheat value is trending low (below 3°F / 1.67°C over the last
hour).
High Superheat This indicates that the superheat value is trending high (above 50°F / 27.78°C over the
last hour).
5. LED Indicators
The controller has 4 LED indicators that allow you to quickly see some basic information about the controller
status as shown in the table below.
6. Alarms
The controller has the capability to detect issues and alert the user of any issue it encounters via alarms.
When any alarm is active, the red ALM LED will be on. To see what alarms are active, connect to the controller
through a mobile device. In the app, there is an alarm bell icon on the top right of the screen. Tapping this
icon moves to the alarm screen. The alarm screen will list all possible alarms. Currently triggered alarms will
be highlighted. See the Setup Section for more details on how to connect to the device. The table below
describes the possible alarms.

Page 8 – Bulletin 100-50-11.1
7. Normal Operation
The operation of the controller can be checked using the Sporlan Tech Check app. First connect to the
controller. For more details on how to connect to the controller, see the Setup Section. Once connected, the
screen will show several process values as described in the table below. These values describe the current
operation of the controller.
Process Value Description
State The current state of the controller.
SH This is the current value of superheat being read by the controller.
SP This is the current suction pressure being read by the controller.
SST This is the current saturated suction temperature being calculated by the controller.
COT This is the current coil outlet temperature being read by the controller.
EEV This is the current valve position of the valve if it is a stepper valve. If it is a pulse valve, this indicates the current pulse duty cycle.
DEV This indicates the current device temperature being measured by the controller. This is the temperature of the controller itself.
8. Overrides
The Tech Check app will allow you the ability to override
some values of the controller for troubleshooting
purposes. These overrides will remain active for 10
minutes before being relinquished and allowing the
controller to control these values again. The values
that can be overridden are the EEV Percent Open (This
is duty cycle for a pulse valve), and the superheat.
9. Firmware Update
Firmware updates may be available from time to time
to provide new features and improvements to the
controller. Those firmware updates may be applied
to the controller using the Tech Check app. First,
connect to the controller using a mobile device. For
more details on how to connect to the controller,
refer to the Setup Section. After connecting, touch
the icon on the upper left to access more options,
and select firmware update. The update may take
up to 5 minutes. The mobile device must not leave
the proximity of the controller during this time for the
update to complete successfully.
10.Data Logs/Graphing
The controller can store historical data, every
20 seconds for 30 days, in order to help with
troubleshooting. This historical data is saved in the
memory of the controller and can be retrieved and
graphed using the Sporlan Tech Check app. In order
to view graphs of historical data, simply connect to
the controller and touch the numerical value on the
row of the process value you wish to graph. It is also
possible to request a CSV file of the logs and share
through e-mail, text, etc.
Appendix A: Ordering Information
Description Item Number Notes
Superheat Controls
SCS Pulse Valve
SCS Stepper Valve
SCS-PB
SCS-SB
Pressure Transducers*
PSPT0150SVSP-S
PSPT0300SVSP-S
PSPT0500SVSP-S
PSPT0652SVSP-S
952572
952574
952576
952579
0 to 150 psis transducer (all other refrigerants)
0 to 300 psis transducer (R410A)
0 to 500 psis transducer (R744)
0 to 652 psis transducer (R744)
*Select one per controller based on refrigerant.

Bulletin 100-50-11.1 – Page 9
Appendix B: Technical Specifications
Electrical
• Supply Voltage: 100-240 VAC, 50-60 Hz
• SCS-PB Power Requirement: 1.5W for controller
+ Pulse Valve Power Rating (31W max)
• SCS-SB Power Requirement: 4W
Mechanical
• Operating Temperature: -22°F to 120°F
(-30°C to 50°C)
• Storage Temperature: -40°F to 140°F
(-40°C to 60°C)
• IP Rating: IPX6, IPX7
• Operating Humidity: 10% to 100% RH
• Storage Humidity: 10% to 100% RH
Compliance
• FCC (US)
• IC (CA)
• CE
• UL Recognized (US and CA),
UL File Number: E75259
• RoHS
OV Category Application Data
SCS controls are designed for use in applications
where the equipment is connected to the AC supply
using a plug and socket (OV Category II applications).
When applying the SCS controls in permanent wired
equipment (OV Category III applications), a 1A inline
fuse and MOV are required.
• Fuse 1A Littlefuse Type 3AG Slo-Blo®or similar.
• MOV 300V Littlefuse V300LA20AP or similar.
Certified UL 1449
Pressure
Transducer
Neutral
Line
Suction
Temperature
Sensor
Evaporator
Refer to the evaporator manufacturer’s
installation/orientation instructions.
1-2” ideal
10-14”
EEV
minimize
MOV*
Fuse*
120-240
VAC Power
SCS-SB
Pressure
Transducer
Neutral
Line
Suction
Temperature
Sensor
Evaporator
Refer to the evaporator manufacturer’s
installation/orientation instructions.
1-2” ideal
10-14”
minimize
MOV*
Fuse*
SCS-PB
SPW
120-240
VAC Power
Earth

Page 10 – Bulletin 100-50-11.1
Bulletin 100-50-11.1 / 42020© 2020 Parker Hannin Corporation
Parker Hannin Corporation
Sporlan Division
206 Lange Drive • Washington, MO 63090 USA
phone 636 239 1111 • fax 636 239 9130
www.sporlan.com
Appendix C: Sensor Installation
Mount the Pressure Transducer
1. Locate or install a ¼” SAE access fitting on the
suction line near the outlet of the evaporator.
Mount it at 12 o’clock on a free-draining horizontal
line to decrease the possibility of oil trapping.
WARNING: Remove pressurized refrigerant from
the line before installing the fitting.
2. Install the transducer, tighten it to 8 ft-lbs, and
check for leaks. Do not use a gasket or a washer.
WARNING: For safety, ensure that the correct
Schrader core is installed in the access fitting
and use caution when removing Schrader cap/
installing transducer to avoid contacting escaping
refrigerant.
3. Connect the pressure transducer cable to the
transducer.
4. Route and secure transducer cable away from hot
surfaces and high power A/C voltage lines.
5. Ensure pressure range and type (gauge or
absolute) are configured properly in the controller,
See Section 3 - SETUP.
6. After startup, use a gauge set to verify proper
pressure reading through the controller. An
improperly installed Schrader core can cause
erroneous pressure readings.
7. Check for leaks after system is in operation.
Mount the Suction Outlet Temperature Sensor
1. Per Appendix B - Wiring Diagram, the temperature
sensor should be installed 10-14 inches (25-36
cm) from the heat exchanger, on a free-draining
horizontal line. Minimize the distance from the
pressure transducer.
2. Use Scotch-Brite™to clean the copper line at the
installation location. Removal of the oxides and dirt
will increase sensor accuracy.
3. Fasten the suction temperature sensor as oriented
in Figure 2. Mount the sensor on the suction
line after the heat exchanger, near the pressure
transducer.
4. Route the cable away from hot surfaces and high
power A/C voltage lines.
5. Verify that the controller is configured properly for
the temperature sensor used (2K, 3K, or 10K), See
Section 3 - SETUP.
6. Wrap temperature sensor and copper tube with
foam insulation to minimize ambient temperature
effects (Figure 3).
Figure 1 Figure 2 Figure 3
This manual suits for next models
3
Table of contents
Other Parker Network Hardware manuals
Popular Network Hardware manuals by other brands

Multitech
Multitech Multi-Tech RouteFinder SOHO RF820 user guide

Patton electronics
Patton electronics NetLink 2707C user manual

Axis
Axis AX ONE manual

Digicom
Digicom Vega Video Network Device Specifications

Deutsche Telekom
Deutsche Telekom T-Eumex 704PC LAN user guide

Avaya
Avaya Cajun P550R Cli reference guide