3
C. BOILER LOCATION REQUIREMENTS
1. Indoor Installation Only:
a. Do not install the boiler outside or in an area that
would expose the boiler or its gas or electrical
components to rain or dripping or spraying water.
b. Do not install the boiler in a location that would
subject the boiler to freezing. Where freeze
protection is needed, follow the guidelines in this
manual.
2. Flooring:
a. The boiler can be installed on combustible
flooring, but must not be installed on carpeting.
b. The floor must be structurally sound and capable
of supporting the weight of the boiler.
c. The boiler must be leveled front to back and side
to side. Use metal shims if necessary.
3. Accessibility:
Jacket parts will have to be removed for some service
procedures. Ensure that the location provides a
reasonable means for service and operation of the
boiler.
4. System Piping, Fuel and Electrical Supply:
a. The boiler must be located such that piping for
water, gas, vent and air can reasonable be
connected.
b. There must be a reasonable means of providing
electrical supply to the boiler.
5. Adjacent Construction:
Locate the boiler in an area that will prevent water
damage to adjacent construction should a leak occur
or during routine maintenance.
6. Combustion Air:
a. Do not place the boiler in a location that would
restrict the flow of combustion air into the air
intake or subject the boiler to a negative air
pressure in the space when using air from the
boiler room.
b. Provide required combustion air openings to the
boiler room and the building (when required)
when using air from the boiler room for
combustion (see Section C, “Combustion Air
Requirements”). If air is piped to the boiler air
intake connection, combustion air openings are
not required unless other appliances share the
same room.
c. Buildings will require the installation of a fresh air
duct or other means of providing make-up air if
the intake air option isn't used. Any building
utilizing other gas burning appliances, a fireplace,
wood stove or any type of exhaust fan must be
checked for adequate combustion air when all of
these devices are in operation at one time. Sizing
of an outside air duct must be done to meet the
requirements of all such devices.
d. The boiler must be supplied with combustion air
in accordance with Section 5.3, "Air for
Combustion and Ventilation," of the latest revision
of the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and all applicable local building
codes. Canadian installations must comply with
CSA B149.1 or .2 Installation Code for Gas
Burning Appliances and Equipment, or applicable
provisions of the local building codes.
7. Negative Room Pressure:
Never operate the boiler in an environment subjected
to a negative pressure unless it is Direct Vented.
Failure to comply with this warning can result in
excessive levels of carbon monoxide.
8. Combustion Air Contamination:
a. Combustion air contaminated with fluorocarbons
or other halogenated compounds such as cleaning
solvents and refrigerants will result in the
formation of acids in the combustion chamber.
These acids will cause premature failure of the
boiler.
b. Construction Dust: If the boiler is operated while
the building is under construction it must be
protected from wood, concrete, sheet rock and
other types of dust. Failure to properly protect the
boiler from construction dust will damage the
boiler.
c. If the boiler has been operated with contaminated
air, it must be thoroughly inspected. Where
possible, boiler components must be cleaned,
following instructions provided in this manual
and/or supplementary instructions from PB Heat.
Where cleaning is not possible, the boiler may
have to be replaced.
d. Never store combustible materials, gasoline or any
product containing flammable vapors or liquids in
the vicinity of the boiler.
9. Clearances:
a. All installations must provide the minimum
clearances to combustible materials given in
Section B, “Clearance Requirements”.
b. The installation should provide the minimum
service clearances given in Section B, “Clearance
Requirements”, when possible. If these clearances
cannot be met, then:
Ensure that boiler components can be
accessed for operation/start-up/maintenance as
required in this manual.
PREINSTALLATION
Do not install the boiler unless the location meets all
of the requirements in Sections 1 through 9 below.
Failure to comply could result in severe personal
injury, death or substantial property damage.
WARNING