Pfannenberg DTS 8 E Series Product guide

外挂式机柜空调操作及安装说明书
DTS 8xxxE 系列
Operating and assembly instruction
For side-mounted cooling units
DTS 8xxxE
685408014B /10-2016

1 685408014B
1 手册提示 ............................................................... 2
2 搬运....................................................................... 2
2.1
运输
.................................................................... 2
2.2
储运
.................................................................... 2
2.3
开箱
.................................................................... 2
3 供货范围 ............................................................... 2
4 一般信息 ............................................................... 2
5 铭牌....................................................................... 2
6 安全....................................................................... 2
7 功能....................................................................... 3
7.1
配置与功能
......................................................... 3
7.2
工作原理
............................................................ 3
7.3
冷凝物
................................................................ 3
8 安装....................................................................... 3
8.1
概述
.................................................................... 3
8.2
安装工作
............................................................ 3
8.3
电气连接
............................................................ 4
9 运行条件 ............................................................... 4
10 投入使用和功能.................................................. 4
10.1
概述
.................................................................. 4
10.2
操作显示器
...................................................... 5
10.3
启动测试模式
................................................... 5
10.4
机组特性
.......................................................... 5
10.5
门触点
.............................................................. 5
10.6
设备故障
.......................................................... 5
10.7
自检功能
.......................................................... 5
10.8
设置的可能性
.................................................. 5
11 参数查看与设置 ................................................. 5
12 清洁和维护 ......................................................... 6
12.1
清洁
................................................................... 6
12.2
维护
................................................................... 6
13 停止使用............................................................. 6
14 故障排除............................................................. 7
15 保障条款............................................................. 7
附表 I ......................................................................... 8

685408014B2
1 手册提示
此手册为百能堡机电设备有限公司(以下简称百能堡)提供
的门装或侧装螺栓固定,外挂式机柜空调系列的安装运行指
南。
提示
每台机柜空调的技术规格及安装、连接和操作相关信息也可
在随机附带的单独文件中查询。本手册中,安全提示和其他
信息以下形式出现:
危险!
如果没有严格遵守所述的措施,将有生命危险或造成健康危
害。
危险!
如果没有严格遵守所述的措施,将可能因电击造成生命或健
康危害。
注意:
如果没有严格遵守所述的措施,将有可能造成生命财物损失。
提示
提示包含关于所述措施或指导的额外信息。
2 搬运
2.1 运输
•
只能通过壳体或吊环来提升机柜空调(
M8
吊环不在供货范
围)。
•
运输时保持机柜空调处于最终使用时相同的摆放状态。
•
如果整体机柜需要运输,请在运输前将机柜空调拆下并单
独包装。
不按照这些指导操作,将导致保障条款失效。
2.2 储运
•储存环境不应超过
70
℃。
•
储存时使机组处于最终使用时的摆放状态。
不按照这些指导操作,将导致保障条款失效。
2.3 开箱
•开箱过程中应当仔细查看机柜空调,看是否存在因运输造
成的破坏,尤其注意是否有部件松动、凹坑、擦伤和漏油
等。
任何损坏应当立即通知承运商(根据
―
损坏规则
‖
指示),
并且适用
―
百能堡产品售后服务声明
―
的最新版本。
•
在处理包装材料前,务必确认里面没有任何附加部件。
危险!
机组的钣金件边缘有可能残留金属毛刺,在维护或安
装时务必带保护手套。
要求保障时,需要提供故障的确切信息(如有可能请提供照
片),机种型号和序列号。
3 供货范围
供货范围包括:
•
机柜空调
•
附件包(包括紧固件,插头式电气连接器等)
•
特殊的附件(如适用)
•技术规格书
•使用说明书
4 一般信息
•
百能堡可以妥善处理旧设备
,
但客户需承担运输费用
.
•
百能堡生产的机柜空调不含以下物质
:
-
多氯三联苯
-
石棉
-
甲醛
-
镉
-
液态有害物质
•
对每台机柜空调进行检查以确保它是完全依照
9.ProdSV
的规定(德国事故预防法规)。
•
交货前百能堡已对每台空调在工厂进行电气安全检测。
5 铭牌
安装和维护,请注意机器背部铭牌标注的详细技术信息。
6 安全
由百能堡生产的机柜空调是专为机柜散热(
IP54
)而设计的。
该设备只适合在固定地点平稳运行。
该机柜空调只可用于所附说明书规定的环境条件。该机柜空
调在很大程度上免维护(见第
12
)
任何其他使用范围被视为非授权使用
,
并将不作保修承诺。
电气设备应定期检查。任何异常如连接松脱或烧焦的电缆必
须被立即修复。
只有专业技术人员才能对热交换系统和电气部件进行操作。
请务必遵守相应的安全和环保法规。
请在安装机组前完整仔细阅读此手册。
本手册构成标准供货不可分割的一部分,
必须保存至机组报废为止

3 685408014B
危险!
任何清洁或维护操作之前,需切断机柜空调电源。
只有原厂备件可以使用。
7 功能
7.1 配置与功能
设备配置:
1
)
高品质关键零部件
2
)
压缩机保护装置
3
)
智能控制系统
4
)
冷凝水蒸发器
(可选)
5
)
2~400V
交流供电(可选)
设备功能
:
1
)
+15
℃
~+55
℃外部环境温度
2
)
内部控制温度 +
25
℃
~+45
℃
3
)
上电自检和运行中实时自检
4
)
冷凝水蒸发器(可选)
5
)
IP54/IP34
防护
6
)
2~ 400V
交流供电(可选)
注意:
机柜空调的具体功能见随机附带的技术规格书。
7.2 工作原理
1
压缩机
2
换热器(冷凝器)
3
截流装置
4
换热器(蒸发器)
5
风机,外循环
6
风机,内循环
7
带温度传感器的电子控制系统
压缩机(
1
)将制冷剂压缩到高压。在这个过程中温度升高。
冷凝器(
2
)中,热量散失到周围环境空气中,制冷剂变成
液体。冷凝器风扇(
5
)吸入并使空气通过冷凝器,然后
排放出去。
在截流装置(
3
)中,冷却液的压力下降。在蒸发器(
4
)中,
冷却剂吸收机柜内空气中的热量并蒸发。因此,来自机柜
中的空气被冷却下来;同时机柜内的空气被除湿。蒸发
器风扇(
6
)吸出机柜内的空气并迫使其通过蒸发器,冷却
空气吹回到机柜内。
机柜空调是由电子系统控制的。温度传感器(
7
)记录了机
柜内的空气温度。
所使用制冷剂不损害臭氧层,而且不可燃。
7.3 冷凝物
在蒸发器上发生的冷却过程中,空气中的水分被凝聚成冷凝
水。为了避免对电控柜及本制冷系统发生任何损害,必须排
出冷凝水。
冷凝水排放方式如下:
•带冷凝水蒸发器(可选)的制冷设备在正常情况下,可以
蒸发掉水分。但为防止蒸发器故障后产生的冷凝水溢流,请
连接冷凝水管路
,
然后再通过水管排出。
始终确保冷凝水正确地排出。
在特定情况下有可能会发生凝结水过量,例如,机柜不密
封或机柜内部温度经常低于露点温度。
注意:
在正常运行过程中发生冷凝水过量
,
请检查机柜的密
封。
我们建议安装一个门接触开关,当机柜门被打开时
,
机
柜空调将自动关闭
,
以防止过度冷凝水。
8 安装
8.1 概述
•
正确选择机柜空调在机柜上的安装位置
,
保证良好的通风。
•
机柜空调之间或是机柜空调和墙壁的距离必须保证至少
200
毫米。
•在机柜内部,空调的电器连接端子处需预留至少
40mm
空间
.
在机柜内部,电气元件不得阻碍空气循环。
•
机柜空调在安装时,机柜空调的电源必须断开!
•
安装现场必须受到保护,免遭污染。
注意:
如果机柜空调是装在机柜门上,必须检查门的铰链能够
支持机柜空调的重量或当门被打开机柜时,不会翻倒。
注意:
金属碎屑可能损坏机柜。
如果在安装现场开安装孔,确保使用保护罩
,
以免切屑
进入机柜,损坏电气元件。
提示
为方便机柜空调安装,
M8
的吊环可以旋入机柜空调顶部固
定,方便吊装,简单
―
一人安装
‖
就能实现。
8.2 安装工作
机柜安装面要开好空气通风口和螺栓安装固定孔,尺寸根据
随机组所附图纸。所附图纸同时说明了电气连接接口位置和
通风口位置。
1)
如机柜未预留机柜空调的开口,在机柜上切出开口(尺寸
见随机组所附图纸),然后去除剪边毛刺。
2)
取出附件包内密封条(标号
8
,
9
或
10,11,12
)贴在门板外侧
(如图)。先将密封条
8
或
11
上的孔与门板圆孔同心后再

685408014B4
按压在门板上,然后将密封条
9
或
10
或
12
外边线与
8
或
11
外边
线对齐后贴在门板上。
3)
在机柜内侧,取出附件包内的螺栓、平垫片、弹垫、螺母
及螺栓(标号
3,4,5,6,7
)将空调锁紧。
4)
将出水管通过机柜空调底板,使冷凝水能自由流下,并将
水管切至所需长度。
1
机柜空调组
5
弹簧垫片
2
机柜侧板或机柜门
6
螺母
3
牙棒
7
螺栓
4
平垫片
8-12
密封条
5
)如果机柜空调在安装时拆下外壳顶部的
M8
螺母,需将其
安装好。
6)
将电线按照接线图(见机柜空调背部)连接到连接头(附
件包中),并连接到机柜空调。
-
导线尺寸:
1.0 –2.5
平方毫米或
AWG18 - AWG14
(在电缆的大小选择,应参照相关法规要求!)
7)
将机柜空调插上电源(见
8.3
)
不同机器可能安装方式不同,请参考随机资料。
8.3 电气连接
注意:
•
机柜空调应当经由断路器连接到电源(请选择合适的断
路器),断开断路装置时
,
其触点间隙应不少于
3
毫米。
•
电源线上不可以串接温度传感器。
•
电源线上需要串接铭牌注明的保险丝
,
作为线路保护。
•
电源连接和维修,如果适用,只能由授权的经过培训的电
工来进行。
电源连接:
电源电压和频率必须符合铭牌标示值。
注意:
如果电压过高可能会导致器件损坏。
一般空调的额定电压
230V
或
400V
。
门触点:
·
为了避免任何破坏性的影响,建议使用一根带护线套的双
绞线电缆。
警告
无需另接外部电源。
如果门触点开关未被使用,需将其短接。
故障指示
对于故障信号指示有
1
对连接触点可使用
(
见技术附页线路
图)
故障信号线安装不受到任何特殊要求限制。
警告
故障指示连接最大容量为:
230V,1A
9 运行条件
•
电压范围为额定电压的
± 10
%以内。
•
电源频率为额定频率的
± 3Hz
以内。
•
环境温度必须低于
55
℃。
•
使用本机时注意使热交换量适合实际的需求。
•
只使用原装备件。
10 投入使用和功能
•
机柜空调包含的功能及可选项见章节
7.
10.1 概述
机柜空调配有温度控制系统。机柜内部温度通过温度传感器
来测量。通过操作显示器可以设定不同的机柜内温度(见附
表)。

5 685408014B
机柜空调具有上电检测、运行时实时监测功能。上电检测过
程中如果有故障,空调会发出相应的报警,这使得在进入工
作模式之前更方便的排查设备故障。
警告
机柜空调只能在装有前盖的情况下运行,否则会因散
热不良造成机柜空调被损坏。
10.2 操作显示器
机柜空调装有操作显示器。上电后操作显示器显示
0.0
℃
,3S
后显示柜内实时温度,表明机组在正常操作模式。如果发生
故障或有报警输出时,操作显示器显示报警代码,警报灯点
亮并伴随报警声,这使诊断机柜空调故障更容易(见章节
14
)。
10.3 启动测试模式
通电前,若门触点断开,则机柜空调不启动,直到
门触点闭
合后,机柜空调进入自测试模式
,
自测试模式将不受外部环境
影响。机柜空调运行启动模式持续
30
秒
,
之后是测试模式持
续
110
秒。测试模式时,有故障设备继续运行,直到测试模
式结束,产生相应的报警代码,如有故障则需解除故障后进
入正常工作模式,如无故障,直接进入正常工作模式。
10.4 机组特性
模式
时间曲线
特征
启动模式
t=0s-3s
t=3s-30s
无功能,操作显示
器显示“
0.0
℃”
显示内部温度
测试模式
t=30s-40s
t=40s-50s
t=50s-80s
t=80s-140s
内风机运行
外风机运行
内风机停止
压缩机运行
外风机停止
内风机、外风机、
压缩机一起运行
10.5 门触点
确保安全门限位开关应连接到指定端口(见机壳上线路图或
附件)当打开机柜门时门触开关即被断开,机柜空调所有马
达延时依次关闭,之后产生报警。
10.6 设备故障
机柜空调故障触点
X54—1,2
脚为常闭触点,上电后无故障为
闭合,有故障时将引起故障触点断开并显示告警代码
(
见第
14)
。
10.7 自检功能
机柜空调具有开机自检和运行中实时自检功能。
开机自检即启动测试模式(见
10.3
、
10.4
)。
实时自检允许设备在正常运转中实时监测是否有异常发生,
并及时上报。
10.8 设置的可能性
机柜空调可通过操作显示器来选择柜内不同设定温度以及
参数。(见第
11
节)
注意:
机柜空调设定参数的改变需由授权的人来完成!
11 参数查看与设置
机柜空调可以通过操作显示器对参数进行监控设置。
•
机柜空调电子控制系统包括主控制系统、操作显示系统。
面板上的指示灯从左到右排列的功能含义如下表:
1.
参数查看
主界面下,按“
Select
”键
3S
,进入界面“
SEE
”,再按
“
Select
”键确认进入,按
“▲”或“▼”键可循环选择柜
内回风温度“
Pb1
”、空调启动温度“
t1
”、门禁开关状态
“
dor
”、内风机运行状态“
IFR
”、外风机运行状态“
EFR
”、
压缩机运行状态“
Con
”、报警输出状态“
ALr
”,在任意一
个参数代码界面按“
Select
”键,显示相应参数的参数值,
按“
Mode
”键返回上层菜单或者静置
5min
自动返回主界面。
具体代码意义详见(附表一)。
2.
参数设置
•
主界面下,按“
Select
”键
3S
,进入界面“
SEE
”,再按
“
Select
”键确认进入后,通过“▲”“
▼
”键选择“
t1
”,
再按“
Select
”键显示具体参数值,长按“▲”键
6S
后即
指示灯
指示灯含义
长亮
闪烁
上电自检
自检
-----
制冷
正在制冷
-----
制热
-----
-----
除湿
-----
-----
外风机
风机运转
-----
告警
告警发生
-----

685408014B6
可调整参数值的大小,调整到正确的数值后再次按
“
Select
”键确认修改,然后按“
Mode
”键返回上层菜单
或者静置
5min
自动返回主界面。如果不需要修改,直接
按“
Mode
”键返回上层菜单即可。
注意:
普通用户只使用“t1”, 即机柜内设定温度,其他
参数只供制造商使用。
注意:
任何画面下,无任何按键触发
300
秒后返回主画面。
参数修改成功后需要返回主界面,修改值才会生效。
注意:
请在规定的范围内(附表
I
)设置参数,不正确的设置将
导致机器不能正常工作!
12 清洁和维护
危险!
在任何清洁或维护操作前,请切断空调电源。
12.1
清洁
机柜空调在正确使用条件下做到了最大可能的免维护,即不
需要定期检查维护。如果有条件定期对冷凝回路进行清洗,
将提高设备的运转效率以及可靠性。
特别注意以下说明
:
•
清洗外部风道,冷凝器以及外风机。
•
用软刷或高压空气进行作业。
步骤如下:
1
)断开机柜空调电源。
2
)打开外壳。
3
)清洁风道。
4
)清洁外风机。
5
)清洁交换器。
6
)装回外壳
7
)接通电源并观察上电自检,确保设备运转正常。
注意:
防止电气元件漏电。
不要使用任何尖锐或锋利的物体。
注意:
防止热交换器损坏。
注意:
防止外罩电气连接损坏。
在拆卸外罩时,应当手动拔去外罩里面的电气连接。安
装时
,
不要忘插上该电气连接!
12.2
维护
设备出现故障后,会自动提示故障代码,主要故障代码对应
的故障原因见章节
14
。
在每一次维护后,请等待设备上电自检结束,查看自检情况,
以确保设备能够正常运转。
13 停止使用
如果机柜空调在较长时间内未被使用,请切断电源。确保未
经授权的人员不会擅自启动空调。
机柜空调需要报废处理时,需根据相关环保法规由专业人员
进行处理。(见第
4
节)

7 685408014B
14 故障排除
尽管有精心维护
,
还是有可能产生故障。机柜空调的实时自检功能能够准确的自行诊断设备故障。
如果机器发生故障,操作显示器显示相关报警代码,用户可根据下表中的报警代码查找,使得诊断更容易。
报警列表
报警代码
描述
故障排除方法
AL01
Pb1 报警
1)检查感温头 Pb1;
2)检查连接线是否损坏;
3)检查接头是否插错位。
AL02
机柜门打开
1) 检查门开关;
2)检查接线是否松动;
3)检查接线是否接错。
AL03
超温告警
1)查看是否 AL02 报警,此时设备停止工作;
2)检查内外风机是否正常工作;
3)检查压缩机是否正常工作;
4)检查冷凝器是否脏堵;
5)检查内部风口是否堵塞,风道是否顺畅;
6)检查热负荷。
警告:
非授权人员不可检修此设备。
15 保障条款
以下情况保障将失效:
·
机组的不恰当使用,不适宜的运行条件或不遵守操作指导;
·
在腐蚀或酸性空气环境下使用;
·
由脏污或脏堵的过滤垫造成的损坏;
·
非授权人员擅动温度控制回路,改动机组或更改机组序列号;
·
由运输或是事故造成的损坏;
·
由非授权组织更换部件;
为了维护您的质保权益,在退回机组时请遵守以下规定:
·
在包装中附上确切的故障描述。
·
附上发货单(百能堡发货单或发票复印件)。
·
随机将所有附件退回;使用原始包装或同规格的包装,运输时先垫付运费及足够的运输保险。
遵守章节
2
提到的运输提示。

685408014B8
附表 I
显示参数(操作显示器)
参数
描述
最小值
最大值
默认值
单位
PB1
内循环回风温度
-30
60
-
℃
*T1
启动温度
20
45
35
℃
Dor
门开关,0代表门开关断开,1代表门开关闭合
0
1
-
-
IFR
内风机,0代表停止工作,1代表正在工作
0
1
-
-
EFR
外风机,0代表停止工作,1代表正在工作
0
1
-
-
Con
压缩机,0代表停止工作,1代表正在工作
0
1
-
-
ALr
故障报警,0代表有故障输出,1代表无故障,设备正常工作
0
1
-
-
AL01
Pb1 报警,0代表有故障,1代表无故障
0
1
-
-
AL02
机柜门打开,0代表有故障,1代表无故障
0
1
-
-
AL03
超温告警,0代表有故障,1代表无故障
0
1
-
-
*
为客户可改参数。
警告:
所有未提及参数请勿擅自更改,否则设备将不能正常工作。

9 685408014B
1 Hints on the manual ............................................ 10
2 Handling .............................................................. 10
2.1 Transport
............................................................. 10
2.2 Storage
................................................................ 10
2.3 Unpacking
........................................................... 10
3 Scope of delivery and options.............................. 10
4 General Information ............................................ 10
5 Name plate .......................................................... 11
6 Safety................................................................... 11
7 Function............................................................... 11
7.1 Function and configuration................................. 11
7.2 Operating principles
............................................ 11
7.3 Condensate
......................................................... 11
8 Installations ......................................................... 12
8.1 General
............................................................... 12
8.2 Installation work
................................................. 12
8.3 Electrical connection
........................................... 13
9 Operating condition ............................................. 13
10 Putting into operation and function ................... 13
10.1 General remarks
................................................ 13
10.2 Operate the display
........................................... 14
10.3 Start-up / Test mode
.......................................... 14
10.4 Unit characteristics
........................................... 14
10.5 Door contact
..................................................... 14
10.6 Equipment fault
................................................. 14
10.7 Self-check function
............................................ 14
10.8 Setting possibilities
............................................ 14
11 Parameters View and Settings ............................14
12 Cleaning and Maintenance .................................15
12.1 Cleaning
............................................................ 15
12.2 Maintenance
..................................................... 16
13 Stopping using ....................................................16
14 Trouble shooting.................................................17
15 Warranty Conditions...........................................17
Appendix I..................................................................18

685408014B10
1Hints on the manual
This handbook contains instructions for the installation and
operation of door and side-mounted, bolt-on Cooling
Series Units provide by Pfannenberg (PCN).
Hint
The technical specifications for each machine along with
additional information on assembly, connections and
operation are contained in a separate sheet.
In this manual, safety recommendations and other
information are structured as follows:
Hazard!
If the measures described in the following are not
strictly observed there is danger to life and health.
Hazard!
If the measures described in the following are not
strictly observed there is danger to life and health
due to electrical shock.
CAUTION:
If the measures described in the following are not
strictly observed material damage may be caused.
Hint
A hint contains additional information on the action or
instruction described.
2Handling
2.1 Transport
• Lift cooling unit only by the casing or with two jack rings
(M8 jack rings is not included)
•Transport the cooling unit only in condition of usage.
•Prior to transport remove the cooling unit and pack it
separately if the complete switch cabinet is to be
transported.
Failure to observe these instructions will render the
warranty provisions null and void.
2.2 Storage
• Never expose cooling units to temperatures exceeding
+70
°
C during storage.
• Store cooling unit only in condition of usage.
Failure to observe these instructions will render the
warranty provisions null and void.
2.3 Unpacking
•During unpacking make a visual inspection of the cooling
unit to see whether any damage has occurred during
transport. Especially pay attention to loose parts, dents,
scratches, visible loss of oil etc.
Any damage must be reported immediately to the
forwarding agent (follow the instructions in "Rules for
Damage Claims"). Moreover, the latest edition of the
"Pfannenberg After Sales Service Declaration" shall
apply.
•Before disposing of packing material ensure that it does
not contain any loose components.
Danger!
Burr caused by production may be present on the metal
edges of the unit. Always wear protective gloves when
carrying out maintenance work and installation.
In case of a warranty claim exact details on the fault
(photograph, if possible) and the indication of type and
serial number of the cooling unit are required.
3 Scope of delivery and options
The Scope of delivery includes:
• Cooling unit
• Enclosed package (among other things, fastening
material, electrical plug-type connectors)
• Special accessories, if applicable
•
Technical Datasheet
•
Manual
4 General Information
• Old devices can be properly disposed of by
Pfannenberg.
They must be sent to one of our works shipment/postage
paid.
• All cooling units produced by Pfannenberg are free
from
–PCT
–Asbestos
–Formaldehyde
–Cadmium
–Substances impairing wetting.
•Every cooling unit is checked to ensure that it is tight
Read this manual completely and carefully
before installing the unit.
This manual is an integral part of the scope
of delivery and must be kept until is
Disposed.

11 685408014B
according to the provisions of 9.ProdSV (German
regulations covering accident prevention).
•PCN has to do the electrical safety testing to every
cooling before delivery.
5 Name plate
For the installation and maintenance, please notice the
details technical data on the name plate which to be find
on the back of the cooling unit casing.
6 Safety
Cooling units produced by Pfannenberg are designed
for application dissipating heat from switch cabinets (IP
54).
The cooling unit is only suitable for installing on the
stationary operation.
Only the authorized specialist can be work on the cooling
system and electrical components.
Please make sure to comply with relevant safety and
environmental regulations.
Hazard!
Cutting off cooling unit power supply before carrying
out any cleaning or maintenance operations.
Only original spare parts may be used.
7 Function
7.1 Function and configuration
Equipment configuration:
1. High quality key components
2. Protection device for the compressor
3. Intelligent control system
4. Condensate evaporator (optional)
5. 2~Phase 400Vac power supply (optional)
Equipment function:
1. General external environment temperature:
+15℃~+55℃
2. General inside control temperature: +25℃~+45℃
3. Start-up self-check and real-time self-check
4. IP54 / IP34 protection class
5. Condensate evaporator (optional)
6. 2~Phases 400Vac power supply (optional)
Caution:
Please refer to the attached technical specification for the
details function of the cooling unit.
7.2 Operating principles
The compressor (1) compresses the refrigerant until high
pressure is achieved. During this process temperature
increases. In the condenser (2) heat is dissipated to
ambient air, the coolant becoming liquid. The condenser
fan (5) of the compensate takes ambient air in through the
condenser, and then it releases the air.
In the expansion valve (3) the pressure of the coolant
drops. In the evaporator (4) the coolant absorbs heat from
the air in the switch cabinet and evaporates. Thus, the air
in the switch cabinet cools down.At the same time the air
inside the switch cabinet is being dehumidified. The
evaporator fan (6) sucks the air out of the switch cabinet
via the evaporator, the cooled air flows back to the switch
cabinet.
The cooling unit is electronically controlled. For that
purpose a temperature sensor records the temperature of
the air inside the switch cabinet (7).
The refrigerant is not detrimental to the ozonosphere; it is
hardly combustible.
7.3 Condensate
During cooling on the evaporator the moisture removed
from the air is collected as condensate. In order to avoid
any damage to the switch cabinet and the cooling unit,
the condensate must be discharged.

685408014B12
The condensate is discharged in the following way:
•In case of normal condensate drainage a reservoir
(option) collects the condensate which is then drained by
means of a hose.
Always ensure that the condensate is drained properly
(safety- drainage).
Excessive condensation can occur if, for example, the
switch cabinet is not sealed or if the internal temperature
of the switch cabinet is frequently below the dew point.
Caution
Please check the sealing of the switch cabinet, if there is
excessive condensate during the normal operation.
In order to prevent the excessive condensate so we
recommend to installed a door contact switch. It will
switch off the cooling unit when the switch cabinet door is
opened.
8 Installations
8.1 General
•In order to keep the cabinet‘s proper ventilation, it is
important to select the correct installation place for the
cooling unit.
•It must be keep the distance at 200mm at least for the
single units or the unit and the wall.
•The cooling unit‘s electrical connection terminal to be
reserved at least 40mm space and the electrical
components shall not impede air circulation in the internal
cabinet.
•It must be switch off the power supply when the cooling
unit installed.
•The site of installation must be protected against
contamination.
Caution:
If the cooling unit is mounted on an switch cabinet door, it
must be confirmed that hinges can support the additional
weight or that the switch cabinet will not topple over when
the door‟s opened.
Caution: Chips may damage the switch cabinet.
It must be use a cover sheet to void the sward enter into
the cabinet to damage the electrical components when
you are installing a hole in the installation site.
Hint
To facilitate installation with heavy units, M8 lifting eyes
can be screwed into the upper fixing on the equipment
housing. Simple‟‟ one man installation‟‟ is thereby
possible.
8.2 Installation work
The mounting surface of the switch cabinet is to be
provided with cutout(s) and holes for air ventilation
openings and for securing the unit according to the
accompanying sheet.
The drawing on the accompanying sheet also shows the
location of the electrical connections and ventilation
openings.
1) If the cabinet is not reserved for the opening hole of the
cooling unit, please cut-out on the cabinet (refer to the
drawing on accompany sheet), then remove burrs from
the cut edge.
2) Please take out sealing strips (Pos.8, 9 or 10, 11, 12)
on the outside of the cabinet, make sure the hole of
sealing strip 8 or 11 concentric with switch cabinet, the
sealing strip 9 or 10 & 12 and 8 or 11 align at outside line,
then paste sealing strip on the swith cabinet.
3) Please take out the thread rod, flat gasket, spring
washer, nut and bolt (Pos. 3, 4, 5, 6, 7) on the inside of the
cabinet and lock the cooling unit tightly.
4) Feeding the condensate run-off tube through the
opening in the base of the unit. Lay the tube with a
downward fall. Shorten as required.

13 685408014B
1 Cooling unit DTS 5 springs shim
2 switch cabinet wall or door 6 nuts
3 thread rod 7 bolts
4 flat gasket 8-12 sealing strip
5) It must fix the M8 nut when strike it on the top of
housing during installing the tooling unit.
6) Clamp the cable as shown in the connection diagram
(see back of unit) to the plug (component pack) and
connect to the unit.
-cable size: 1.0-2.5mm2or AWG18-AWG14 (in the
selection of cable size, the relevant regulations must be
observed)
7) Plugging in the power supply on the cooling unit. (see
Section 8.3)
For unit with different mounting method please refer to
technical data sheet supplied in the accessory bag with
the unit.
8.3 Electrical connection
Caution:
•The cooling unit must be connected to the mains
by means of a disconnecting device with a contact gap of
at least 3mm when switch off.
•No temperature sensor must be series-connected to the
cooling unit feed.
•The fuse as indicated on the name plate must be
series-connected as line protection.
•Power connection and repairs, if applicable, may only be
carried out by authorized trained electricians.
Power supply connection:
Both mains voltage and frequency must correspond to the
nominal values indicated on the name plate of the cooling
unit.
Attention: The cooling unit may be damaged if the
voltage is too high. It‟s nominal voltage is 230V or 400V.
Door contact:
In order to avoid any disruptive influences, it is
recommended that a sheathed cable with twisted pair
leads be used.
Caution: No external voltage may be applied.
If no door contact switch is used, the connecting contacts
are to be bridged.
Fault indication:
For connection of the fault signal line there are 1
connection contact and/or connection lines available (see
circuit diagram on the technical supplementary sheet)
The installation of the fault signal line is not subject to any
special requirement.
Caution: The contact may be loaded with
max.230V, 1A
9Operating condition
•The voltage must be within ±10%of the value indicated.
•The frequency must be within ±3Hz of the value
indicated.
•Ambient temperature must be below 55℃.
•Use the unit such that the cooling capacity suits the
actual demand.
•Use genuine spare parts only.
10 Putting into operation and function
•Please refer to section 7 for the cooling unit which
including the function and options.
10.1 General remarks
The cooling unit is provided with an electronic control
system.The cooling unit‘s internal temperature is

685408014B14
measured by temperature sensor.The cooling unit can be
set at different internal temperature through operating
console display, (See attached table) the system will
Disallowed when exceeds the limit temperature.
The cooling unit has the function of power-on self-test, the
run-time real-time monitoring. The cooling unit will
generate an alarm when there is a failure during power-on
self-test.
Caution: The cooling unit can only run in the case
of installing the front cover, otherwise it will be damaged
by poor heat dissipation.
10.2 Operate the display
The cooling unit is provided with an operation display.
―0.0℃‖ is displayed for 3s after the supply power is
switched on, then internal temperature is shown. This
indicates the unit works properly. If there is a failure or an
alarm, the operation display‘s alarm lamp will be light and
accompanied by an alarm sound, which makes it easier to
diagnose the cooling unit. (Refer to section 14)
10.3 Start-up / Test mode
The cooling unit will can‘t work If on front of get supply
power the door switch is open, The test mode is basically
activated after renewed connection of the supply voltage
and is independent of the instantaneous ambient
conditions when the door contact is closed.First of all the
unit runs though a start-up mode lasting 30 seconds
which is followed by a test mode lasting 110 seconds. The
unit will still running when there is an alarm during the test
mode. After finishing the test mode, if have alarms, show
the alarm code in the panel, must take off the alarm, it can
enter into a normal working mode if there is no failure.
10.4 Unit characteristics
Mode
Time curve
Characteristics
Start-up
mode
t=0s-3s
t=3s-30s
No function,Operation
display shows ‗‘0.0℃‘‘
Shows internal
temperature
Test mode
t=30s-40s
t=40s-50s
t=50s-80s
t=80s-140s
Internal fan start up;
External fan start up
Internal fan stop;
Compressor start up
External fan stop;
Internal fan, external
fan, compressor all
start up.
10.5 Door contact
For safety reasons, a door limit switch should be
connected to the terminals provided on the cooling unit.
(see the wiring diagram on housing cover or supplement).
With the switch in place, when enclosure door is opened
(thereby opening the switch), all of the motors are turned
off with a time lag.
10.6 Equipment fault
Failure contact X54—1,2pin is NC, it close when power
supply without alarm, a fault in the cooling unit will cause
the breaking and show the alarm code. (See Section 14).
10.7 Self-check function
The cooling unit has functions of power-on self-check, and
real-time self-check.
Power-on self-check function is power-on testing mode.
(see Sections 10.3&10.4)
Real-time self-check function allows the cooling unit
monitoring if there is an abnormal occurrence during
operation and reporting timely.
10.8 Setting possibilities
By means of operation display, different cabinet
temperature as well as parameters can be selected. (see
Section 11)
Attention: Changes to the operating parameters
of the cooling unit should only be made by authorized
personnel.
11 Parameters View and Settings
Parameters of cooling unit can be monitored and set by
operation display.
•
Cooling unit control system includes master control board,
operation panel.

15 685408014B
Operation panel
1. View Parameters
In the home page, press ‖Select‖for 3s, operation display
shows ―SEE‖, press ‖Select‖again, using ‖▲‖―▼‖, user
can select following parameters in cycle: ‖pb1‖, ‖t1‖, ‖dor‖,
―IFR‖, ―EFR‖, ―Con‖, ―ALr‖, at any parameter,
press ‖Select‖again, corresponding value will be shown,
Press ―Mode‖to go back to previous menu, or wait 5min
to go back to home page.
The codes means see (Appendix I)
2. Parameter setting
•In the
home page
, into parameters ―t1‖value, then
press ‖
▲
‖for 6S, user can
press ‖▲‖or ―▼‖to get the
desired value
,
then press ―Select‖again to confirm the
change,
Press ―Mode‖to go back to previous menu, or
wait 5min to go back to home page. If no need to
change, just press ―Mode‖to back to previous menu.
Caution:
·Normal user only can use „‟T1‟‟, it‟s Internal setting
temperature of the cabinet, other parameters only for
manufacturer using.
·After resetting, the unit must be return home page.
·On any parameter interface, press “Mode”to go back to
previous menu until home page.
·
On any interface, home page will be shown without
pressing any button for 300s.
Caution:
Please set the parameter in the specified range (Appendix
1) and incorrect setting will cause the machine to be
unable to work properly.
12 Cleaning and Maintenance
Hazard!
Please cut off the cooling unit‟s power before carrying out
any cleaning or maintenance operation.
12.1 Cleaning
The cooling unit is to achieve the maximum possible free
maintenance in the correct using condition, that is mean
no need for regular inspection and maintenance.
It will be improved the operation efficiency and reliability of
the equipment if there are conditions for the periodic
cleaning of the condensate.
Pay a special attention to the following instructions.
•Clean the pipe of the external fan, condenser and the
external fan.
•Work with a soft brush or high pressure air.
Proceed as follows:
1) Cut off the cooling unit‘s power.
2) Remove the external cover.
3) Clean the fan pipe.
4) Clean the external fan.
5) Clean the exchangers.
6) Put in back the external cover
7) Connect the power and observe the self-check function
to make sure the equipment is running properly.
Caution: Protect the electric components against
leakage
Caution: Protect the heater exchanger to
damage
Don‟t use any pointed or Sharp-edged objects.
Caution: To prevent the damage to the
electrical connection on the covering hood.
If the covering Hood is removed, the eclectic
plug-in connections on the inside must be removed
by hand.
Light
Description
Lighting
Flash
Self-check
Self-check
-----
Cold
Cooling
-----
Heat
-----
-----
Huminity
-----
-----
Fan
Running
-----
Alarm
Alarm
-----

685408014B16
12.2 Maintenance
After equipment malfunction, it will automatically prompt
the fault code, please refer to Chapter 14 of the main fault
code corresponding to the fault reason.
After each maintenance, please wait for finishing
power-on self-test, check self-checking situation, in order
to make sure the equipment can work properly.
13 Stopping using
Please disconnect the cooling unit when it is not in use for
a longer period. Ensure that non-authorize persons
cannot start the cooling unit.
When the cooling unit is no longer needed, it must be
disposed of by authorized specialist personnel in
accordance with all applicable environmental protection
regulations. (See section 4)

17 685408014B
14 Trouble shooting
In spite of careful maintenance, the equipment is likely to have a failure. Functions of real-time self-check can diagnose
the failure by equipment itself.
If a fault occurs, operation display will show the relevant alarm code, user match tech code with below list to get a shooting
easily.
Alarm codes list:
Alarm code
description
Trouble shooting method
Al01
Sensor 1 error
1) Check sensor of Pb1;
2) Check the connect wire;
3) Make sure connect correct.
Al02
Cabinet door open
1) Check door switch;
2) Make sure connect don't loose;
3) Make sure connect correct.
Al03
High temperature
1) If alarm AL02, cooling until stop work;
2) Make sure internal fan and external fan work normal;
3) Make sure compressor work normal;
4) Check condenser if it‘s dirty and blocked;
5) Check internal fan channel;
6) Check heat load.
Caution: Non-authorized personnel cannot repair the equipment.
15 Warranty Conditions
Warranty becomes null and void:
•In case of improper usage of the unit, noncompliance with operating conditions or non observance of instructions;
•If operated in rooms in which corrosives or acids are present in the atmosphere;
•In case of damage caused by contaminated or jammed air filters;
•If a non-authorize person interrupts the cooling circulation, modifies the unit or changes the serial number;
•In case of damage caused by transport or by accidents;
•For the exchange of parts by unauthorized companies;
In order to maintain your warranty rights please observe the following when returning the unit;
•Enclose an exact description of the fault in the shipping package.
•Enclose proof of delivery (delivery note or copy of invoice).
•Return the unit together with all accessories;use the original packaging or packaging of equivalent quality, send the unit
freight prepaid and covered by an adequate transport insurance. Observe the hints on transport mentioned in section 2

685408014B18
Appendix I
Shown parameters (operation display)
Parameter
Description
Min.
Max.
Default
Unit
Pb1
Air return of inner cycle
-30
60
-
℃
* T1
Internal setting temperature
20
45
35
℃
Dor
Door switch, 0 means open, 1means close
0
1
-
-
IFR
Internal fan, 0 means OFF, 1 means ON
0
1
-
-
EFR
External fan, 0 means OFF, 1 means ON
0
1
-
-
Con
Compressor, 0 means OFF, 1 means ON
0
1
-
-
ALr
Alarm, 0 means alarm output, 1 means units work normal
0
1
-
-
AL01
Sensor 1 error, 0 means alarm, 1 means normal
0
1
-
-
AL02
Cabinet door open, 0 means alarm, 1 means normal
0
1
-
-
AL03
High temperature, 0 means alarm, 1 means normal
0
1
-
-
* means the parameters can change by user.
Caution:
Please don‟t change any unmentioned parameter without authorization, otherwise the equipment will not work
properly.

19 685408014_V0.1
百能堡机电设备(苏州)有限公司
中国苏州工业园区兴浦路333号,现代工业坊5-1-D
邮编:215021
电话:+86-512-6287-1078
传真:+86-512-6287-1077
邮箱:service@pfannenberg.cn
http://www.Pfannenberg.cn
Pfannenberg (Suzhou) Pte. Ltd.
5-1-D, No.333 Xingpu Road, Modern Industrial
Park, SIP, Suzhou 215021, Jiangsu, P.R.C
Tel: +86-512-6287-1078
Fax: +86-512-6287-1077
e-mail: service@pfannenberg.cn
http: //www.pfannenberg.cn
685408014B /10-2016
Table of contents
Other Pfannenberg Cooling Box manuals