Permalert FluidWatch FW25-50 Operation manual

The FluidWatch®Leak Detection
System has been engineered to
monitor small areas for water leaks.
Typical applications include
unmanned equipment rooms, small
raised floor areas, and small tanks.
The system continuously monitors
the capacitance of the sensor cable
and detects changes from the initial
value.
FluidWatch can be powered by 120
VAC, 240 VAC or 24 VDC. Just
seconds after the coaxial sensor
cable contacts water or water-based
liquids, the unit enters into alarm.
The sensor can be quickly dried in
place after the leak is cleaned up
and the system put back on-line.
The FluidWatch system uses an
LED "traffic light" display to indicate
status: Green - system normal,
Yellow - sensor cable break; and
Red - wet cable or a short. The alarm
unit activates an audible alarm and
10 A, 250 VAC, SPDT relays when
either a leak or break occurs. There
are two operator buttons. One is
used to test the system periodically
and the other to silence the alarm.
The silence button can be disabled
via an internal switch to prevent
unauthorized alarm silencing. There
is an internal adjustment to select a
desired alarm threshold from several
inches to several feet to suit any
application. Another internal switch is
used to select whether the system
will silence the alarm automatically
upon cable reset or require an
operator to push the silence button
manually.
FluidWatch is available with three
sensor cable lengths or as a special.
Each model comes complete with a
monitoring unit, jumper cable and
sensor cable, cable mounts, and
cable tags. All cable connectors are
factory installed. The sensor string
can be mixed lengths of jumper and
sensor for monitoring multiple areas.
Model
Number
Part
Number
Sensor Cable Length
ft (m)
FW25-50
8027870
50 (15)
FW25-75
8027871
75 (23)
FW25-100
8027872
100 (30)
FWXX-XXX
Special*
*Maximum total length of sensor and jumper cable 125 ft (38 m)
FluidWatch®
Leak Detection System
Product Data
PRODUCT FEATURES / BENEFITS
Senses water-based liquids within seconds of
contact
Sensitivity from several inches to several feet
Durable sensor cable
Not susceptible to dust/dirt contamination of
the sensor string
Special lengths available upon request
Comes in a kit, complete with jumper cable,
sensor cable, cable mounts, and cable tags.

TECHNICAL DATA:
•Unit Dimensions: 7.17" H x 7.09" W x 2.46" D
(182 mm x 180 mm x 62.5 mm)
Type 12K (IP52)
•Power: 110 ⁄ 240 VAC 50 ⁄60 Hz, 10 VA, 24 VDC 3 W
•Unit Weight: 1.75 lb (0.8 kg)
•Unit Operating Temperature: 0°F to 120°F
(-18°C to 50°C)
•Std. Jumper Cable Length: 25 ft (7.5 m)
•Std. Sensor Cable Temperature Limit 400°F (205°C)
ALARM OUTPUTS:
•AUDIBLE ALARM
•RED, YELLOW, GREEN LEDS
•4 –10 A SPDT RELAYS
PART 1 • SYSTEM
1.1
The FluidWatch Leak Detection
System shall consist of an electronic
monitoring unit, coaxial water-
sensing cable, interconnecting
jumper cable, cable mounts, and
identification tags required for a
typical installation. All cable
connectors shall be factory installed.
The system supplier shall have ten
years of experience in the
manufacture of the leak detection
systems.
PART 2 • COMPONENTS
2.1
The monitoring unit shall be able to
monitor one length of sensing cable.
Three LEDs shall be visible on the
door of the unit indicating System
Monitoring (Green), Leak Detected
(Red), or Wire Break (Yellow). The
unit shall have an audible alarm and
be equipped with four SPDT Form
1C relays having contacts rated for
10A continuous @ 250 VAC.
A Power/Fault relay shall be normally
energized when the system is
powered and deactivate after a loss
of power. The audible alarm and
relays shall be activated in the event
of a leak (2 relays) or a continuity
fault (1 relay).
The system sensitivity shall be easily
adjusted several inches to several
feet of wet cable.
The system shall have two switches
for operator input: test and alarm
silence. Internal jumpers shall enable
the silence button and enable
automatic silence after the cable
resets. Internal switches select
AC/DC operating voltage.
The monitoring unit shall be powered
by [120 VAC] [240 VAC] [24 VDC]. It
shall be housed in a nonmetallic
enclosure with nominal dimensions
of 7ʺx 7ʺx 3ʺ.
2.2
The standard sensor shall be a
coaxial cable consisting of an
insulated center conductor, water
permeable dielectric core, and outer
braid conductor.
The sensing cable shall have the
ability to detect the presence of
water at any point along the cable's
length. The cable shall be easily
field repairable, flexible, and carry
less than 6 VDC under normal
operating conditions.
2.3
The system shall include one
monitoring unit, one length of
sensing cable, one 25 ft (7.5 m)
jumper cable to connect the sensing
cable to the monitoring unit, one
cable mount for every 5 ft (1.5 m) of
sensing and jumper cable, and five
cable tags.
PART 3 • INSTALLATION
3.1
All FluidWatch system components
shall be installed in accordance with
the manufacturer's installation
instructions.
3.2
The monitoring unit shall be installed
and powered in accordance with
NEC and local code requirements.
The information contained in this document is subject to change without notice. PermAlert, a Division of PERMA-PIPE, Inc., believes the information contained herein to be reliable, but makes no
representations as to accuracy or completeness. PermAlert offers a sole and exclusive warranty as is stated in the Standard Terms and Conditions of Sale for these products. In no event will
PermAlert be liable for any indirect, incidental or consequential damages.
PermAlert • 6410 W. Howard St. • Niles, IL 60714-3302
Ph: 847 966-2190 •Fax 847 470-1204 •www.permalert.com
© 2017 PERMA-PIPE, Inc. •All Rights Reserved •Printed in the U.S.A. •(4/17)