PCI MicroTrans II Manual

MicroTransII
Summing Signal Processor
Operation & Maintenance Manual
Engineered for accuracy, applicability,
durability and simplicity in HVAC air systems
and industrial process control loops


MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated i Revision Level 002
TABLE OF CONTENTS
TABLE OF CONTENTS............................................................................................................................. i
1. INTRODUCTION .............................................................................................................................. 1
1.1. DESCRIPTION............................................................................................................................ 1
1.2. BASIC OPERATION .................................................................................................................. 1
1.3. PI1/D Control Loop...................................................................................................................... 1
1.3.1. PI1/D Parameter Description and Response......................................................................... 1
1.3.2. Correctly Tuned Control Loop.............................................................................................. 2
1.4. SPECIFICATIONS ...................................................................................................................... 2
1.4.1. Power Supply........................................................................................................................ 2
1.4.2. Power Consumption.............................................................................................................. 2
1.4.3. Accuracy ............................................................................................................................... 2
1.4.4. Temperature Input Options................................................................................................... 2
1.4.5. External Flow Input Options................................................................................................. 2
1.4.6. Economizer Override Input Options..................................................................................... 2
1.4.7. System Start Input................................................................................................................. 2
1.4.8. Process (MT2 Measured / Total) Output Options................................................................. 2
1.4.9. Controller Output Options .................................................................................................... 2
1.4.10. High/Low Alarm Relay Outputs ....................................................................................... 2
1.5. SAFETY....................................................................................................................................... 3
1.5.1. Electrical Connections .......................................................................................................... 3
1.5.2. Static Electricity.................................................................................................................... 3
2. PRODUCT DIMENSIONS ................................................................................................................ 4
2.1. MECHANICAL DIMENSIONS.................................................................................................. 4
3. INSTALLATION ............................................................................................................................... 5
3.1. ELECTRICAL & PNEUMATIC INSTALLATION................................................................... 5
3.2. TEMPERATURE TRANSMITTER CONNECTION................................................................. 6
3.2.1. 4-20mA Output/2-Wire Loop Powered Temperature Transmitter ....................................... 6
3.2.2. 0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter .................................... 6
3.2.3. 0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter .................................... 7
3.2.4. 0-10VDC or 4-20mA from a Building Management System (BMS)................................... 7
4. INPUT/OUTPUT SET-UP ................................................................................................................. 8
4.1. TEMPERATURE INPUT (OPTION).......................................................................................... 8
4.2. External AIRFLOW Input............................................................................................................ 8
4.3. Economizer Override Input (Option) ........................................................................................... 8
4.4. Process Output.............................................................................................................................. 8
4.5. Temperature Output ..................................................................................................................... 8
4.6. Controller Output ......................................................................................................................... 9
4.7. Output Voltage Selection ............................................................................................................. 9
5. COMMON STARTUP CONFIGURATION CHANGES................................................................ 10
5.1. AREA FACTOR ........................................................................................................................ 10
5.2. OPERATING RANGE .............................................................................................................. 11
5.3. CONTROLLER PARAMETERS .............................................................................................. 12
5.3.1. Tuning Parameters .............................................................................................................. 12
5.3.2. Controller Setpoint (Internal Value) ................................................................................... 12
5.3.3. Action.................................................................................................................................. 13
5.4. TEMPERATURE COMPENSATION FOR AIR DENSITY.................................................... 14
5.4.1. Temperature Input Signal Selection.................................................................................... 14

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated ii Revision Level 002
5.4.2. Temperature Units .............................................................................................................. 14
5.4.3. Temperature Values ............................................................................................................ 15
5.4.4. Temperature Input............................................................................................................... 16
5.4.5. Fixed Value......................................................................................................................... 17
6. ACTIVE DISPLAYS & KEY FUNCTIONS ................................................................................... 18
6.1. POWER-UP INITIATION DISPLAY....................................................................................... 18
6.2. PROCESS DISPLAY DESCRIPTIONS ................................................................................... 18
6.3. KEY FUNCTIONS .................................................................................................................... 19
7. DISPLAY MENUS........................................................................................................................... 20
7.1. FIELD SETUP & TECH. CONFIGURATION MENUS.......................................................... 20
8. FIELD SETUP MENUS................................................................................................................... 21
8.1. OPERATING RANGE .............................................................................................................. 21
8.2. ZERO PRESSURE CALIBRATION......................................................................................... 21
8.3. ENGINEERING UNITS ............................................................................................................ 22
8.4. LOCKDOWN............................................................................................................................. 22
8.4.1. Lockdown Value................................................................................................................. 22
8.4.2. Lockdown Delay................................................................................................................. 23
8.5. FLOW CORRECTION .............................................................................................................. 23
8.5.1. Flow Correction (K-Factor Calculator) .............................................................................. 23
8.5.2. Flow Correction (K-Factor) ................................................................................................ 24
8.6. AUTOZERO .............................................................................................................................. 24
8.6.1. AutoZero Status .................................................................................................................. 24
8.6.2. AutoZero Interval................................................................................................................ 25
8.6.3. AutoZero Test Process........................................................................................................ 25
8.7. TEMPERATURE COMPENSATION ...................................................................................... 25
8.7.1. Temperature Units .............................................................................................................. 26
8.7.2. Temperature Values ............................................................................................................ 26
8.7.3. Temperature Input............................................................................................................... 27
8.7.4. Fixed Value......................................................................................................................... 28
8.8. Measured Flow DISPLAY FILTER .......................................................................................... 28
8.9. External Flow Display Filter ...................................................................................................... 29
8.10. Output Process Filter .............................................................................................................. 29
8.11. Output Temperature Filter ...................................................................................................... 30
8.12. HIGH/LOW ALARM OPTIONS........................................................................................... 31
8.12.1. Alarm Status.................................................................................................................... 31
8.12.2. Alarm Values................................................................................................................... 31
8.12.3. Alarm Delay .................................................................................................................... 32
8.13. DP DISPLAY FORMAT ....................................................................................................... 32
8.14. FACTORY DEFAULTS ........................................................................................................ 33
9. TECH CONFIGURATION MENUS ............................................................................................... 34
9.1. CONTROLLER PARAMETERS .............................................................................................. 34
9.1.1. Controller Display............................................................................................................... 34
9.1.2. Tuning Parameters .............................................................................................................. 34
9.1.3. Action.................................................................................................................................. 35
9.1.4. Controller Setpoint (Internal Value) ................................................................................... 35
9.1.5. Output Start......................................................................................................................... 36
9.1.6. Alarm On/Off...................................................................................................................... 37
9.1.7. Output Override .................................................................................................................. 37
9.1.8. System Alarm Delay ........................................................................................................... 37

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated iii Revision Level 002
9.1.9. Economizer Override .......................................................................................................... 38
9.2. AREA FACTOR ........................................................................................................................ 38
9.3. TRANSDUCER CALIBRATION ............................................................................................. 40
9.3.1. Minimum Calibration.......................................................................................................... 40
9.3.2. 50% Calibration .................................................................................................................. 40
9.3.3. Span Calibration.................................................................................................................. 41
9.4. TEMPERATURE FIXED VALUE (No Temp Comp Option).................................................. 41
9.5. External Flow Source ................................................................................................................. 42
9.6. External Flow Span .................................................................................................................... 42
9.7. altitude........................................................................................................................................ 43
9.8. PROCESS OUTPUT MENU ..................................................................................................... 44
9.8.1. Output Selection.................................................................................................................. 44
9.8.2. Voltage Output Level Select............................................................................................... 45
9.8.3. Minimum Calibration.......................................................................................................... 45
9.8.4. Span Calibration.................................................................................................................. 46
9.9. TEMPERATURE OUTPUT MENU ......................................................................................... 46
9.9.1. Voltage Output Level Selection.......................................................................................... 46
9.9.2. Minimum Calibration.......................................................................................................... 47
9.9.3. Span Calibration.................................................................................................................. 47
9.10. CONTROLLER OUTPUT MENU ........................................................................................ 48
9.10.1. Voltage Output Level Selection ...................................................................................... 48
9.10.2. Minimum Calibration...................................................................................................... 48
9.10.3. Span Calibration.............................................................................................................. 49
9.11. CORRECTION COEFFICIENT ............................................................................................ 49
9.11.1. Probe Coefficient............................................................................................................. 49
9.11.2. Piezometer Ring Coefficient ........................................................................................... 50
9.12. FOUR POINT FLOW CORRECTION.................................................................................. 51
9.13. MAC ADDRESS (BACNET COMMUNICATION OPTION)............................................. 52
9.14. INSTANCE NUMBER (BACNET COMMUNICATION OPTION) ................................... 52
9.15. MODBUS ID (MODBUS COMMUNICATION OPTION).................................................. 53
9.16. BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS).......................... 53
10. WARNING MESSAGES .............................................................................................................. 54
10.1. INPUT PRESSURE OVERRANGE MESSAGE .................................................................. 54
10.2. TRANSDUCER CALIBRATION MESSAGE...................................................................... 54
10.3. OPERATING RANGE MESSAGE ....................................................................................... 54
10.4. NEW OPERATING RANGE MESSAGE ............................................................................. 55
11. TROUBLESHOOTING GUIDE ................................................................................................... 56


MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 1 Revision Level 002
1. INTRODUCTION
1.1. DESCRIPTION
The MicroTransII Summing Signal Processor employs current state-of-the-art digital microprocessor
technology to produce highly stable and accurate air flow measurements. The MicroTransII is factory
configured and calibrated to the exact specification determined at time of order. The MicroTransII
Summing Signal Processor is capable of receiving an external air flow signal (4-20mA / 0-10 VDC) ,
summing the two air flow values and displaying the MicroTransII measured air flow and the total air
flow. The MicrotransII offers an optional controller that utilizes a proprietary algorithm which results in
true three mode control incorporating proportional band, integral (reset) and inverse derivative (P, I,
1/D) controller functionality and tuning. The controller will provide responsive modulation of a control
damper or variable speed drive guaranteeing a constant airflow or pressure is maintained. Additional
optional features include AutoZero; High/Low Remote Alarms; Temperature Compensation; and
LonWorks®, BACnet®-MS/TP Master, and Modbus® Slave communication. Simple field
configuration of engineering units, operating range, process noise filtering, alarm set points, etc., are
performed via password protected intuitive menus that are accessed through the integral six button touch
pad. Device monitoring and configuration can also be performed by a building management system
through a LonWorks®, BACnet®-MS/TP Master, or Modbus® Slave communication network.
1.2. BASIC OPERATION
The transducer receives a differential pressure signal from the pressure or flow sensing element. This
signal is scaled and linearized before being displayed along with the total air flow value from an external
transmitter. The process output (4-20mA, 0-5VDC, or 0-10VDC) signal is selectable between the
MicrotransII measured air flow and the total air flow value. The AutoZero option detects and corrects
any zero offset caused by large ambient temperature changes. The Temperature Compensation option
compensates the flow and velocity signal for density changes caused by variations in the process air
temperature; an external temperature transmitter or input signal from the building management system is
required.
1.3. PI1/D CONTROL LOOP
The PI1/D controller measures the difference between the process value and the setpoint value to
determine the error value. The controller continually attempts to remove this error by varying the
control output signal to adjust the variable frequency drive (VFD) or damper. To optimize the control
loop response, the control parameters (Proportional Band [PB], Integrator Time [Reset], and Inverse
Derivative [1/D]) may need to be adjusted.
1.3.1. PI1/D Parameter Description and Response
- Proportional Band (PB): The function of the PB parameter is to amplify the current
error value (process value minus setpoint value) to make a quick control change to a large
error change. The PB adjustment range is 1 to 100%. The formula is Gain = 100% / PB.
For example, a PB setting of 100% is a gain of 1; i.e., it takes a 100% error signal to get a
full response of the controller. Conversely, a PB setting of 10% is a gain of 10; i.e., it
takes a 10% change of the error signal to get a full response of the controller. Therefore,
decreasing the PB value will cause the controller’s response to speed up.
- Integrator Time (Reset): The function of the Reset is to remove any residual error
present after the PB and 1/D functions. The Reset adjustment range is 1 to 300 seconds.
Decreasing the Reset value will cause the controller’s response to speed up.

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 2 Revision Level 002
- Inverse Derivative (1/D): The function of the 1/D parameter is to filter out the noise by
delaying the controller response for a specific time period and then give a quick boost to
the control output signal. The 1/D function helps improve response and stability of the
control loop. The 1/D adjustment range is 1 to 300 seconds. Decreasing the 1/D value
will cause the controller’s response to speed up.
1.3.2. Correctly Tuned Control Loop
A correctly tuned control loop will respond to an error change quickly and return the process to the
setpoint value with minimum overshoot and oscillation, referred to as a critically damped or tuned
system (See Figure 1). The three control parameters operate in concert with each other, however each
has a specific roll in controller response.

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 1 Revision Level 002
1.3.2.1. Poorly Tuned Control Loop
A poorly tuned control loop may respond to an error change too quickly and overshoot the setpoint
value, respond to slowly and never return to setpoint value or continually oscillate above and below the
setpoint value (See Figure 2). For an output that responds too quickly and continues to overshoot,
Paragon Controls suggests increasing the 1/D and Reset values in small increments to slow the response.
An output that gradually approaches the setpoint but never really gets there is too slow. Paragon
Controls suggests decreasing the 1/D and Reset values in small increments to speed up the response.

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 2 Revision Level 002
1.4. SPECIFICATIONS
1.4.1. Power Supply
20 to 28 VAC/DC
1.4.2. Power Consumption
Standard Unit: 192mA at 24VAC
113mA at 24VDC
Full Options: 417mA at 24VAC
229mA at 24VDC
1.4.3. Accuracy
±0.25% full scale (Standard)
±0.10% full scale (Optional)
1.4.4. Temperature Input Options
0-10VDC
4-20mA
1.4.5. External Flow Input Options
0-10VDC
4-20mA
1.4.6. Economizer Override Input Options
0-10VDC
4-20mA
1.4.7. System Start Input
Dry Contact
1.4.8. Process (MT2 Measured / Total) Output Options
0-5VDC
0-10VDC
4-20mA (700Ωmaximum load)
1.4.9. Controller Output Options
0-5VDC
0-10VDC
4-20mA (700Ωmaximum load)
1.4.10. High/Low Alarm Relay Outputs
Two single (1 form C) dry contacts rated for:
5 amps at 30VAC/dc
10 amps at 120VAC

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 3 Revision Level 002
1.5. SAFETY
1.5.1. Electrical Connections
Before any electrical connections are made, ensure the POWER SWITCH is in the OFF position.
1.5.2. Static Electricity
The circuit board contains components which are susceptible to damage caused by static electrical
discharge. Should it be necessary to remove the circuit board from the enclosure, appropriate
precautions must first be taken to ensure that the operator and the circuit board are at the same electrical
potential.

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 4 Revision Level 002
2. PRODUCT DIMENSIONS
2.1. MECHANICAL DIMENSIONS
PG21(3/4")
PG13.5(1/2") PG13.5(1/2")
MOUNTING SCREW DIA. UP TO 1/4".
8.2"
(TYP OF 2)
PG13.5(1/2")
STANDARD 1/4" COMPRESSION OPTION
5.0"
I.D./DATA LABEL
PARAGON
INCORPORATED
CONTROLS
PCI
MicroTrans
SIGNAL PROCESSOR
1,225
75 F
ACFM
II
*
Cont. Sp: 1500
Cont. Output: 45% RUN
9.56"
3.12"
7.0"
Measured 3,500
Total

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 5 Revision Level 002
3. INSTALLATION
3.1. ELECTRICAL & PNEUMATIC INSTALLATION
- Remove the cover by turning each corner cover mounting screw counter clockwise.
- The NEMA 4X enclosures incorporate three 1/2 inch conduit connections and one 3/4 inch
conduit connection to interface all electrical wiring and pneumatic tubing to the device.
Determine which conduit connection will be used and remove the black plug and install the
appropriate conduit fitting (By Others).
- The five electrical connectors (J1, J2, J3, J4, and J5) located on the MicroTransII board have
removable terminal blocks for ease of installing the interface wiring. (Caution - All electrical
connections must be made with the MicroTrans
II
power switch in the OFF position).
(24VAC/DC)
POWER SUPPLY
REFER TO SECTION 3.2
FOR PROPER TEMPERATURE
TRANSMITTER CONNECTION
RECEIVING DEVICE
(PROCESS) +
-
LCD DISPLAY
ESC
J1 J2 J3 J5
123 6
54 1112 13
7161514 1817 2827
ENTER
ON
OFF
POWER SWITCH DISPLAY
2221 252324 26
J4
19208910
AINP
mA
V
TMP SP ECO PRO CNTTMP
AOUT
LON
SVC
RECEIVING DEVICE
(TEMPERATURE)
+
-
5
J2
4
3
J1
2
1
26
25
24
23
J4
22
21
J5
28
27
18
17
16
15
14
13
12
11
J3
20
19
9
8
7
6
10
RECEIVING DEVICE
(VFD OR DAMPER)
CONTROLLER OUTPUT
+
-
24VAC/DC
EARTH GROUND
+PROCESS OUTPUT
-PROCESS OUTPUT
+24VDC OUTPUT POWER
+TEMPERATURE INPUT
-TEMPERATURE INPUT(GND)
+TEMP. OUTPUT
-TEMP. OUTPUT(GND)
PURGE HOLD (DRY CONTACT)
+ EXT FLOW SIGNAL INPUT
- EXT FLOW SIGNAL INPUT
+ ECON. OVERRIDE
- ECON. OVERRIDE
+ CONT. OUTPUT
- CONT. OUTPUT
SYSTEM START (DRY CONTACT)
COM
NO
NC
COM
NO
NC
HIGH ALARM
LOW ALARM
+ NETWORK COMMUNICATIONS
- NETWORK COMMUNICATIONS
Tp CONNECTION
Sp CONNECTION
FE-1000
STATIC (LOW)
PRESSURE
CONNECTION
TOTAL (HIGH)
PRESSURE
CONNECTION
TYPICAL FLOW ELEMENT CONNECTION
+
-TRANSMITTER
EQ AIRFLOW

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 6 Revision Level 002
3.2. TEMPERATURE TRANSMITTER CONNECTION
Verify Temperature Input switch (TMP) position matches the input signal type. Shielded cable is
recommended for all connections between the MicroTransII and the Temperature Transmitter.
3.2.1. 4-20mA Output/2-Wire Loop Powered Temperature Transmitter
TEMP.
TRANSMITTER
(4-20mA LOOP
POWERED)
+
-
LCD DISPLAY
ESC
J1 J2 J3 J5
123 6541112137161514 1817 2827
ENTER
ON
OFF
POWER SWITCH DISPLAY
2221 252324 26
J4
19208910
AINP
mA
V
TMP SP ECO PRO CNTTMP
AOUT
LON
SVC 5
J2
4
9
8
7
6
10
+PROCESS OUTPUT
-PROCESS OUTPUT
+24VDC OUTPUT POWER
+TEMPERATURE INPUT
-TEMPERATURE INPUT(GND)
+TEMP. OUTPUT
-TEMP. OUTPUT(GND)
VERIFY CORRECT TEMP
INPUT SWITCH POSITION
UP = mA
DOWN = V
3.2.2. 0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter
TEMP. TRANSMITTER
(24VAC POWERED /
0-10VDC OUTPUT)
+
-
LCD DISPLAY
ESC
J1 J2 J3 J5
123 6541112137161514 1817 2827
ENTER
ON
OFF
POWER SWITCH DISPLAY
2221 252324 26
J4
19208910
AINP
mA
V
TMP SP ECO PRO CNTTMP
AOUT
LON
SVC 5
J2
4
9
8
7
6
10
+PROCESS OUTPUT
-PROCESS OUTPUT
+24VDC OUTPUT POWER
+TEMPERATURE INPUT
-TEMPERATURE INPUT(GND)
+TEMP. OUTPUT
-TEMP. OUTPUT(GND)
24VAC
POWER
SOURCE
+-
O
VERIFY CORRECT TEMP
INPUT SWITCH POSITION
UP = mA
DOWN = V
Note: If the MicroTransII power source is 24VAC, the same power source can be used to power the
Temperature Transmitter.

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 7 Revision Level 002
3.2.3. 0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter
TEMP. TRANSMITTER
(24VDC POWERED /
0-10VDC OUTPUT)
+-
LCD DISPLAY
ESC
J1 J2 J3 J5
123 6541112137161514 1817 2827
ENTER
ON
OFF
POWER SWITCH DISPLAY
2221 252324 26
J4
19208910
AINP
mA
V
TMP SP ECO PRO CNTTMP
AOUT
LON
SVC 5
J2
4
9
8
7
6
10
+PROCESS OUTPUT
-PROCESS OUTPUT
+24VDC OUTPUT POWER
+TEMPERATURE INPUT
-TEMPERATURE INPUT(GND)
+TEMP. OUTPUT
-TEMP. OUTPUT(GND)
O
VERIFY CORRECT TEMP
INPUT SWITCH POSITION
UP = mA
DOWN = V
3.2.4. 0-10VDC or 4-20mA from a Building Management System (BMS)
TEMPERATURE SIGNAL
FROM BMS SYSTEM
(0-10VDC / 4-20mA)
+
-
LCD DISPLAY
ESC
J1 J2 J3 J5
123 6
54 1112 13
7161514 1817 2827
ENTER
ON
OFF
POWER SWITCH DISPLAY
2221 252324 26
J4
19208910
AINP
mA
V
TMP SP ECO PRO CNTTMP
AOUT
LON
SVC 5
J2
4
9
8
7
6
10
+PROCESS OUTPUT
-PROCESS OUTPUT
+24VDC OUTPUT POWER
+TEMPERATURE INPUT
-TEMPERATURE INPUT(GND)
+TEMP. OUTPUT
-TEMP. OUTPUT(GND)
VERIFY CORRECT TEMP
INPUT SWITCH POSITION
UP = mA
DOWN = V

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 8 Revision Level 002
4. INPUT/OUTPUT SET-UP
The MicroTransII has been configured and calibrated at the factory for the specific application. Refer to
the MicroTransII Set-Up label located on the left side of unit to verify correct Input/Output configuration
for the application. If input or output configuration changes are required refer to the tables in the
sections below and the figure in Section 3.1.
4.1. TEMPERATURE INPUT (OPTION)
To change the input configuration, set the TMP switch as follows:
Temperature Input AINP (TMP)Selection
4-20mA mA
0-10VDC V
4.2. EXTERNAL AIRFLOW INPUT
To change the input configuration, set the SP switch as follows:
Setpoint Input AINP (SP) Selection
4-20mA mA
0-10VDC V
4.3. ECONOMIZER OVERRIDE INPUT (OPTION)
To change the input configuration, set the ECO switch as follows:
Economizer Override Input AINP (ECO) Selection
4-20mA mA
0-10VDC V
4.4. PROCESS OUTPUT
To change the output configuration, set the PRO switch as follows:
(Note: See section 4.7 for voltage level select)
Process Output AOUT (PRO) Selection
4-20mA mA
0-10VDC V
0-5VDC V
4.5. TEMPERATURE OUTPUT
To change the output configuration, set the TMP switch as follows:
(Note: See section 4.7 for voltage level select)
Temperature Output AOUT (TMP) Selection
4-20mA mA
0-10VDC V
0-5VDC V

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 9 Revision Level 002
4.6. CONTROLLER OUTPUT
To change the output configuration, set the CNT switch as follows:
(Note: See section 4.7 for voltage level select)
Process Output AOUT (CNT) Selection
4-20mA mA
0-10VDC V
0-5VDC V
4.7. OUTPUT VOLTAGE SELECTION
To change the output configuration (0-10VDC or 0-5VDC), perform the following procedure:
Step 1. From the active display, enter the Tech. Configuration Menu by pressing the Up/Down
buttons simultaneously.
Step 2. Enter password number 1000 and press the Enter button.
Step 3. Scroll down to the appropriate menu (Process Output Menu, Temp Output Menu or Cont
Output Menu) and press the Enter button.
Step 4. Select the Output Level menu.
Step 5. Select either 0-5VDC or 0-10VDC and press the Enter button.
Step 6. Press the ESC button 3 times to return to the process display.

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 10 Revision Level 002
5. COMMON STARTUP CONFIGURATION CHANGES
5.1. AREA FACTOR
The Area Factor can be entered or modified as follows:
Step 1. From the active display, enter the Tech. Configuration Menu by pressing the Up/Down
buttons simultaneously.
Step 2. Enter password number 1000 and press the Enter button.
Step 3. Press the Enter button once to access the Area Factor Menu.
Step 4. Enter the new Area Factor using the Up/Down/Left/Right buttons.
Step 5. Press the Enter button once.
Step 6. Press the ESC button twice.
Step 7. The active display should now be displayed.
Tech. Config.
Password: 0000
Controller Parameters Area Factor
Area Factor (FT2)
Transducer Cal.
Ext. Flow Source (001.000)
Ext. Flow Span
Altitude
Process Output Menu
Temp. Output Menu
If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Op Range will be
Reset to the MAX
F.S. Value
(Press Enter)

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 11 Revision Level 002
Area Factor
(FT )
(001.000)
Area Factor
(FT )
Accepted
(001.200)
Op Range Outside
Allowable Value.
Op Range Will be
Reset to MAX
F.S. Value
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Area
Factor and pressing
the Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
Enter Value
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Area Factor Example-
2
2
5.2. OPERATING RANGE
The Operating Range allows the user to enter a value which will represent 100% of the process output
signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for
the user to enter as the Operating Range. The Operating Range can be changed using the following
steps:
Step 1. From the active display, enter the Field Menu by pressing and holding the Enter button
for 3 seconds.
Step 2. Press the Enter button once to access the Operating Range Menu.
Step 3. Enter the new Operating Range using Up/Down/Left/Right buttons.
Step 4. Press the Enter button once.
Step 5. Press the ESC button twice.
Step 6. The active display should now be displayed.
Step 7. The Process Output is automatically rescaled to the new Operating Range.
Field Setup
Menu
Operating Range Operating Range
Zero Calibration (6,932-12,656)
Eng. Units (SCFM)
Lockdown
Flow Correction Enter Value
AutoZero (10,000)
Temp. Comp.
Meas. Fl. Disp. Fltr

MicroTransII Summing Operation & Maintenance Manual
Paragon Controls Incorporated 12 Revision Level 002
5.3. CONTROLLER PARAMETERS
5.3.1. Tuning Parameters
The Tuning Parameters Menu allows the user to tune the controller parameters to match the system
dynamics. The Proportional Band value can be entered as a percent value from 1 to 100%. Reset and
Inverse Derivative values will range from 0 to 300 seconds. Decreasing any of the three tuning
parameter values will cause the controller’s response to speed up. Default values will be Proportional
Band = 10%, Reset (Integrator Time) = 70 seconds and Inverse Derivative = 60 seconds.
Tech. Config.
Password: 1000
Controller Parameters Controller Function Tuning Parameters Tuning Parameters
Area Factor Tuning Parameter Proportional Band Proportional Band
Transducer Cal. Action Integrator Time (0010)%
Ext. Flow Source Setpoint Int/Ext 1/Derivative Integrator Time
Ext. Flow Span Cont. Setpoint (070) sec.
Altitude Output Start 1/Derivative
Process Output Menu Alarm ON/OFF (060) sec.
Temp. Output Menu Output Override
5.3.2. Controller Setpoint (Internal Value)
The Controller Setpoint Menu allows the user to enter an Internal Setpoint Value. The acceptable
setpoint range is 0 to the Operating Range Value entered. The Setpoint Value can be changed by
performing the following steps:
Step 1. From the active display, enter the Tech. Configuration Menu by pressing the
Up/Down buttons simultaneously.
Step 2. Enter password number 1000 and press the Enter button
Step 3. Verify Controller Parameters is highlighted and press the Enter button.
Step 4. Scroll down until Cont. Setpoint is highlighted and press the Enter button.
Step 5. Enter the new Setpoint value using the Up/Down/Left/Right buttons.
Step 6. Press the Enter button once.
Step 7. Press the ESC button 3 times.
Step 8. The active display should now be displayed.
Tech. Config.
Password: 1000
Controller Parameters Tuning Parameter Cont. Setpoint
Area Factor Action (ACFM)
Transducer Cal. Setpoint Int/Ext
Ext. Flow Source Cont. Setpoint (000,000)
Ext. Flow Span Output Start
Altitude Alarm ON/OFF
Process Output Menu Output Override
Temp. Output Menu More Selections
Table of contents
Other PCI Signal Processor manuals