PHNIX PCF-2.2BD User manual

SWIMMING POOL DEHUMIDIFIER
Installation & Operation Manual

CONTENT
1
2
2
2
2
3
4
4
5
6
7
8
10
11
12
6
7
1. Preface
2.
2.1 Marks
2.2 Icons
2.3 Warnings
2.4 Attention
3. Specifications
3.1 Parameters
3.2 Performance Curve
3.3 Dimensions
3.4 Working Principle
3.5 Product Features
3.6 Hygrostat Control
4. Installation
4.1 Installation Precautions
4.2 Positioning
4.3 Minimum Installation Distances
4.4 Drainage
5.Operation and Usage
5.1.The wire controller operation interface
5.2. Function of wire controller
5.3. Controller interface diagram and definition
6.Maintenance
6.1 Maintenance
6.2 Troubleshootings
Installation Precautions
8
8
11
8
15
16
16
17

CONTENT
1
2
2
2
2
3
4
4
5
6
7
8
10
11
12
6
7
1. Preface
2.
2.1 Marks
2.2 Icons
2.3 Warnings
2.4 Attention
3. Specifications
3.1 Parameters
3.2 Performance Curve
3.3 Dimensions
3.4 Working Principle
3.5 Product Features
3.6 Hygrostat Control
4. Installation
4.1 Installation Precautions
4.2 Positioning
4.3 Minimum Installation Distances
4.4 Drainage
5.Operation and Usage
5.1.The wire controller operation interface
5.2. Function of wire controller
5.3. Controller interface diagram and definition
6.Maintenance
6.1 Maintenance
6.2 Troubleshootings
Installation Precautions
8
8
11
8
15
16
16
17

2
Mark Meaning
A wrong operation may lead to death or heavy injury on people.
A wrong operation may lead to harm to people or loss of property.
WARNING
ATTENTION
Entrust a specialized personnel for installation. Wrong installation
may cause leakage, personnel electric shock or fires.
Confirm whether wether the unit is with correct earthing. Wrong
connection may cause personnel shock.
INSTALLATION
PROFESSIONAL
INSTALLER IS REQUIRED
EARTHING
IS REQUIRED
Icon Meaning
Prohibition. What is prohibited will be nearby this icon.
Compulsory implement. The listed actions need to be taken.
Attention(include warnings)
Please pay attention to what is indicated.
Do not put fingers or others into the fan or evaporator of the unit,
otherwise harm may be occurred.
OPERATION
PROHIBITION
SHUT OFF
THE POWER
When the unit needs to be moved or installed again, please entrust
dealer or qualified person to carry it out. Improper installation may lead to
water leakage, electrical shock, injury or fire.
It is prohibited to repair the unit by the user himself, otherwise electrical
shock or fire may occur.
When the unit needs to be repaired, please entrust dealer or qualified
person to carry it out. Improper movement or repair on the unit may lead to
water leakage, electrical shock, injury or fire.
MOVE AND REPAIR
ENTRUST
ENTRUST
PROHIBIT
2.1 Marks
2.2 Icons
2.3 nWar ings
When there is something wrong or strange smell from the unit, please cut
off the power to the unit immediately.
2. Installation Precautions
1. Preface
1
Fig.1
Main unit Wall suspension bar Manual
Thank you for choosing Swimming Pool Dehumidifier for controlling the climate in you pool
area. This product strictly complies with design and production standards to provide perfect
performance, high reliability and good adaptability for you.
Read the entire manual before the initial start-up of the unit. It is important to know the correct
operating procedures for the unit and all safety precautions to prevent the possibility of
property damage and/or personal injury. Do not modify or intervene on the unit by yourself
only as this could create dangerous situations and the manufacturer will not be responsible
for any damage caused.
This instruction must be kept carefully and must always accompany the appliance. If it is
lost or damaged, please contact the local technical service center.
1.1 Fail to comply with these recommendations will invalidate the warranty.
●This unit must be installed by an authorized installer.
●All repair or maintenance interventions must be performed by the technical service
department or by professionally qualified personnel.
●All repair or maintenance interventions must be performed in the specified period and
times.
●Use the spare parts ONLY provided by the manufacturer.
1.2 In case of system leakage, disconnect the power to the unit and call the technical service
department or other professionally qualified personnel as soon as possible, and do not
intervene personally on the appliance.
If the unit is not used for a long time, you should disconnect the power to the unit.
1.3 Packing List (Fig.1)
Expansion bolts

2
Mark Meaning
A wrong operation may lead to death or heavy injury on people.
A wrong operation may lead to harm to people or loss of property.
WARNING
ATTENTION
Entrust a specialized personnel for installation. Wrong installation
may cause leakage, personnel electric shock or fires.
Confirm whether wether the unit is with correct earthing. Wrong
connection may cause personnel shock.
INSTALLATION
PROFESSIONAL
INSTALLER IS REQUIRED
EARTHING
IS REQUIRED
Icon Meaning
Prohibition. What is prohibited will be nearby this icon.
Compulsory implement. The listed actions need to be taken.
Attention(include warnings)
Please pay attention to what is indicated.
Do not put fingers or others into the fan or evaporator of the unit,
otherwise harm may be occurred.
OPERATION
PROHIBITION
SHUT OFF
THE POWER
When the unit needs to be moved or installed again, please entrust
dealer or qualified person to carry it out. Improper installation may lead to
water leakage, electrical shock, injury or fire.
It is prohibited to repair the unit by the user himself, otherwise electrical
shock or fire may occur.
When the unit needs to be repaired, please entrust dealer or qualified
person to carry it out. Improper movement or repair on the unit may lead to
water leakage, electrical shock, injury or fire.
MOVE AND REPAIR
ENTRUST
ENTRUST
PROHIBIT
2.1 Marks
2.2 Icons
2.3 nWar ings
When there is something wrong or strange smell from the unit, please cut
off the power to the unit immediately.
2. Installation Precautions
1. Preface
1
Fig.1
Main unit Wall suspension bar Manual
Thank you for choosing Swimming Pool Dehumidifier for controlling the climate in you pool
area. This product strictly complies with design and production standards to provide perfect
performance, high reliability and good adaptability for you.
Read the entire manual before the initial start-up of the unit. It is important to know the correct
operating procedures for the unit and all safety precautions to prevent the possibility of
property damage and/or personal injury. Do not modify or intervene on the unit by yourself
only as this could create dangerous situations and the manufacturer will not be responsible
for any damage caused.
This instruction must be kept carefully and must always accompany the appliance. If it is
lost or damaged, please contact the local technical service center.
1.1 Fail to comply with these recommendations will invalidate the warranty.
●This unit must be installed by an authorized installer.
●All repair or maintenance interventions must be performed by the technical service
department or by professionally qualified personnel.
●All repair or maintenance interventions must be performed in the specified period and
times.
●Use the spare parts ONLY provided by the manufacturer.
1.2 In case of system leakage, disconnect the power to the unit and call the technical service
department or other professionally qualified personnel as soon as possible, and do not
intervene personally on the appliance.
If the unit is not used for a long time, you should disconnect the power to the unit.
1.3 Packing List (Fig.1)
Expansion bolts

3.1 Parameters
Swimming Pool Dehumidifier
3. Specifications
4
Test condition: Ambient temperature: 30℃,Relative humidity: 80%.
Unit
L/h
L
2
m
dB(A)
/
kW
A
kW
A
%RH
℃
mm
kg
/
mm
PCF-2.2BD
2.2
53
42
47
0.93
4.1
1.02
4.3
40~90
PCF-3.0BD
3.0
72
60
48
1.33
6.1
1.55
7.14
40 90~
220-240V~/50Hz
10~36
See nameplate/ package label
R410A
See 3.3
Model
Rated Capaclty
Dihumidification capacity perday
Max pool area
Nolse Level
Rated Voltage/Freq
Rated Power Input
Rated Running Current
Max.Power Input
Max.Running Current
Relative Humidity
Temperature
Dimensions(L/W/H)
Net Weight
Refrigerant
Condensation Pipe Diameter 16
PCF-4.3BD
4.3
103
83
48
1.97
8.7
2.28
10
40 90~
1616
Operating limits: temperature 10℃~36℃
relative humidity 40%~90%
3
Remember that some fundamental safety rules should be followed when using this product:
1. This appliance is not intended for use by persons(including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety. Children should be supervised to ensure that they do not play with the appliance.
2. It is forbidden to touch the appliance with wet hands or body when barefoot.
3. It is forbidden to carry out any cleaning before having disconnected the appliances from the
electricity mains supply by turning the system master switch to OFF.
4. It is forbidden to modify the safety or adjustment devices or adjust without authorization and
indication of the manufacturer.
5. It is forbidden to pull, cut or knot the electrical cables coming out of the appliance, even if it is
disconnected from the mains supply.
6. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
7. It is forbidden to poke objects or anything else through the inlet or outlet grills.
8. It is forbidden to dispose of or leave in the reach of children the packaging materials which
could become a source of danger.
9. It is forbidden to climb onto the appliance or rest any object on it.
10. It is forbidden to touch the unit with hands directly as the external parts of the appliance can
reach temperatures of more than 70℃.
11. The appliance shall be installed in accordance with national wiring regulations.
INSTALLATION
Fix the unit
Need circuit breaker
Make sure that there is circuit breaker for the unit. Lack of
circuit breaker can lead to electrical shock or fire.
Prohibit
Please use the suitable fuse.
If copper or icon is used to replace the fuse, it will cause
failure, even fire.
主 体 的 安 装
OPERATION
Check the installation
basement
Disconnect the power
Please check the installation basement regularly to avoid
any decline or damage which may hurt people or damage
the unit.
Please disconnect the power to the unit for clean or
maintenance.
Make sure that the basement of the unit is strong enough
to avoid any decline or fall down.
Meaning
Meaning
2.4 Attention
2. Installation Precautions
Warinng:

3.1 Parameters
Swimming Pool Dehumidifier
3. Specifications
4
Test condition: Ambient temperature: 30℃,Relative humidity: 80%.
Unit
L/h
L
2
m
dB(A)
/
kW
A
kW
A
%RH
℃
mm
kg
/
mm
PCF-2.2BD
2.2
53
42
47
0.93
4.1
1.02
4.3
40~90
PCF-3.0BD
3.0
72
60
48
1.33
6.1
1.55
7.14
40 90~
220-240V~/50Hz
10~36
See nameplate/ package label
R410A
See 3.3
Model
Rated Capaclty
Dihumidification capacity perday
Max pool area
Nolse Level
Rated Voltage/Freq
Rated Power Input
Rated Running Current
Max.Power Input
Max.Running Current
Relative Humidity
Temperature
Dimensions(L/W/H)
Net Weight
Refrigerant
Condensation Pipe Diameter 16
PCF-4.3BD
4.3
103
83
48
1.97
8.7
2.28
10
40 90~
1616
Operating limits: temperature 10℃~36℃
relative humidity 40%~90%
3
Remember that some fundamental safety rules should be followed when using this product:
1. This appliance is not intended for use by persons(including children) with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety. Children should be supervised to ensure that they do not play with the appliance.
2. It is forbidden to touch the appliance with wet hands or body when barefoot.
3. It is forbidden to carry out any cleaning before having disconnected the appliances from the
electricity mains supply by turning the system master switch to OFF.
4. It is forbidden to modify the safety or adjustment devices or adjust without authorization and
indication of the manufacturer.
5. It is forbidden to pull, cut or knot the electrical cables coming out of the appliance, even if it is
disconnected from the mains supply.
6. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
7. It is forbidden to poke objects or anything else through the inlet or outlet grills.
8. It is forbidden to dispose of or leave in the reach of children the packaging materials which
could become a source of danger.
9. It is forbidden to climb onto the appliance or rest any object on it.
10. It is forbidden to touch the unit with hands directly as the external parts of the appliance can
reach temperatures of more than 70℃.
11. The appliance shall be installed in accordance with national wiring regulations.
INSTALLATION
Fix the unit
Need circuit breaker
Make sure that there is circuit breaker for the unit. Lack of
circuit breaker can lead to electrical shock or fire.
Prohibit
Please use the suitable fuse.
If copper or icon is used to replace the fuse, it will cause
failure, even fire.
主 体 的 安 装
OPERATION
Check the installation
basement
Disconnect the power
Please check the installation basement regularly to avoid
any decline or damage which may hurt people or damage
the unit.
Please disconnect the power to the unit for clean or
maintenance.
Make sure that the basement of the unit is strong enough
to avoid any decline or fall down.
Meaning
Meaning
2.4 Attention
2. Installation Precautions
Warinng:

Warm damp air
Warmer & dehumidified air
3.4 Working Principle:
6
Fig.3
The unit works by drawing moist air over a refrigerated coil with a small fan. The cold coil of
the refrigeration device condenses the water, which is removed, then the air is reheated by the
hot coil. This process works most effectively with higher ambient temperatures with a high
dew point temperature(Fig.3).
Model
PCF-2.2BD
Length: A 1295 1495
3.3 Dimensions
3.3.1 Applicable product model:PCF-2.2/3.0/4.3BD
3. Specifications
1495
Fig.2
PCF-3.0BD PCF-4.3BD
222
677
3. Specifications
5
3.2 Performance Curve
PCF-2.2BD
40
35
30
25
20
15
10
5
0
0 0.5 1.0 1.5 2.0
l/h
C
0
2.5 3.0
40
35
30
25
20
15
10
5
0
0 0.5 1.0 1.5 2.0
l / h
3.52.5 3.0
C
0
40
35
30
25
20
15
10
5
0
0 0.5 1.0 1.5 2.0 2.5 3.0 4.0
l/h
C
0
5
40%RH 60%RH 80%RH
40%RH 60%RH 80%RH
40%RH 60%RH 80%RH
PCF-3.0BD
PCF-4.3BD

Warm damp air
Warmer & dehumidified air
3.4 Working Principle:
6
Fig.3
The unit works by drawing moist air over a refrigerated coil with a small fan. The cold coil of
the refrigeration device condenses the water, which is removed, then the air is reheated by the
hot coil. This process works most effectively with higher ambient temperatures with a high
dew point temperature(Fig.3).
Model
PCF-2.2BD
Length: A 1295 1495
3.3 Dimensions
3.3.1 Applicable product model:PCF-2.2/3.0/4.3BD
3. Specifications
1495
Fig.2
PCF-3.0BD PCF-4.3BD
222
677
3. Specifications
5
3.2 Performance Curve
PCF-2.2BD
40
35
30
25
20
15
10
5
0
0 0.5 1.0 1.5 2.0
l/h
C
0
2.5 3.0
40
35
30
25
20
15
10
5
0
0 0.5 1.0 1.5 2.0
l/h
3.52.5 3.0
C
0
40
35
30
25
20
15
10
5
0
0 0.5 1.0 1.5 2.0 2.5 3.0 4.0
l/h
C
0
5
40%RH 60%RH 80%RH
40%RH 60%RH 80%RH
40%RH 60%RH 80%RH
PCF-3.0BD
PCF-4.3BD

4. Installation
8
Fig.5
4.1 Installation Precautions
4.1.1 To ensure that the installation is performed correctly and that the appliance will perform
perfectly, please carefully follow the instructions indicated in this manual. Fail to respect the
rules indicated not only can cause malfunctions of the appliance but also invalidate the
warranty, hence our company shall not respond for any damage to persons, animals or
property.
4.1.2 It is important that the electrical installation is made according to the laws in force,
respects the data indicated in the technical sheet and the unit is correctly earthed.
4.1.3 The appliance must be installed in a position that allows the routine maintenance, such
as filter cleaning.
4.2 Positioning
4.2.1 Avoid installing the unit in proximity to:
-positions subject to exposure to direct sunlight;
-sources of heat;
-in places with oil fumes
-places subject to high frequencies.
4.2.2 Make sure that:
-the wall on which the unit is to be installed is strong enough to support the weight;
-the part of the installation wall does not have pipes or electric wires passing through;
-the installation wall is perfectly flat;
-there is an area free of obstacles which could interfere with the inlet and outlet air flow;
-it is preferably that there is an outside perimeter-wall to allow the discharge of condensation
outside;
4.3 Minimum Installation Distances
4.3.1 Removing the four rubber feet of the unit are suggested if hanging it on the wall.
4.3.2 Fig. 5 indicates the minimum mounting distances between the wall-mounted swimming
pool dehumidifier and furniture in the room.
0.2m
0.5m
0.2m
0.2m
3. Specifications
3.5.1 Ultra-low noise
With the advanced air ducting technology and the super quiet cross-flow fan, the unit can
operate with ultra-low noise.
3.5.2 Ultra-thin casing
With the ultra-thin casing of 200mm, which is the result of compact design, the unit can
save more space for you when it is compared with the common dehumidifierswith the
thickness of 400mm.
3.5.3 Fashionable appearance
With noble &fashion arc frame and elegant & graceful snow white color, the unit will be
perfectly combined with your pool house.
3.5.4 Newly design controller.
With simple operating display, the newly developed controller makes the unit operation
easier and more user-friendly.
3.6.1 The dehumidifier is controlled by a built-in hygrostat set on one side of the unit and
the target RH value can be set ranges from 30% to 90%.
3.6.2 The unit will not start to dehumidify until the actual RH is beyond the setting value.
3.6.3 We recommend that an external hygrostat should be installed to ensure a constant
measure of the humidity in the pool area.
3.6.4 The location of hygrostat is as the following (Fig.4):
3.6 Hygrostat Control
3.5 Product Features
7
Built-in hygrostat
Fig.4

4. Installation
8
Fig.5
4.1 Installation Precautions
4.1.1 To ensure that the installation is performed correctly and that the appliance will perform
perfectly, please carefully follow the instructions indicated in this manual. Fail to respect the
rules indicated not only can cause malfunctions of the appliance but also invalidate the
warranty, hence our company shall not respond for any damage to persons, animals or
property.
4.1.2 It is important that the electrical installation is made according to the laws in force,
respects the data indicated in the technical sheet and the unit is correctly earthed.
4.1.3 The appliance must be installed in a position that allows the routine maintenance, such
as filter cleaning.
4.2 Positioning
4.2.1 Avoid installing the unit in proximity to:
-positions subject to exposure to direct sunlight;
-sources of heat;
-in places with oil fumes
-places subject to high frequencies.
4.2.2 Make sure that:
-the wall on which the unit is to be installed is strong enough to support the weight;
-the part of the installation wall does not have pipes or electric wires passing through;
-the installation wall is perfectly flat;
-there is an area free of obstacles which could interfere with the inlet and outlet air flow;
-it is preferably that there is an outside perimeter-wall to allow the discharge of condensation
outside;
4.3 Minimum Installation Distances
4.3.1 Removing the four rubber feet of the unit are suggested if hanging it on the wall.
4.3.2 Fig. 5 indicates the minimum mounting distances between the wall-mounted swimming
pool dehumidifier and furniture in the room.
0.2m
0.5m
0.2m
0.2m
3. Specifications
3.5.1 Ultra-low noise
With the advanced air ducting technology and the super quiet cross-flow fan, the unit can
operate with ultra-low noise.
3.5.2 Ultra-thin casing
With the ultra-thin casing of 200mm, which is the result of compact design, the unit can
save more space for you when it is compared with the common dehumidifierswith the
thickness of 400mm.
3.5.3 Fashionable appearance
With noble &fashion arc frame and elegant & graceful snow white color, the unit will be
perfectly combined with your pool house.
3.5.4 Newly design controller.
With simple operating display, the newly developed controller makes the unit operation
easier and more user-friendly.
3.6.1 The dehumidifier is controlled by a built-in hygrostat set on one side of the unit and
the target RH value can be set ranges from 30% to 90%.
3.6.2 The unit will not start to dehumidify until the actual RH is beyond the setting value.
3.6.3 We recommend that an external hygrostat should be installed to ensure a constant
measure of the humidity in the pool area.
3.6.4 The location of hygrostat is as the following (Fig.4):
3.6 Hygrostat Control
3.5 Product Features
7
Built-in hygrostat
Fig.4

Attention:
If the condensation water discharges directly into a container, the condensate outlet
should above the container to avoid immersing in the container.
Select a suitable size hose to connect to the built-in hose if it is needed(Fig.7).
4.4 Drainage
Fig.7
Condensate drainage hose
9
4.3.3 Wall mounted installation
Insert 5 expansion bolts into holes which are bored by φ10 drill and fix the wall suspension
bar horizontally(Fig.6).
Fig.6
4. Installation
Expansion bolt
Wall
Wall suspension bar
5. UsageOperation and
11
5.1.The wire controller operation interface
5.1.1 Full display interface
5.1.2 Key description
Key number Key name
Up
Down
ON/OFF
Wind speed button
Key function
Press this key to select the upward option or
increase the parameter value.
Press this key to select the downward option or
decrease the parameter value.
Press this button to turn on/off ancel the
current operation and return to the previous menu
and c
Press to set the wind speed and confirm/save
Parameter setting symbol
Main display area
Dehumidification mode
Humidity symbol
Celsius symbol
Compressor symbol
Defrost symbol Fault symbol
Lock symbol
④
③
②
①
①
②
③
④
Parameters

Attention:
If the condensation water discharges directly into a container, the condensate outlet
should above the container to avoid immersing in the container.
Select a suitable size hose to connect to the built-in hose if it is needed(Fig.7).
4.4 Drainage
Fig.7
Condensate drainage hose
9
4.3.3 Wall mounted installation
Insert 5 expansion bolts into holes which are bored by φ10 drill and fix the wall suspension
bar horizontally(Fig.6).
Fig.6
4. Installation
Expansion bolt
Wall
Wall suspension bar
5. UsageOperation and
11
5.1.The wire controller operation interface
5.1.1 Full display interface
5.1.2 Key description
Key number Key name
Up
Down
ON/OFF
Wind speed button
Key function
Press this key to select the upward option or
increase the parameter value.
Press this key to select the downward option or
decrease the parameter value.
Press this button to turn on/off ancel the
current operation and return to the previous menu
and c
Press to set the wind speed and confirm/save
Parameter setting symbol
Main display area
Dehumidification mode
Humidity symbol
Celsius symbol
Compressor symbol
Defrost symbol Fault symbol
Lock symbol
④
③
②
①
①
②
③
④
Parameters

12
5. UsageOperation and
5.2. Function of wire controller
5.2.1 ON and OFF
Off state: press the On/Off key, the unit enters the On state; key lights and display lights
are up.
On state: press the On/Off key, the unit enters the Off state; key lights and display lights
are off .
On interface
Off interface
5.2.2Target humidity setting
Press the up or down key
he humidity value flashesand t
Press the up or down key
Change the target
humidity value
Press the wind speed key or
no operation ettings will
be saved automatically in 5s
And return to the main interface
s
In the ON interface, short press the up or down key after the target humidity flashing,Press the
up or down key to change the target humidity value.
Press the switch key
13
5. UsageOperation and
In the main interface short press the wind speed button to enter the wind speed setting, wind
speed level value flashing,Short press the wind speed key, wind speed cycles between 1-3,
if no operation in 5s, settings will be saved automatically and return to the main interface.
5.2.3 wind speed setting
Press the wind speed
key to enter win
d speed setting
Press the wind speed key
to choose the wind
speed level
If no operation in 5s, settings
will be saved automatically
and return to the main
interface; or press On/Off
button to return to the main
interface with no save
To avoid any faulty operations by others, please lock the keyboard after finishing settings.
In the main interface, long press On/Off button for 5 seconds, you can lock the keyboard;
in the keyboard lock state, long press On/Off button for 5 seconds, you can unlock the
keyboard. In the lock keyboard interface you can only unlock, other operations are invalid.
5.2.4 keyboard lock function

12
5. UsageOperation and
5.2. Function of wire controller
5.2.1 ON and OFF
Off state: press the On/Off key, the unit enters the On state; key lights and display lights
are up.
On state: press the On/Off key, the unit enters the Off state; key lights and display lights
are off .
On interface
Off interface
5.2.2Target humidity setting
Press the up or down key
he humidity value flashesand t
Press the up or down key
Change the target
humidity value
Press the wind speed key or
no operation ettings will
be saved automatically in 5s
And return to the main interface
s
In the ON interface, short press the up or down key after the target humidity flashing,Press the
up or down key to change the target humidity value.
Press the switch key
13
5. UsageOperation and
In the main interface short press the wind speed button to enter the wind speed setting, wind
speed level value flashing,Short press the wind speed key, wind speed cycles between 1-3,
if no operation in 5s, settings will be saved automatically and return to the main interface.
5.2.3 wind speed setting
Press the wind speed
key to enter win
d speed setting
Press the wind speed key
to choose the wind
speed level
If no operation in 5s, settings
will be saved automatically
and return to the main
interface; or press On/Off
button to return to the main
interface with no save
To avoid any faulty operations by others, please lock the keyboard after finishing settings.
In the main interface, long press On/Off button for 5 seconds, you can lock the keyboard;
in the keyboard lock state, long press On/Off button for 5 seconds, you can unlock the
keyboard. In the lock keyboard interface you can only unlock, other operations are invalid.
5.2.4 keyboard lock function

14
5. UsageOperation and
When the unit fails, the fault code displays in the main display area, press the up or down
button, faults will display in cycle. Press the On button to return to the main interface.
5.2.5 fault interface
Press the up or
down button to
check faults
Press the
On/Off key to
return the main
interface
You could determine or remove failures according to the following malfunction table:
5.2.6 Malfunction table
Malfunction
Reason
Code Solution
High pressure protection
3 times and above P1
P2
P3
P4
P5
P6
P7
P8
E0
E8
High pressure protection
Exhaust overtemperature
Protection
Air return temperature
sensing fault
Coil temperature sensing
fault
Exhaust temperature
sensing fault
Humidity sensing fault
Fan feedback signal fault
Communication fault
Exhaust overtemperature
protection 3 times and above
High pressure switch off
3 times and above
High pressure switch off
Compressor overload
Compressor overload 3
times and above
Air return temp. Sensing
head open or short circuit
Coil temperature sensing
head open or short circuit
Exhaust temperature sensing
head open or short circuit
Humidity sensing open or
short circuit
Fan feedback signal open or
short circuit
Remote controller and main
board communication error
Check the pressure switch and the
cooling circuit
Check the pressure switch and the
cooling circuit
Check that the system compressor
operation
Check and replace the return air
temperature head
Check and replace coil temperature head
Check and replace the exhaust
temperature head
Check and replace the humidity sensor
Check the fan feedback signal
Check remote controller and main
board/wiring
Check that the system compressor
operation
P9
P0
Check and replace the ambient
sensor
Ambient temp .Sens or
failure
Ambient sensor open or
short circuit
Ambient overtemperature
or too cold protection Ambient temperature
overheat or too cold
15
TEMP1
COM
NO
COMP
N1
N2
TEMP2
EEV
COMM_3
HPS
RH_1 RH_2
OP_LED
FM_DC
5.3. Controller interface diagram and definition
The input and output interfaces of the mainboard are described below.
N1
Number Symbol
The definition of the ports
01
02
03
04
05
06
07
08
09
10
11
12
13
Power supply zero line
Compressor zero line
Power line
Compressor output port
Fan output
Wire communication
No use
High pressure protection
Electronic expansion valve
Return air temperature / coil temperature
Exhaust temperature/Ambient temperature
No use
Humidity detection
RH_2
RH_1
TEMP2
TEMP1
EEV
HPS
OP_LED
COMM_3
FM_DC
NO
COM
N2
5. UsageOperation and
CS1000

14
5. UsageOperation and
When the unit fails, the fault code displays in the main display area, press the up or down
button, faults will display in cycle. Press the On button to return to the main interface.
5.2.5 fault interface
Press the up or
down button to
check faults
Press the
On/Off key to
return the main
interface
You could determine or remove failures according to the following malfunction table:
5.2.6 Malfunction table
Malfunction
Reason
Code Solution
High pressure protection
3 times and above P1
P2
P3
P4
P5
P6
P7
P8
E0
E8
High pressure protection
Exhaust overtemperature
Protection
Air return temperature
sensing fault
Coil temperature sensing
fault
Exhaust temperature
sensing fault
Humidity sensing fault
Fan feedback signal fault
Communication fault
Exhaust overtemperature
protection 3 times and above
High pressure switch off
3 times and above
High pressure switch off
Compressor overload
Compressor overload 3
times and above
Air return temp. Sensing
head open or short circuit
Coil temperature sensing
head open or short circuit
Exhaust temperature sensing
head open or short circuit
Humidity sensing open or
short circuit
Fan feedback signal open or
short circuit
Remote controller and main
board communication error
Check the pressure switch and the
cooling circuit
Check the pressure switch and the
cooling circuit
Check that the system compressor
operation
Check and replace the return air
temperature head
Check and replace coil temperature head
Check and replace the exhaust
temperature head
Check and replace the humidity sensor
Check the fan feedback signal
Check remote controller and main
board/wiring
Check that the system compressor
operation
P9
P0
Check and replace the ambient
sensor
Ambient temp .Sens or
failure
Ambient sensor open or
short circuit
Ambient overtemperature
or too cold protection Ambient temperature
overheat or too cold
15
TEMP1
COM
NO
COMP
N1
N2
TEMP2
EEV
COMM_3
HPS
RH_1 RH_2
OP_LED
FM_DC
5.3. Controller interface diagram and definition
The input and output interfaces of the mainboard are described below.
N1
Number Symbol
The definition of the ports
01
02
03
04
05
06
07
08
09
10
11
12
13
Power supply zero line
Compressor zero line
Power line
Compressor output port
Fan output
Wire communication
No use
High pressure protection
Electronic expansion valve
Return air temperature / coil temperature
Exhaust temperature/Ambient temperature
No use
Humidity detection
RH_2
RH_1
TEMP2
TEMP1
EEV
HPS
OP_LED
COMM_3
FM_DC
NO
COM
N2
5. UsageOperation and
CS1000

Press the key of "UP" or "Down" to check that if there are more failure codes.
You can find solutions to the problems according to the codes.
Solution
Malfunction Code
P1
P2
P3
P5
P6
P7
P8
E0
Reason
Solution to failure P1/P2/P3:
1. If P1/P2/P3 appears together with other failures, please solve the others first.
2. If there is no other failures of P3~E0, and P1 & P2 still exist, please disconnect the power to
the unit and connect again after 1 hour.
3. If only P3 exists, please keep the fan running for 30min. If P3 still exist after the running,
please disconnect the power to the unit and connect again after 1 hour.
Note: Please contact with when failures can not be solved. Technical Service Assistance
6. Maintenance
6.2 Trouble shooting
17
High pressure protection
Condenser outlet
temp. overhigh
Evaporator outlet temp.
sensor failure
Humidity sensor failure
Motor feedback
signal failure
Evaporator inlet temp.
sensor failure
Condenser outlet temp.
sensor failure
High pressure protection
has appeared 3 times in
30mins.
High pressure protection
is too frequently.
Condenser coil temp.
is too high
This temp. sensor is broken
or in open/short circuit
The feedback wiring is in
bad connection.
Or fan motor is damaged.
This temp. sensor is broken
or in open/short circuit
This temp. sensor is broken
or in open/short circuit
Humidity sensor is broken
or in open/short circuit
Discharge pressure
is too high
1.Check the feedback
wiring of fan motor.
2.Or replace the fan
motor.
Check or replace
this temp. sensor
Check the below
solutions to failure
P1/P2/P3
Check or replace
this temp. sensor
Check or replace
this temp. sensor
Check or replace this
humidity sensor
16
6. Maintenance
To guarantee the unit reliable and security operation for a long time, it is suggested to maintain and clean
up the unit every six months.
. Please take the following steps to clean up the strainer regularly:
6.1 Maintenance
1)Press the two red buttons and drag it down slowly(Fig.8);
2)Seperate the return air filter screen from the units as the image shown below(Fig.9);
3)Take away the return air filter screen and flush it with water(Fig.10).
4)
.
Set the filter net and the air return grille to the original place and press the limiting pin.
(Fig.11)。
5)Clean up the unit outer with soft and damp rag(Fig.12) To protect the paint-coat of the
unit, please don’t use rough sponge or corrosive detergent to do these.
Warning:Cut off power supply before cleaning or maintaining the unit.
Fig.12
Fig.11
AIR FILTER
RED BUTTON
Fig.9
Fig.8Fig.8
Fig.10
SPRING LATCH
LIMITING PIN

Press the key of "UP" or "Down" to check that if there are more failure codes.
You can find solutions to the problems according to the codes.
Solution
Malfunction Code
P1
P2
P3
P5
P6
P7
P8
E0
Reason
Solution to failure P1/P2/P3:
1. If P1/P2/P3 appears together with other failures, please solve the others first.
2. If there is no other failures of P3~E0, and P1 & P2 still exist, please disconnect the power to
the unit and connect again after 1 hour.
3. If only P3 exists, please keep the fan running for 30min. If P3 still exist after the running,
please disconnect the power to the unit and connect again after 1 hour.
Note: Please contact with when failures can not be solved. Technical Service Assistance
6. Maintenance
6.2 Trouble shooting
17
High pressure protection
Condenser outlet
temp. overhigh
Evaporator outlet temp.
sensor failure
Humidity sensor failure
Motor feedback
signal failure
Evaporator inlet temp.
sensor failure
Condenser outlet temp.
sensor failure
High pressure protection
has appeared 3 times in
30mins.
High pressure protection
is too frequently.
Condenser coil temp.
is too high
This temp. sensor is broken
or in open/short circuit
The feedback wiring is in
bad connection.
Or fan motor is damaged.
This temp. sensor is broken
or in open/short circuit
This temp. sensor is broken
or in open/short circuit
Humidity sensor is broken
or in open/short circuit
Discharge pressure
is too high
1.Check the feedback
wiring of fan motor.
2.Or replace the fan
motor.
Check or replace
this temp. sensor
Check the below
solutions to failure
P1/P2/P3
Check or replace
this temp. sensor
Check or replace
this temp. sensor
Check or replace this
humidity sensor
16
6. Maintenance
To guarantee the unit reliable and security operation for a long time, it is suggested to maintain and clean
up the unit every six months.
. Please take the following steps to clean up the strainer regularly:
6.1 Maintenance
1)Press the two red buttons and drag it down slowly(Fig.8);
2)Seperate the return air filter screen from the units as the image shown below(Fig.9);
3)Take away the return air filter screen and flush it with water(Fig.10).
4)
.
Set the filter net and the air return grille to the original place and press the limiting pin.
(Fig.11)。
5)Clean up the unit outer with soft and damp rag(Fig.12) To protect the paint-coat of the
unit, please don’t use rough sponge or corrosive detergent to do these.
Warning:Cut off power supply before cleaning or maintaining the unit.
Fig.12
Fig.11
AIR FILTER
RED BUTTON
Fig.9
Fig.8Fig.8
Fig.10
SPRING LATCH
LIMITING PIN

Code:20170309-0001
This manual suits for next models
2
Table of contents