Phoenix Mecano IJB Series User manual

IM.IJB.X.12.2018 IECEx/ATEX Page 1
Instruction Manual for Power Distribution, Switchgear and Control
Assembly –IJB Series
All work on this Ex-equipment must be carried out only by qualified
Specialist personnel following EN/IEC 60079-14. Any subsequent
modification must be within framework of this operation manual
The operating permit expires in the event of non-compliance!

IM.IJB.X.12.2018 IECEx/ATEX Page 2
Contents
1.0 Safety Instructions ..........................................................................................................................2
1.1 Safety Notes....................................................................................................................................2
1.2 Modification and alteration............................................................................................................3
2.0 Standard Conformity …………………………….......................................................................................3
3.0 Function .........................................................................................................................................3
4.0 Technical Data................................................................................................................................4
5.0 Installation......................................................................................................................................5
5.1 Dimensional drawings....................................................................................................................5
5.2 Installation Conditions...................................................................................................................9
5.3 Mounting & operating positions....................................................................................................9
5.4 Electrical Connection...................................................................................................................10
6.0 Commissioning ............................................................................................................................11
7.0 Inspection, Maintenance, Overhaul and Repair...........................................................................11
7.1 Inspection and Maintenance .......................................................................................................11
7.2 Repair and Overhaul.....................................................................................................................11
8.0 Specific conditions of use.............................................................................................................11
9.0 Technical support…………………………………………………………………………………………………………………….11
1.0 Safety Instructions
1.1 Safety notes
The target group of these instructions is electrical operatives and instructed staff
following EN/IEC 60079-14.
Operating permit expires in event of non-compliance.
Use the devices only for their intended purpose!
We cannot be held liable for damage caused by incorrect or unauthorized
use or by non-compliance with these operating instructions.
Use the device only if it is undamaged.
Serious risk of injury!
Only original parts supplied by ROSE are permissible for spares and repair
work. Other spare parts can invalidate explosion protection.
The explosion group, temperature class and ambient temperature marked on the
enclosure must be observed!
Please look at marking on enclosure, it should be installed in zone, explosion
group, T Class & ambient temperature for which they are suitable.
We cannot be held liable for damage caused by incorrect selection.
Any unauthorized work on the device is prohibited!
Installation, maintenance, overhaul and repair may only be carried out by
appropriately authorized and trained personnel.
Repairs affecting the explosion protection must only be carried out by ROSE or a
qualified authorized person in accordance with EN/IEC 60079-19!
Do not allow combustible dust deposit to form on enclosure!
Regular cleaning of dust deposit is recommended to avoid hot surface
becoming ignition risk.

IM.IJB.X.12.2018 IECEx/ATEX Page 3
Observe the following information during installation and operation
Remove all foreign bodies (e.g. uncertified plugs for transportation) from enclosure.
Any damage may compromise the explosion protection
National and local safety regulation
National and local accident prevention regulations
National and local assembly and installation regulations
Generally recognized technical regulations
Safety notes in this instruction manual
Characteristic values and related operating conditions on the rating plates and data
plates
Additional information plates on the device
1.2 Modification and alterations
Alteration and modifications to the device are not permitted!
Do not add terminals and components without consultation to manufacture.
Do not make additional cable or conduit entries.
We shall not take any liability or warranty obligations for damage resulting from
alterations and modifications.
2.0 Standard Conformity
The equipment is tested and approved for explosion hazard area to
IEC 60079-0:2017 & EN IEC 60079-0:2018, IEC 60079-1:2014 & EN 60079-1:2014, IEC60079-
31:2013 & EN 60079-31:2014, IEC 60529:2013 & EN 60529:1992/A2:2013 standards and ATEX
Directive 2014/34/EU.
The recognized national conditions and stipulation concerning electrical equipment in hazardous
area must be considered while installing and operating explosion proof electrical equipment.
These enclosures can be used in hazardous area in Zones 1, 2, 21, 22.
They are not certified for Zone 0, 20.
3.0 Function
These enclosures are used as Power distribution, Switchgear and Control Assembly. The
protection technique allows using standard electrical products having arcing or sparking
components inside enclosure. These electrical components are mounted & wired
according to customer specification.
Use the device for its intended purpose only!
Otherwise, the manufacturer’s liability and warranty expires.
Use the device under operating conditions described in instruction manual.
The device can be used in areas subject to explosion hazards only according to this
instruction manual.
No changes to the device impairing their explosion protection are permitted.
Install the device only if is undamaged, dry and clean.

IM.IJB.X.12.2018 IECEx/ATEX Page 4
4.0 Technical Data
Manufacturer: ROSE Systemtechnik GmbH
Erbeweg 13-15, D-32457 Porta Westfalica,
GERMANY
Explosion Protection:
IECEx Gas: Ex db IIB+H2 T* Gb
Dust: Ex tb IIIC * Db
ATEX Gas: II 2 G Ex db IIB+H2 T* Gb
Dust: II 2 D Ex tb IIIC T* Db
‘* See marking
IECEx Certificate of Conformity No: IECEx DEK 18.0073X
EC Type examination Certificate No: DEK 18ATEX0117X
Electrical Data
Rated operation voltage: 1.1KV AC/DC (Declared voltage rating is nominal and item having higher
voltage rating may be populated as required in consultation with manufacturer.
TYPE NO IJB 01 IJB 02 IJB 03 IJB 04 IJB 05 IJB 06
Max rated current 125A 232A 309A 415A 520A 850A
Max conductor size 35Sqmm 95Sqmm 150Sqmm 240Sqmm 300Sqmm 500Sqmm
Max PE Conductor Size 16mm2 50mm2 70mm2 120Sqmm 150Sqmm 240Sqmm
Ambient Temperature
“-60⁰C*/ -20⁰C ≤ Ta ≤ +40⁰C…..+110⁰C
*IJB 04, IJB 05 & IJB 06 are suitable for “-20⁰C” only, other types are suitable for both “-20⁰C and 60⁰C”.
Mechanical data
Enclosure: Marine grade copper free aluminium alloy or Stainless Steel (on request)
O Ring: Silicone (Optional)
Finish: RAL 7035 for Aluminum and Natural finish for Stainless Steel
Earthing: 2Nos External and 1No Internal
Degree of protection: IP66 as per IEC 60529:2013 & EN 60529:1992+A2:2013
Installation: 4 mounting holes
Number, size & location of entries
Number, size & location of entries shall be in combination as required within max permissible
limits in Metric as per ISO 965 or NPT as per ANSI/ASME B1.20.1 specified as per table. Generally
these entries will be from sides of base. However, entries from rear of base can be provided as
required subject to
a) Total area of entries from all sides and rear shall not exceed total area of entries allowed from
all the four sides
b) All reinforcement provided in the base shall remain intact and
c) Min center to center distance shall be maintained as in case of entries from sides.

IM.IJB.X.12.2018 IECEx/ATEX Page 5
MAX PERMISSIBLE ENTRIES FROM EACH SIDE
TYPE M20 or
1/2”NPT
M25 or
3/4”NPT
M32 or 1”NPT M40 or
1.1/4”NPT
M50 or
1.1/2”NPT or
2”NPT
M63 or
2.1/2”NPT
M75 or 3”NPT
Short
side
Long
side
Short
side
Long
side
Short
side
Long
side
Short
side
Long
side
Short
side
Long
side
Short
side
Long
side
Short
side
Long
side
IJB 01 11 17 06 11 05 08 03 06 02 03 - - - -
IJB 02 14 20 09 14 06 09 05 08 03 04 - - - -
IJB 03 18 24 14 20 09 14 06 09 04 06 03 04 02 02
IJB 04 22 28 17 23 11 15 08 11 05 07 04 05 02 02
IJB 05 26 34 21 27 14 18 09 12 06 08 04 06 03 04
IJB 06 34 40 27 33 18 23 12 15 08 10 06 07 04 05
Marking
TYPE
NO[4]
T Class[1]
T6
T5
T4
Min
Ambient
Temp
[3]
Dust Temp
Marking[2]
T80⁰C
T95⁰C
T130⁰C
Max ambient
temp[3]
+40⁰C
+50⁰C
+60⁰C
+40⁰C
+50⁰C
+55⁰C
+60⁰C
+75⁰C
+40⁰C
+50⁰C
+60⁰C
IJB 01
Max Watt
Dissipation[5]
108W
X
56W
X
X
108W
X
56W
X
X
X
-20⁰C
OR
-60⁰C
IJB 02
120W
X
72W
X
X
120W
X
72W
X
X
X
IJB 03
145W
X
76W
X
X
145W
X
76W
X
X
X
IJB 04
198W
150W
95W
280W
220W
X
160W
X
480W
430W
360W
-20⁰C
IJB 05
300W
200W
136W
408W
309W
X
241W
X
659W
586W
491W
IJB 06
332W
218W
155W
473W
400W
X
282W
X
894W
818W
636W
Thread type i.e. Metric or NPT and size of threaded entry shall be marked on supplied enclosure
by affixing suitable sticker.

IM.IJB.X.12.2018 IECEx/ATEX Page 6
5.0 Installation
5.1 Dimensional drawings (All dimensions in mm) – subject to alterations
Weight in Al: 12.1 Kg
Weight in Al: 15.7 Kg

IM.IJB.X.12.2018 IECEx/ATEX Page 7
Weight in Al: 22.9 Kg
Weight in Al: 29.8 Kg

IM.IJB.X.12.2018 IECEx/ATEX Page 8
Weight in Al: 49.3 Kg
Weight in Al: 74.2 Kg

IM.IJB.X.12.2018 IECEx/ATEX Page 9
5.2 Installation conditions
Built in components
The T Class is dependent on power dissipation of components, wiring and Max ambient
temperature. Refer Technical data.
Only replacement of components built inside the enclosure is permitted. Any addition or
alternation without consultation to ROSE is not permitted and may lead to ignition risk.
Replacement of Display window is not possible.
5.3 Mounting and operating position
Mounting the enclosure
Mount the enclosure by using four screws. Refer dimensional drawing for mounting holes
& mounting dimension.
Tighten the mounting screws properly.
Opening the enclosure
The enclosure lid is bolted. Use Allen key of appropriate size to open lid bolts.
Closing the enclosure
These enclosures are with/ without O ring in base. In case O ring is damaged, please
replace with supplies from ROSE and mount properly in groove.
In case O Ring is not provided, ingress protection is ensured by application of silicone
grease Anabond 662 or equivalent (e.g. Fuchs Renolit Unitemp 2).
To prevent corrosion of flange joint it is coated with silicone grease Anabond 662 or
equivalent (e.g. Fuchs Renolit Unitemp 2).
Apply a coat of silicone grease Anabond 662 or equivalent (e.g. Fuchs Renolit Unitemp 2)
on flange of lid & base before closing.
Bolt the lid of enclosure and tighten the bolts using appropriate size of Allen keys. No
bolts should be missing or loose.
Lid bolts are of SS A2.70 grade. In case of replacement, replace by same size of same or
higher strength.
Danger due to not approved cable glands & accessories!
Only certified cable glands & accessories of required Ex protection shall be
used.
Each entry shall have no more than one thread adopter. A blanking element
shall not be used with a thread adopter.
In case of non-compliance explosion protection can no longer be guaranteed.
Danger due to open holes or unused cable entries on the enclosure!
If holes or unused cable entry is left open, explosion protection can no longer
be guaranteed.
Close open holes using stopping plugs approved for required type of
protection.

IM.IJB.X.12.2018 IECEx/ATEX Page 10
5.4 Electrical Connection
Internal wiring
Incorrect wiring inside enclosure!
Strictly adhere to wire size and length for which heat loss dissipation are
taken into account for permissible wattage for a given T Class. In case of
non-compliance explosion protection can no longer be guaranteed.
Strictly adhere to the creepage and clearance required.
Use only insulated wires of suitable voltage grade.
Mounting rails or components must be loosened and fastened properly.
External Wiring
Danger due to improper cables!
The cables must comply with IEC/EN 60079-14 and relevant regulation and
must have the required cross section.
Strictly adhere to cable size and length for which heat loss dissipation are
taken into account for permissible wattage for a given T Class and ambient
temperature.
In case of non-compliance explosion protection can no longer be
guaranteed.
Danger due to improper cable glands!
The cable glands shall be appropriate to cable type and size and with
suitable approval as per IEC/EN 60079-14.
Entry threads have been marked on enclosure by sticker, please use cable
gland of appropriate size and type.
In case of non-compliance explosion protection can no longer be
guaranteed.
Protective Earth conductor connection
Always connect the protective earth (PE) conductor!
The device is equipped with one internal and two external protective
conductor connection arrangements with SS Screw, 1 No. tooth (Anti-
rotational) washer and 2 No. plain washers.
Use ring type lug of suitable material and size to be affixed between 2 plain
washers.
The PE conductor size shall be as under:
Cross sectional area of
phase Conductor S mm2
Minimum cross sectional area of the
corresponding PE conductor in mm2
S ≤ 16
S with min of 4mm2
16 < S ≤ 35
16
S>35
0.5 S

IM.IJB.X.12.2018 IECEx/ATEX Page 11
6.0 Commissioning
Check the device before putting it into service!
To ensure proper operation the equipment must be checked prior to putting it in
service.
If the enclosure is connected incorrectly, explosion protection is no longer
guaranteed!
The device must be operated only with completely closed enclosures.
Before commissioning ensure that:
No components are damaged.
The equipment has been installed according to regulations.
There are no foreign bodies inside the device.
The specified tightening torques has been observed.
7.0 Inspection, Maintenance, Repair and Overhaul
7.1 Inspection and Maintenance:
Consult the relevant national regulations (e.g. IEC/EN 60079-17) to determine the type
and extent of inspections.
Plan the intervals such that any expected defects are detected promptly.
Risk of Electric Shock!
Before opening the device, disconnect it from power supply and wait for some
time to allow internal components to cool down.
7.2 Repair and Overhaul
Damaged enclosure cannot be repaired at site. Only control accessories, electrical components,
cable glands & accessories can be changed. Please follow IEC/EN 60079-19 for repair of damaged
enclosure.
8.0 Specific conditions of use:
The ambient temperature range depends on the model (with or without
glass window), the pressure applied during the routine overpressure test
and on the glass thickness. See instruction manual point no 4.
For enclosures provided with a powder coating or liquid painting and
intended for use in Group III applications, the user shall minimize the risk
from electrostatic discharge by suitable selection and installation.
The maximum number of apertures, their maximum sizes and their
positions are specified in the instruction manual point no 4.
The flanged flame path is more than required by IEC 60079-1. Contact
ROSE for information on the dimensions of the flameproof joint.
Refer to associated certificates of Ex components/ equipment used in
assembly.
9.0 Technical Support:
Contact ROSE Systemtechnik GmbH, Erbeweg 13-15, D-32457 Porta Westfalica,
GERMANY for technical support.
This manual suits for next models
6
Table of contents
Other Phoenix Mecano Enclosure manuals
Popular Enclosure manuals by other brands

LEGRAND
LEGRAND On-Q ENP3050 installation instructions

Dell
Dell EMC PowerEdge MX7000 Installation and service manual

TOOQ
TOOQ TQE-2599RGB user manual

Unibos
Unibos BR-TB3-X4 user guide

Heckler Design
Heckler Design WindFall FRONT MOUNT Assembly & installation

AMS
AMS XE-311EX User manual & installation guide