Pittway NOTIFIER MINIGAS Guide

a Division of Pittway Corporation
Documento: M-010.1-MGAS-ENG
Edizione:01/1997 Rev.: A.1

FRONT PANEL & VISUAL INDICATIONS
GENERAL
PRE-ALARM
GENERAL
ALARM
TEST
MAINS
CONNEC.
BATTERY
TROUBLE
NOT
USED
GENERAL
PROGRAMMING
IN PROGRESS
ENABLE/PRE-ALARM/
TROUBLE
(ZONE 1 PRE-ALARM STATUS)
ZONE 2
WORKING
ZONE 1
WORKING
FAN CONTROL 1
INHIBIT
ZONES
ENABLE/ALARM/TROUBLE
(ZONE 2 ALARM STATUS) FAN CONTROL
TROUBLE
FAN CONTROL 2
INHIBIT
GENERAL
TROUBLE
ENABLE/ALARM/TROUBLE
(ZONE 1 ALARM STATUS)
FAN CONTROL
TROUBLE
ENABLE/PRE-ALARM/
TROUBLE
(ZONE 2 PRE-ALARM STATUS)
ENABLED ZONE (GREEN)
ZONE PRE-ALARM AND ALARM (RED)
ZONE TROUBLE (YELLOW)
MAINS (GREEN)
BATTERY TROUBLE (YELLOW)
GENERAL PRE-ALARM (RED)
GENERAL ALARM (RED)
GENERAL TROUBLE (YELLOW)
FAN CONTROLS IN PROGRESS (RED)
FAN CONTROLS INHIBIT (RED LED)
FAN CONTROLS TROUBLE (YELLOW LED)
TEST LED IN PROGRESS (RED)
STEADY ON LED = ENABLED ZONE
STEADY ON LED = PRE-ALARM OR ALARM ON ZONE
STEADY ON LED = TROUBLE ON ZONE (SHORT CIRCUIT OR CUT)
STEADY ON LED = MAINS CONNECTED
STEADY ON LED = DISCHARGED OR MISSING BATTERY
STEADY ON LED = PRE-ALARM IN PROGRESS
STEADY ON LED = ALARM IN PROGRESS
STEADY ON LED = TROUBLE IN PROGRESS
STEADY ON LED = CONTROL ACTIVATED
SWITCHED OFF LED = ENABLED FAN CONTROL
BLINKING LED = MANUAL INHIBIT INPUT ACTIVE
STEADY ON LED = TROUBLE ON LINE
In normal condition led blinks with a frequency of about 8 Hz, this blink allows to verify the
CPU running. Led remains steady on only during the battery test executed automatically each
minute.
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 1

GENERAL DESCRIPTION
MINIGAS is a microprocessor
g
as control panel with 2 zones. On each zone you can install up to 3 detectors.
Control panel cabinet is suitable for wall-mountin
g
.
Control panel has a 24 Vcc power supply for panel board and for connected detectors, as well as a
battery-char
g
er for stand-by accumulators.
Besides, there is an auxiliary output to provide power to external devices, for example: sirens, bells, etc.
When the internal powersupply is not enou
g
h,there’san inputfor anexternalauxiliary power supply equipped
with batteries.
On the frontal panel there is a keypad enabled by a key for the followin
g
operations:
•SIGNAL SILENCE;
•LINES RESET (ALARMS RESET);
•ENABLE - DISABLE ZONES;
•WALK-TEST and LAMP-TEST.
Besides, on the frontal panel you can find some LED’s to si
g
nal:
•enabled/disabled zone (2 LED each);
•pre-alarm zone (1 LED each);
•alarm zone (1 LED each);
•trouble zone (2 LED each);
•
g
eneral pre-alarm in pro
g
ress;
•
g
eneral alarm;
•
g
eneral trouble;
•mains supply 220 V connected;
•dischar
g
ed or not connected battery;
•test or walk-test in pro
g
ress;
•fan control in pro
g
ress;
•fan control trouble (1 LED for each zone);
•fan control inhibit (1 LED for each zone).
Inside the control panel there are 10 DIP-switches .
The only pro
g
rammin
g
s admitted are: delay time of fan controls and the
g
eneral alarm control len
g
th.
On the main Control Panel terminal block there are the followin
g
outputs:
•4 x ZONE PRE-ALARM AND ALARM TRANSISTOR OUTPUTS - Outputs O.C. 30 Vdc;
•GENERAL ALARM - Free volta
g
e 1 switch control;
•GENERAL ALARM - 1 supervised control for 24 V sirens;
•GENERAL TROUBLE - Free volta
g
e 1 switch control;
•GENERAL PRE-ALARM - Free volta
g
e 1 switch control;
•FAN CONTROL - 1;
•FAN CONTROL - 2;
•PRE-ALARM ZONE 1 - Free volta
g
e 1 switch control;
•PRE-ALARM ZONE 2 - Free volta
g
e 1 switch control.
On the main control panel terminal block there are the followin
g
inputs (all FORM C RELAY CONTACTS):
•Fan control 1 - Manual Start;
•Fan control 2 - Manual Start;
•Fan control 1 Inhibit;
•Fan control 2 Inhibit;
•Fan control Survey line 1;
•Fan control Survey line 2.
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 2 Rev. A.1 MGAS.chp

ELECTRIC FEATURES
GROUND PLANT
Ground plant has to be realised accordin
g
to CEI and ISPELS rules and it must have a resistance below 10
Ohm (to be measured at the well with disconnected mains).
CONTROL PANEL POWER SUPPLY
Control Panel receives power by mains volta
g
e, otherwise, if this one is missin
g
, it works usin
g
an internal
stand-by accumulator.
Stand-by time depends on the quantity of connected detectors (see table).
Features required for the mains supply are:
•volta
g
e = 220 VAC sin
g
le phase + 10%, -15%;
•frequency = 50 Hz +/- 0.5 Hz (+/- 1%).
N.B.: it’s important to pay attention when you have to install a control panel near electromagnetic
sources (ex.: repeaters, radio links, engines, etc.).
POWER SUPPLY
Power supply consists in two section:
1 - main card power supply, detectors and
external devices;
2 - battery-char
g
er for stand-by accumula-
tors.
N.B.: on the “+ 24 Detectors and External Devices” output are available max 24 V - 3.15 A with batteries
connected. Constant current available is 500 mA (used for detectors).
BATTERY-CHARGER SECTION
•Output volta
g
e: 27.6 V.
•Output current: 400 mA.
•Quantity of connectable batteries: 2 x 12 V - 5.7 Ah.
•Rechar
g
e time: about 20 hours (with completely dischar
g
ed battery).
•Stand-by time (with 2 char
g
ed batteries 12 V - 7 Ah) and without alarms:
- 24 hours with 1 detector;
- 18 hours with 2 detectors;
- 14 hours with 3 detectors;
- 12 hours with 4 detectors;
- 10 hours with 5 detectors;
- 8 hours with 6 detectors.
•Si
g
nals from/to power supply (not available on the terminals):
- outputs = mains trouble, dischar
g
ed battery;
- inputs = batteries test from CPU.
FUSES LIST
•On main volta
g
e 220 V = 500 mA delayed.
•On siren control = 1 A delayed.
•On battery input = 3.15 A FAST.
DETECTORS LINES POWER SUPPLY
Detectors receive power supply by control panel. Features of such power supply are the followin
g
:
•volta
g
e = nominal 24 Volt (27.6 Volt);
•current max = 500 mA;
•fuse = 3.15 A FAST.
VOLTAGE CURRENT NOTES
+ 5 V 200 mA Control panel power supply regulated
+ 24 V 0.5 A Detectors power supply regulated
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 3

DETECTORS QUANTITY TO INSTALL ON EACH LINE
The maximum number of detectors connectable to each line depends on the current sink of the detector used.
When you are installin
g
NOTIFIER detectors the maximum number is 3 for each line.
RELAIS FEATURES
DETECTORS LINES OPERATING DESCRIPTION
MINIGAS control panel allows to connect 2 zones with 3 wires for readin
g
and for powerin
g
g
as detectors.
Wirin
g
cut causes a trouble si
g
nal.
Lines are current controlled, with 4 threshoulds of interventions, as follows:
FUNCTION
General alarm
General alarm
General trouble
General pre-alarm
Fan control 1
Fan control 2
Zone 1 pre-alarm
Zone 2 pre-alarm
FEATURES
1 contact rated at 24 Vcc / 1A
Max 24 V/1 A resistives, 1 volt-free switch
Max 24 V/1 A resistives, 1 volt-free switch (norm. ener
g
.)
Max 24 V/1 A resistives, 1 volt-free switch
24 V/100 mA
24 V/100 mA
Max 24 V/1 A resistives, 1 volt-free switch
Max 24 V/1 A resistives, 1 volt-free switch
ALARM 26 mA
PRE-ALARM 18 mA
NORMAL 10 mA
CURRENT
THRESHOULD OF
INTERVENTION
CUT 0 mA
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 4 Rev. A.1 MGAS.chp

INSTALLATION
Control panel can be wall-mounted with nr. 4 self-lockin
g
dowels (brick walls) or with thread-formin
g
self-tappin
g
screw (prefabricated panels etc.).
The screws diameter must be of max 4 mm.
We su
gg
est not installin
g
the control panel near heat sources (radiators, central heatin
g
s, etc.).
Control panel can be opened unscrewin
g
the two cover fixin
g
screws.
Connectin
g
cables with detectors, auxiliary devices and the mains can be put inside the control panel via the
special holes, makin
g
run them alon
g
the cabinet lateral walls, providin
g
an opportune len
g
th.
Fixing Holes 260 mm
Batteries cable
Transformer
2 Batteries 12 V
Ground
PSU ZONES SERVICES
200 mm
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 5

MAINS AND BATTERIES CONNECTION
Mains supply cable has to pass trou
g
h the hole near the correspondin
g
terminal block placed on the
transformer.
220 VAC mains supply connection has to beexecuted via a three conductors cable (phase - neutral -
g
round).
The connection of
g
round wire comin
g
from mains has to be made on the terminal block placed on the
transformer.
Mains connection must be executed respectin
g
the followin
g
phases:
1) switch off the 220 VAC mains supply;
2) disconnect the terminal block M2 from control panel;
3) connect the mains supply cable;
4) install and connect the batteries as indicated in this manual;
5) switch on the 220 VAC mains;
6) pro
g
ram control panel via 10 DIP-SWITCH (only for the two annexed functions);
7) connect the terminal block M2;
»N.B. : as soon as you put the M2 terminal block , control panel receives power supply and automatically
itstartsworkin
g
. However, it needs to wait some hours before havin
g
a complete char
g
e of new batteries.
8) verify LED workin
g
on the panel, as indicated in para
g
raph “START-UP”;
9) close the control panel cabinet.
INTERNAL BATTERY-CHARGER
Control panel has an internal battery-char
g
er which is connected to the batteries via M2 polarised connector.
This provides a 27,6 Vcc volta
g
e and a max. current of 400 mA.
Batteries features:
•nominal volta
g
e = 12 V;
•nominal current = 7 Ah max.
DETECTORS LINES
Detectors lines have 3 wires.
ATTENTION: not used line ALWAYS has to be closed with a 2K2 5%, 1/4 W End-of-line resistor,
(supplied) on the control panel terminal block. Otherwise you’ll have a trouble signal for line-cut.
See next pa
g
e dia
g
ram for connectin
g
.
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 6 Rev. A.1 MGAS.chp

PANEL TERMINAL BLOCK WIRING
VULGAS 100 Detectors
Base B201 GAS
Manual Start
Fan Controls Inhibit Fan Controls output
General Alarm Siren
N.C.
Survey
lines
Zone 1 Zone 2
Transf. Battery Detector
WPD
O.C. output
Zone Pre-alarm
and alarm
Gen. Gen. Gen. Gen. Zone1 Zone2
Al. Al. Troub. Pre-al. Pre-al. Pre-al.
VULGAS DETECTORS
»N.B.: in the diagram are indicated all types of gas Detector commercialised by NOTIFIER.
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 7

ALARM AUXILIARY DEVICES
Control panel can drive a 24 Vcc siren via the first of the two
g
eneral alarm outputs.
Control panel constantly checks the lines inte
g
rity (a
g
ainst cuts and short circuit).
In order to obtain this function, it needs to have a siren equipped with an end-of-line resistor.
The output is protected by a 1 A fuse.
The second
g
eneral alarm output allows the user to have a volta
g
e free relais switch.
Besides, in the control panel you can find:
•1 switch control to si
g
nal GENERAL PRE-ALARM;
•1 switch control to si
g
nal the GENERAL TROUBLE;
•1 switch control to si
g
nal the ZONE 1 PRE-ALARM;
•1 switch control to si
g
nal the ZONE 2 PRE-ALARM.
All the above mentioned controls are VOLTAGE FREE and isolated from the internal circuit.
Supervised siren 24 V
12V or 24V self-powered Siren
General alarm
Supervised control
Form C contacts
Auxiliary battery or power supply
12V or 24V
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 8 Rev. A.1 MGAS.chp

FAN CONTROLS
Control panel is able to check and drive 2 fan controls, joined respectively to zone 1 and to zone 2.
Fan lines are controlled for wire-cut, therefore relais and electro-valves used must bear a 1mA current.
As far as electro-valves or relais connection is concerned, follow the supplier’s instructions. Anyway it’s better
to use a shielded cable connectin
g
the shield to the
g
round.
For each line it’s possible to connect an electro-valve or relais 24 Vcc, max 100 mA.
Fan control lines are protected by an electronic device that, in case of persistent short, it operates limitin
g
the output current.
The line-cut is si
g
naled by special LED.
As far as INHIBITS and survey line connections is concerned, it’s better they are executed with a shielded
cable and with the shield connected to the
g
round.
»ATTENTION: not used line ALWAYS has to be closed with an 2K7, 5%, 1/4 W end-of-line resistor,
on the control panel terminal block. Otherwise you’ll receice a trouble signal for line-cut .
AUXILIARY INPUTS TO FAN CONTROLS
Inside the control panel there are also the followin
g
inputs for NORMALLY CLOSED CONTACTS, connected
to the fan control mana
g
ement:
•Input for FAN CONTROL 1 INHIBIT;
•Input for FAN CONTROL 2 INHIBIT;
•N.C. Survey line for FAN CONTROL 1;
•N.C. Survey line for FAN CONTROL 2.
»ATTENTION: not used lines ALWAYS have to be connected to ground on the control panel terminal
block. Otherwise you’ll have:
- for inhibit input = control panel behaves as the fan control is INHIBIT;
- for N.C. survey line = control panel behaves as the fan control CANNOT START.
Relay
Relay
FAN CONTROL 1
FAN CONTROL 2
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 9

TERMINAL BLOCK
Transformer
+24V 0,5A Detectors
Batteries
or aux. PSU
O.C. output for zone alarm and pre-alarm in case of alarm they are negative
+24 V LINE 250 mA
Detectors lines
Zone 2Zone 1
Supervised General Alarm Volt free General Alarm
General Trouble
General Pre-alarm
Zone 1 Pre-alarm
Zone 2 Pre-alarm
Fan controls
N.C. Controls
Fan Controls Inhibit
Manual Start
Power Supply Zones Services
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 10 Rev. A.1 MGAS.chp

GENERAL ALARM CONTROL
The output is protected by a 1 A delayed fuse, which failure is si
g
naled by:
•
g
eneral trouble LED steady on;
•
g
eneral alarm LED blinkin
g
;
•buzzer sounds.
Same si
g
nal also for line-cut .
START - UP AND PROGRAMMING
After havin
g
correctly installed the control panel, as instructions, power on the mains and connect the
batteries.
Control panel starts the “LAMP TEST” for 5 seconds.
Then, it makes a detectors lines RESET that you can reco
g
nize via the ENABLE ZONE
g
reen LED blinkin
g
for 20 seconds.
After this phase, control panel is workin
g
.
Openin
g
the control panel cabinet, in the middle of the board, you can find 10 DIP-SWITCHES.
Those are factory pre-setted and user can modify ONLY DIP nr. 5, 6, 10.
FAN CONTROL STARTING TIME DELAY
Delay time to start fan controls can be pro
g
rammed usin
g
DIP SWITCH nr. 5 and 6.
Those are factory pre-setted for 20 seconds.
WAIT TIME DIP NR. 5 DIP. NR. 6
20 seconds ON ON
40 seconds ON OFF
60 seconds OFF ON
90 seconds OFF OFF
GENERAL ALARM CONTROL LENGTH
Trou
g
h the DIP-SWITCH nr. 10 it’s possible to limit the
g
eneral alarm siren len
g
th upto 15 minutes otherwise
you can let it in alarm untill the Lines Reset (factory pre-setted for infinite).
ALARM LENGTH DIP NR. 10
Infinite (until the line reset) OFF
Max 15 minutes ON
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 11

CONTROL PANEL WORKING
Control panel carryin
g
out will be the followin
g
:
•ONE ZONE PRE-ALARM;
•Zone pre-alarm control on;
•General pre-alarm control on;
•ONE ZONE ALARM;
•General alarm control on;
•Zone Fan control on (dependin
g
on delay time pro
g
rammed).
FAN CONTROL MANAUL START INPUTS
Control panel has two manual start inputs, each associated with the relatives fan controls.
Whenoneof this buttonsis released (arenormallyclosed),therelativefancontrol starts(apart fromthecontrol
panel state of the moment).
Fan controls don’t start in the followin
g
cases:
•Inhibit input = open;
•Fan control = in trouble;
•Survey fan controls line = open;
•Battery trouble detected.
FAN CONTROL INHIBIT INPUTS
Control panel has two inhibit inputs, each associated with the relatives fan controls.
These N.C. inputs inhibit the fan control on which are joined, accordin
g
to this rule:
•Input contact closed = ENABLED line;
•Input contact open = DISABLED line.
In case of inhibit, on the control panel front, you can see the correspondin
g
LED steady on .
The led survey in real time the inhibit input state.
When there’s an alarm the control panel proceeds as above mentioned, up to the end of pre-alarm time.
At this point panel verify the inhibit input state.
When the input is enabled the relative fan control starts.
Anyway, the procedure is stopped by a SIGNAL SILENCE and /or by a ZONES RESET.
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 12 Rev. A.1 MGAS.chp

FRONT PANEL OPERATIONS
KEY USE
Control panel has a key which allows to enable the keypad use.
KEYPAD
ENABLE AND DISABLE ZONES
An enabled zone allows to detect alarms and troubles.
A disabled zone only si
g
nal trouble or alarm on the relative front panel Led’s, without activate any control.
A disabled zone can be enabled (only if it isn’t in trouble) pressin
g
once the relative zone key.
An enabled zone can be disabled pressin
g
once the relative zone key.
The zone status is indicated by the relative LED.
When the zone is ENABLED the led is steady on, while when the zone is DISABLED the led is switched off.
KEY IN POSITION =
KEY IN POSITION = ENABLED KEYPAD
DISABLED KEYPAD
ENABLE ALARM
ENABLE PRE-ALARM
ENABLE PRE-ALARM
ENABLE ALARM
SIGNAL SILENCE TEST
NOT USEDRESET
Doc. M-010.1-MGAS-ENG Installation and Use Manual NOTIFIER ITALIA
MGAS.chp Rev. A.1 Page 13

SIGNAL SILENCE
In order to silence the controls or buzzer, it needs to press the SILENCE Key (see the siren crossed symbol).
ALARMS RESET
In order to reset detectors lines it needs to press the RESET key (see the arrow symbol). Before executin
g
this procedure you must operate a silence.
STARTING TEST
Pressin
g
TEST key you are able to do a lamp test in order to verify the ri
g
ht workin
g
of control panel led’s and
the buzzer.
Pressin
g
twice this key, you are able to start WALK-TEST.
The operator can try to put in alarm the detectors one at a time, and then verify that the control panel could
receive the alarm, and after 5 seconds could reset it automatically.
Pressin
g
the key for the third time you can exit from the WALK-TEST mode.
Durin
g
all the test phase, the test led, on the control panel is steady on.
PROCEDURE TO RESET FAN CONTROL
•In case of a manual start inputs restore the manual button in normal condition.
•Verify that the detectors are no more in alarm (all zone Alarm LED’s must be off).
•Press the si
g
nal silence key on the control panel keypad.
•Press the Line reset key on the control panel keypad.
•Verify as follows:
1) that there aren’t alarm or trouble si
g
nals, produced, for example by survey line or by fan controls;
2) that there aren’t inhibit si
g
nals.
NORMAL CONDITION
(NO TROUBLES
AND ALARMS)
SIGNAL SILENCE
ALARM
Management
ALARM
Management
ALARM
NOTIFIER ITALIA Installation and Use Manual Doc. M-010.1-MGAS-ENG
Page 14 Rev. A.1 MGAS.chp

Documento: M-010.1-MGAS-ENG
Edizione: 01/1997 Rev.: A.1
All specifications are subject to change without notice.
Delivery times depend on product availability.
All rights reserved.
NOTIFIER ITALIA s.r.l.
HEADQUARTERS
20097 San Donato Milanese (MI) - ITALY - Via Buozzi, 55
Tel.: 02/51897.1 (ISDN)
Fax: 02/51897.30
Table of contents