Release date 2014-06-17 14:05 Date of issue 2014-06-17 121457_eng.xml
Technical data HiD2844
2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
General specifications
Signal type Digital Input
Supply
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage 20.4 ... 30 V DC via Termination Board
Rated current 15 mA at 24 V (per channel)
Power loss 0.35 W at 24 V (per channel)
Input
Connection SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-)
Rated values acc. to EN 60947-5-6 (NAMUR)
Connectable sensor types potential free contact or proximity sensor
Switching point contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA
Line fault detection breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value
Output
Connection SL1: 8a(+), 7a(-); 8b(+), 7b(-); 10a(+), 9a(-); 9b(+), 10b(-)
Rated voltage 30 V
Rated current 50 mA
Output one optocoupled transistor per channel
Signal level 1-signal: (external voltage) -1 V
0-signal: blocked output (off-state current max. 50 µA, typical 5 µA)
Error message output
Connection SL1: 6b
Output type open collector transistor (internal fault bus)
Transfer characteristics
Switching frequency < 2 kHz
Electrical isolation
Output/power supply functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Output/Output functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electrical isolation EN 50178
Electromagnetic compatibility NE 21:2006
For further information see system description.
Degree of protection IEC 60529
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Relative humidity 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protection IP20
Mass approx. 140 g
Dimensions 18 x 106 x 128 mm (0.7 x 4.2 x 5 in)
Mounting on Termination Board
Coding pin 1 and 2 trimmed
For further information see system description.
Data for application in connection
with Ex-areas
EC-Type Examination Certificate CESI 02 ATEX 086 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection ¬II (1)G [Ex ia Ga] IIC , ¬II (1)D [Ex ia Da] IIIC
Input Ex ia, Ex iaD
Voltage Uo13.2 V
Current Io20 mA
Power Po66 mW
Supply
Maximum safe voltage Um250 V AC (Attention! Umis no rated voltage.)
Statement of conformity PF 11 CERT 2109 X , observe statement of conformity
Group, category, type of protection,
temperature class
¬II 3G Ex nA IIC T4 Gc [device in zone 2]
Electrical isolation
Input/input safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V
Input/Output safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2007, EN60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006