13800A991 11/08/12 2
NOTE: READ THESE INSTRUCTIONS CAREFULLY
BEFORE ATTEMPTING TO INSTALL PUMP.
DESCRIPTION AND APPLICATION
SSM33, SSM33I and SRM4: Myers SSM33, SSM33I
and SRM4 Series Pumps are single seal units,
available in automatic or manual. The SSM33 and
SSM33I series pumps are designed for normal sump
and dewatering, and can also be used in effluent
applications. When used in effluent dosing or S.T.E.P.
applications, the pump must be installed in a separate
tank or compartment at the discharge side of the
septic tank. NEVER INSTALL PUMP IN MAIN TANK
WHERE SLUDGE COLLECTS. DO NOT USE THE
SSM33 OR SSM33I PUMP SERIES FOR RAW
SEWAGE. The SRM4 series pumps are designed for
residential sewage and dewatering applications where
a larger solid size is required.
General: These pumps use shaded pole, 1550 RPM
motors. SSM33 and SSM33I are available in 115
volt only and the SRM4 is available in 115 or 230
volt and all are single phase only. Both the manual
and automatic models come standard with a 10
ft. power cord. A 20 ft. cord and switch length are
optionally available. All automatic models come with a
mechanical (mercury free) piggyback float switch or a
vertical float switch. The SSM33 and SSM33I pumps
are designed to handle 1/2" spherical solids and
have a 1-1/2" NPT discharge threading. The SRM4
pumps are designed to handle 2" spherical solids and
have a 2" NPT discharge threading. An engineered
thermoplastic vortex impeller designed to efficiently
produce the required pressures and flows is used.
WARNING! THESE PUMPS ARE NOT APPROVED
FOR, AND SHOULD NOT BE USED IN SWIMMING
POOLS, FOUNTAINS OR PUMPING POTABLE
(DRINKING) WATER.
AIR LOCKING
A pump is said to be air locked if water traps air in the
pump and it cannot get out, thus preventing the pump
from operating.
Sump pumps have a 1/16" air vent hole in the
impeller chamber to let out trapped air. If this
hole becomes plugged, pump may air lock. As a
secondary precaution a 1/8" hole should be drilled
in the discharge pipe below the check valve. The
check valve should be 12 to 18 inches above pump
discharge. Do not put check valve directly into pump
discharge opening.
LEVEL CONTROLS
The automatic models come with 10' or 20' power
cord and mechanical (mercury free), piggyback
float switch. The 115 or 230 volt piggyback switch
is tethered directly to the pump. The switch can
optionally be mounted to the discharge pipe using
a minimum 3-5/8" tether length. The switch must
float free from pump and basin wall. Plug the switch
cord plug into a properly grounded, rated voltage
receptacle. Plug the power cord into the back of the
switch cord and tape the cords to the discharge pipe
every 12". The power receptacle must be located
outside the wet sump or basin due to the DANGER of
current leakage.
On all duplex units or simplex installations with
additional options like high water alarm, the power
cord plug must be cut off and wired into a control
panel or into a sealed junction box if used in wet sump
or basin. The AWS-1 control also acts as a sealed
junction box for connecting power cord to pump cord.
MOTOR TYPE
The motors used in these pumps are pressed into the
cast iron housings and surrounded by dielectric oil
for superior heat transfer. The SSM33 and SSM33I
are rated at 1/3 HP and the SRM4 is rated at 4/10
HP. All units have class A motor insulation. SSM33
and SSM33I are available in 115 volt, single phase
only and SRM4 is available in 115 or 230 volt, single
phase. All have overload protection, and use a double
sleeve bearing design. These pumps have no starting
switches and do not require a control panel for simplex
installation.
SAFETY WARNINGS
WARNING: Risk of electric shock. Pumps
are supplied with a grounding conductor and
grounding-type attachment plug on the power cord.
To reduce the risk of electric shock, be certain
that it is connected only to a properly grounded,
grounding-type receptacle. DO NOT cut off ground
pin or use an adapter fitting. DO NOT use an
extension cord with this pump.
All pumps have a GROUND WIRE that is connected to
the motor. This wire goes to the receptacle or control
panel which must be connected to a good outside
GROUND.
When wiring this pump follow all local electrical and
safety codes and ordinances as well as the most
recent National Electric Code (NEC-ANSI/NFPA 70).