manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pertronic
  6. •
  7. Smoke Alarm
  8. •
  9. Pertronic 2251CPI User manual

Pertronic 2251CPI User manual

Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) as shown in the wiring
diagram. (See Figure 2.)
2. Set the desired address on the sensor address switches. (See Figure 1.)
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 2. WIRING DIAGRAM
2
31
2
33
1
2
1
(–)
(+)
+ -
Compatible
Control Panel
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
CLOSE LOOP OPTIONAL WIRING
Remote
Annunciator
(–)
(+)
RA
+–
+
RA
+–
+
RA
+–
+
C0129-10AUS
TAMPER-RESISTANCE
Intelligent photoelectric smoke sensors include a tamper-resistant capability
that prevents their removal from the base without the use of a tool. Refer to
the base manual for details on making use of this capability.
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication)
Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: -10°C to 50°C
Air Velocity: 0 to 1219.2 m/min.
Height: 51 mm installed in B501AUS-W/B501AUS-IV Base
Diameter: 104 mm installed in B501AUS-W/B501AUS-IV Base
Weight: 95 g
Isolator Load Rating: 0.0063*
Applicable Standards: AS 7240.7 and NZS4512
*Please refer to your isolator base/module manual for isolator calculation instructions.
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ).
GENERAL DESCRIPTION
2251CPI and 2251CPI-Ware plug-in type smoke sensors that combine a phot-
oelectronic sensing chamber with addressable-analog communications.
The sensors transmit an analog representation of smoke density over a com-
munication line to a control panel. Rotary dial switches are provided for set-
ting the sensor’s address. (See Figure 1.)
FIGURE 1. ROTARY ADDRESS SWITCHES
TENS ONES
910
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100Z).
Fire Alarm and Control panels offer different feature sets across different mod-
els. As a result, certain features of the photoelectric sensors may be
available on some control panels, but not on others. 2251CPI and 2251CPI-
Wsupport CLIP (Classic Loop Interface Protocol) mode. The possible
features available if supported by the control panel are:
1. The sensor’s LEDs can operate in three ways—on, off, and blinking—and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the control panel for specific opera-
tion. The photoelectric sensors require compatible addressable communica-
tions to function properly. Connect these sensors to listed-compatible control
panels only.
Compatible bases: B501AUS-W/B501AUS-IV.
SPACING
Pertronic recommends spacing sensors in compliance with AS 1670.1:2015 or
NZ4512. All detectors should be spaced and installed in accordance with the
requirements of the relevant authority having jurisdiction. For specific infor-
mation regarding sensor spacing, placement, and special applications, refer
to AS 1670.1:2015, NZ4512, or the Smoke Detector Application Guide.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
I56-7385-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
2251CPI and 2251CPI-W
Intelligent Photoelectric Smoke Sensors
www.pertronic.co.nz
www.pertronic.com.au
1 I56-7385-000
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing
methods must satisfy the Authority Having Jurisdiction (AHJ).
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor
electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs to
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry
Sensitivity readings are available through the FACP. Refer to the manufac-
turer’s published instructions for proper use.
Additionally, canned aerosol simulated smoke (canned smoke agent) may
be used for smoke entry testing of the smoke detector.
When used properly, the canned smoke agent will cause the smoke detec-
tor to go into alarm. Refer to the manufacturer’s published instructions for
proper use of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary
by manufacturer. Misuse or overuse of these products may have long term
adverse effects on the smoke detector. Consult the canned smoke agent manu-
facturer’s published instructions for any further warnings or caution statements.
A sensor that fails any of these tests may need to be cleaned as described
under CLEANING, and retested.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. (See Figure 4.)
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently push-
ing it until it locks into place.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
Note: Dispose of electronic waste according to national and local regulations
when scrapping or replacing a device. Do not discard as general trash.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
FIGURE 3. FEATURES OF THE PHOTO DETECTOR
Magnet
Test
Marker
LED
Base
Alignment
Notch
Magnet Test Marker
Base Alignment Notch
LED C2021-00
FIGURE 4. CLEANING THE PHOTO DETECTOR
Cover
Removal
Tabs
Sensor Cover
Sensing Chamber
Cover and Screen
Sensing Chamber
C2022-00
ON-SITE SENSITIVITY ADJUSTMENT
The sensitivity for this device is set at FDCIE.
For more information on sensitivity settings refer to the manufacturer's Fire
Alarm Control Panel manual.
Australian
Standard
Lic. SMKH25312
SAI-Global
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the
tamper seal on the packaging is present and
unbroken and the product has not been tampered
with since leaving the factory. Do not install this
product if there are any indications of tampering.
If there are any signs of tampering the product
should be returned to the point of purchase.
It is the responsibility of the system owner to
ensure that all system components, i.e. devices,
panels, wiring etc., are adequately protected to
avoid tampering of the system that could result
in information disclosure, spoofing, and integrity
violation.
2I56-7385-000
Ver. B

This manual suits for next models

1

Popular Smoke Alarm manuals by other brands

Xtralis VESDA Commissioning Guide

Xtralis

Xtralis VESDA Commissioning Guide

Climax Technology SD-29-H manual

Climax Technology

Climax Technology SD-29-H manual

Sensor 217E Series Installation guide & user manual

Sensor

Sensor 217E Series Installation guide & user manual

Kidde 0945CA manual

Kidde

Kidde 0945CA manual

Panasonic 3309 Specification sheet

Panasonic

Panasonic 3309 Specification sheet

UniPOS EVPU FD 7130 instruction manual

UniPOS

UniPOS EVPU FD 7130 instruction manual

Siemens DB721-CN Installation

Siemens

Siemens DB721-CN Installation

resideo 5800SMOKEV Installation and setup guide

resideo

resideo 5800SMOKEV Installation and setup guide

Gira 0869 00/04 Instructions for installation

Gira

Gira 0869 00/04 Instructions for installation

Kidde 914 user guide

Kidde

Kidde 914 user guide

Code one A owner's manual

Code one

Code one A owner's manual

Distech Controls GS-SDD Series Hardware installation guide

Distech Controls

Distech Controls GS-SDD Series Hardware installation guide

Teknim TFD 1430 Installation and user manual

Teknim

Teknim TFD 1430 Installation and user manual

family first FFP9VH user manual

family first

family first FFP9VH user manual

Convoy Security YT202 Installation and maintenance instructions

Convoy Security

Convoy Security YT202 Installation and maintenance instructions

jablotron JA-60SR quick start guide

jablotron

jablotron JA-60SR quick start guide

Universal SS-785 instructions

Universal

Universal SS-785 instructions

WAGNER TITANUS PRO-SENS Technical manual

WAGNER

WAGNER TITANUS PRO-SENS Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.