Phenix 18010-X User manual

INSTRUCTION MANUAL 27E21
SAVE THIS INSTRUCTIONS
18010-X
1. To reduce the risk of electrical shock, disconnect all power sources before servicing.
2. This product requires an unswitched AC power supply of 120-277V, 50/60Hz.
3. This product is for use with generator or inverter supplied emergency lighting operating with auto
or preset 0-10V dimming level. Make sure all connections are in accordance with the National or
Canadian Electrical code and any local regulations.
4. This product is UL Listed for factory or field installation, and use with grounded.
5. This product is suitable for use in dry or damp locations. This product is also suitable for
installation in sealed and gasketed junction box or fixtures. Do not mount in near gas, heaters,
air outlets or other hazardous location.
6. Use this product in -20°C minimum, 65°C maximum ambient temperatures (Ta).
7. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition and void warranty.
8. Do not use this product for other than intended use.
9. Installation and service should be performed by qualified service personnel.
10. This product should be mounted in locations and at heights where it will not readily be subjected
to tampering by unauthorized personnel.
WWW.PHENIXLIGHTING.COM
E308866
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
DIMMABLE EMERGENCY LIGHTING CONTROL DEVICE

INSTALLATION
WWW.PHENIXLIGHTING.COM 2/6
CAUTION: MAKE CERTAIN BOTH THE AC POWER AND EMERGENCY POWER ARE OFF UNTIL
THE INSTALLATION IS COMPLETE.
INSIDE THE JUNCTION BOX
18010-1
LED test switch
1. OPERATING SPECIFICATIONS
Set the emergency power by dipswitch A and B,
set the 0-10V dimming level by dipswitch C.
2. INSTALLING THE 18010-X
The 18010-X can be mounted inside or outside the junction box or luminaire.
3. INSTALLING THE LED TEST SWITCH (OPTIONAL)
Select a convenient location for the LED test switch so that it can be seen after installation.
Drill a 1/2"(12 mm) hole for mounting the LED test switch. Connect the wires from the LED
test switch to the 18010 according to the wiring diagram.
OUTSIDE THE JUNCTION BOX
INSIDE THE LUMINAIRE
18010-1
LED test switch
OUTSIDE THE LUMINAIRE
18010-3
Two 5/8" (15mm) holes with
conduit connector for 18010-3
Emergency Power (P)
0-10V Dimming Level (K)
B
C
1. P = A x 100 + B x 10
2. P = 1000W (A=0, B=0)
A
C
K
09
Auto
9V
1
1V
2
2V
0
9
8
7
6
5
1
2
3
4
0
9
8
7
6
5
1
2
3
4
0
9
8
7
6
5
1
2
3
4
LED test switch
18010-3

WWW.PHENIXLIGHTING.COM 3/6
WIRING
1. The 18010-X requires an unswitched AC power supply of 120-277 volt, 50/60Hz.
2. Ensure the input current of the 18010-X does not exceed 5A. The total power of 0-10V
dimmable load does not exceed 600W @120V and 1385W @277V.
3. Refer the wiring diagrams below for wiring. Consult the factory for other wiring diagram.
EMERGENCY POWER SUPPLY BY SINGLE INVERTER
GROUND INVERTER
18010-1
NEUTRAL
HOT
NEUTRAL N in
L in
L-sw
L-unsw
Dim in
Fire
LED
LED
Dim in/out
Dim out
Red(+)
White(-)
0-10 VDC
DIMMER
AC DRIVER / BALLAST
DIM OUT (+)
DIM OUT (-)
Optional 24 VDC
Fire Alarm Override
AC DRIVER / BALLAST
Optional
LED Test Switch
WALL SWITCH
HOT
120-277V AC
OUT HOT
OUT NEUTRAL
L out
N out
GROUND
GROUND INVERTER
18010-3
NEUTRAL
HOT
NEUTRAL
0-10 VDC
DIMMER
AC DRIVER / BALLAST
DIM OUT (+)
DIM OUT (-)
Optional 24 VDC
Fire Alarm Override
AC DRIVER / BALLAST
Optional
LED Test Switch
WALL SWITCH
HOT
120-277V AC
OUT HOT
OUT NEUTRAL
GROUND
YELLOW/GREEN
WHITE
WHITE/ORANGE
ORANGE
BLACK
YELLOW
GRAY
VIOLET
GRAY/WHITE
VIOLET/WHITE
BLUE
RED/WHITE (-)
RED (+)
BLUE

WWW.PHENIXLIGHTING.COM 4/6
WIRING
EMERGENCY POWER SUPPLY BY GENERATOR OR CENTRAL INVERTER
Red(+)
White(-)
0-10 VDC
DIMMER
AC DRIVER / BALLAST
DIM OUT (+)
DIM OUT (-)
Optional 24 VDC
Fire Alarm Override
AC DRIVER / BALLAST
Optional
LED Test Switch
OUT HOT
OUT NEUTRAL
GROUND
18010-1
N in
L in
L-sw
L-unsw
Dim in
Fire
LED
LED
Dim in/out
Dim out
L out
N out
UL1008
TRANSFER SWITCH
WALL SWITCH
HOT
EMERGENCY
PANEL
NEUTRAL
NEUTRAL
G
N
HOT
120-277V AC
NEUTRAL
HOT
EMERGENCY
POWER
NORMAL POWER
18010-3
Red(+)
0-10 VDC
DIMMER
AC DRIVER / BALLAST
DIM OUT (+)
DIM OUT (-)
Optional 24 VDC
Fire Alarm Override
AC DRIVER / BALLAST
Optional
LED Test Switch
OUT HOT
OUT NEUTRAL
GROUND
UL1008
TRANSFER SWITCH
WALL SWITCH
HOT
EMERGENCY
PANEL
NEUTRAL
NEUTRAL
G
N
HOT
120-277V AC
NEUTRAL
HOT
EMERGENCY
POWER
NORMAL POWER
VIOLET
GRAY/WHITE
VIOLET/WHITE
BLUE
RED/WHITE (-)
BLUE
YELLOW/GREEN
WHITE
WHITE/ORANGE
ORANGE
BLACK
YELLOW
GRAY

WWW.PHENIXLIGHTING.COM 5/6
DIMENSION
18010-3
Item No. L
mm [inch]
211 [8.31]
M (Mounting)
mm [inch]
W
mm [inch]
H
mm [inch]
162 [6.38] 30 [1.18] 22 [0.87]
18010-1
Item No. L
mm [inch]
153 [6.02]
M (Mounting)
mm [inch]
W
mm [inch]
H
mm [inch]
143 [5.63] 30 [1.18] 22 [0.87]
Mounting Hole: ø12 0 [ø0 47]. .
25 0 [0 98]. . 255 [10 04].
PUSH T O T EST
T=5 [0.20]
6 0 [0 24]. .
Dimension unit: mm [inch]
LED TEST SWITCH

WWW.PHENIXLIGHTING.COM 6/6
OPERATION / TESTING / MAINTENANCE
OPERATION
The 18010-X dimmable emergency lighting control device can work in
conjunction with both an auxiliary generator or a central inverter system
and single inverter to power existing fluorescent or LED fixtures for emergency
lighting at full or reduced illumination with designed or preset dimming level
regardless of the wall switch position or normal dim setting.
TESTING AND MAINTENANCE
1. APD (Auto Preset Dimming) technology (The dipswitch C is set to 0)
a) Initial Auto Test
When the system is connected properly and powered on after a power failure,
the 18010-X will perform an initial Auto Test:
Bypassing the wall switch and overriding the dimmer to detect the
connected dimmable load's maximum power - PMax. load, calculating the
dimming level - K (which will dim the load in emergency mode) base on the
PMax. load and the emergency power (Set by the dipswitch A and B), dimming
the load with the dimming level K to simulate emergency mode.
b) Auto adjusting
18010-X is constantly detecting the PMax. load in normal mode, the Initial Auto
Test will be restarted automatically when PMax. load increases.
2. Preset dimming (The dipswitch C is set to 1-9)
The dimming level K is preset to 1-9V.
MANUAL TEST (Optional)
- Press the LED test switch (LTS) one time to simulate emergency mode.
- Press the LTS 2 times continuously within 3 seconds to restart the Initial Auto
Test.
LED TEST SWITCH (LTS) CONDITIONS
- LTS On: Normal Condition
- LTS Off: Power Failure
- LTS Gradual Change: In Testing Mode