Pivot ATLAS User manual

MODULAR SWITCH MODE
BATTERY CHARGER / POWER SUPPLY
USER’S MANUAL
Important Safety,
Installation,
Operation, and
Maintenance
Instructions

ATLAS 2 of 44 User’s Manual
TABLE OF CONTENTS
TABLE OF CONTENTS..............................................................................................................................2
IMPORTANT SAFETY INSTRUCTIONS....................................................................................................3
1. INTRODUCTION.................................................................................................................................5
2. THEORY OFOPERATION................................................................................................................6
3. RECEIVING AND INSTALLING THE CHARGER.............................................................................6
4. AC INPUT ...........................................................................................................................................9
5. DC OUTPUT.......................................................................................................................................9
6. BATTERY TEMPERATURE SENSOR............................................................................................10
7. USER INTERFACE MODULE (UIM)...............................................................................................11
7.1. User Interface Module (UIM)...................................................................................................11
7.2. Digital Meter...........................................................................................................................12
8. CHARGER OPERATION.................................................................................................................13
9. LED INDICATORS...........................................................................................................................14
9.1. UIM LEDs...............................................................................................................................14
9.2. iPM Bi-Color LED ...................................................................................................................15
10. ETHERNET COMMUNICATION......................................................................................................15
10.1. Direct Local Communication .................................................................................................15
10.2. Networked Remote or Local Communication ........................................................................16
10.3. Manual (Static) Mode .............................................................................................................16
10.4. Changing the Ethernet Port Settings .....................................................................................17
10.5. Automatic (DHCP) Mode ........................................................................................................18
10.6. Restoring the Factory-Default Ethernet Port Settings............................................................19
11. WEB SERVER..................................................................................................................................19
11.1. Dashboard .............................................................................................................................19
11.2. Configuration >> System Settings.........................................................................................22
11.3. Configuration >> Charge Settings .........................................................................................22
11.4. Configuration >> Alarm Settings ...........................................................................................25
11.5. Configuration >> Date and Time Settings ..............................................................................27
11.6. Configuration >> Ethernet Settings >> Ethernet Port.............................................................27
11.7. Configuration >> Ethernet Settings >> SNMP ........................................................................28
11.8. Configuration >> User Accounts ...........................................................................................28
11.9. Configuration >> Upgrades....................................................................................................30
11.10. History ...................................................................................................................................31
11.11. Logout ...................................................................................................................................34
12. MAINTENANCE................................................................................................................................34
13. TROUBLESHOOTING AND SERVICING.......................................................................................34
13.1. ATLAS Charger Troubleshooting Chart.................................................................................35
13.2. UIM Replacement Information................................................................................................38
13.3. Service Parts List...................................................................................................................39
14. CHARGER WIRE DIAGRAMS ........................................................................................................40
15. SPECIFICATIONS............................................................................................................................42

ATLAS 3 of 44 User’s Manual
IMPORTANT SAFETY INSTRUCTIONS
1. SAVE THESE INSTRUCTIONS –This manual contains important safety and operating instructions.
Keep it in a location where it is available to anyone who may operate the charger.
2. Before using battery charger, read all instructions and cautionary markings on battery charger,
battery, and product using battery.
LOOK FOR THIS SYMBOL TO POINT OUT SAFETY PRECAUTIONS.
IT MEANS: BE ALERT—YOUR SAFETY IS INVOLVED. IF YOU DO
NOT FOLLOW THESE SAFETY INSTRUCTIONS, INJURY OR
PROPERTY DAMAGE CAN OCCUR.
3. DANGER: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, CAREFULLY READ AND
FOLLOW THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS BEFORE INSTALLING
OR OPERATING THE CHARGER.
4. INSTRUCTIONS IMPORTANTES CONCERNANT LA SECURITÉ.
5. WARNING: TO REDUCE THE RISK OF FIRE, INSTALL THIS BATTERY CHARGER ON A
SURFACE OF NON-COMBUSTIBLE MATERIAL.
6. DANGER: RISK OF ELECTRIC SHOCK. DISCONNECT CHARGER FROM BATTERY AND AC
POWER BEFORE SERVICING. TURNING OFF THE CHARGER DOES NOT REDUCE THIS RISK.
7. DANGER: RISK OF ELECTRIC SHOCK. DO NOT TOUCH UNINSULATED PORTION OF AC OR
DC CONNECTORS OR UNINSULATED BATTERY TERMINAL.
8. DANGER: RISQUE DE CHOCKS ÉLECTRIQUES. NE PAS TOUCHER LES PARTIES NON
ISOLÉES DU CONNECTEUR DE SORTI OU LES BORNES NON ISOLÉES DE L’ACCUMULATEUR.
9. CAUTION: CHARGE ONLY BATTERIES OF THE SAME TYPE, VOLTAGE, CELL NUMBER, AND
AMP-HOUR CAPACITIES AS THE CHARGER IS CONFIGURED FOR. OTHER TYPES OF
BATTERIES MAY BURST CAUSING PERSONAL INJURY AND DAMAGE. BEFORE CHARGING
ANY OTHER TYPE OF RECHARGEABLE BATTERY, CHANGE THE CHARGER
CONFIGURATION/SETTINGS AS RECOMMENDED BY THAT BATTERY MANUFACTURER.
10. ATTENTION: UTILISER POUR CHARGER UNIQUEMENT LES ACCUMULATEURS AU PLOMB À
ELECTROLYTE LIQUIDE. D’AUTRES TYPES D’ACCUMULATEURS POURRAIENT ÉCLATER ET
CAUSER DES.
11. DANGER: TO PREVENT ELECTRICAL SHOCK, DO NOT TOUCH EITHER AC OR DC
UNINSULATED PARTS. MAKE SURE ALL ELECTRICAL CONNECTORS ARE IN GOOD WORKING
CONDITION. DO NOT USE CONNECTORS THAT ARE CRACKED, CORRODED OR DO NOT MAKE
ADEQUATE ELECTRICAL CONTACT. USE OF A DAMAGED OR DEFECTIVE CONNECTOR MAY
RESULT IN A RISK OF OVERHEATING OR ELECTRIC SHOCK.
12. WARNING: HAZARD OF ELECTRIC SHOCK.

ATLAS 4 of 44 User’s Manual
13. WARNING: BATTERIES GENERATE EXPLOSIVE GASES. TO PREVENT ARCING OR
BURNING NEAR BATTERIES, DO NOT DISCONNECT DC CHARGING CORD FROM BATTERIES
WHEN THE CHARGER IS OPERATING. KEEP SPARKS, FLAME, AND SMOKING MATERIALS
AWAY FROM BATTERIES.
14. WARNING: ALWAYS SHIELD EYES WHEN WORKING NEAR BATTERIES. DO NOT PUT
WRENCHES OR OTHER METAL OBJECTS ACROSS BATTERY TERMINAL OR BATTERY TOP.
ARCING OR EXPLOSION OF THE BATTERY CAN RESULT.
15. WARNING: BATTERIES PRODUCE HYDROGEN GAS, WHICH CAN EXPLODE IF IGNITED.
NEVER SMOKE, USE AN OPEN FLAME, OR CREATE SPARKS NEAR THE BATTERY. VENTILATE
THE AREA WHEN THE BATTERY IS CHARGING IN AN ENCLOSED PLACE.
16. WARNING: BATTERIES CONTAIN CAUSTIC MATERIAL, WHICH MAY CAUSE BURNS. DO
NOT GET IN EYES, ON SKIN, OR CLOTHING. IF CONTACT WITH THE EYES OCCURS, FLUSH
IMMEDIATELY WITH CLEAN WATER FOR 15 MINUTES AND OBTAIN MEDICAL ATTENTION.
17. WARNING: DE-ENERGIZE ALL AC AND DC POWER CONNECTIONS BEFORE SERVICING
THIS UNIT. IF INJURY DOES OCCUR, APPLY STANDARD TREATMENT FOR ELECTRICAL SHOCK
AND, IF NECESSARY, CONSULT WITH A PHYSICIAN.
18. WARNING: THE CHARGER IS NOT FOR OUTDOOR USE. DO NOT EXPOSE THE CHARGER
TO RAIN OR SNOW.
19. CAUTION: DO NOT OPERATE THE CHARGER IF IT HAS RECEIVED A SHARP BLOW, BEEN
DROPPED, OR OTHERWISE DAMAGED. HAVE A QUALIFIED SERVICE TECHNICIAN EXAMINE
AND REPAIR AS NEEDED.
20. WARNING: DO NOT DISASSEMBLE THE CHARGER. HAVE THE CHARGER EXAMINED BY A
NATIONAL RAILWAY SUPPLY SERVICE AGENT. INCORRECT RE-ASSEMBLY OF THE CHARGER
MAY RESULT IN AN EXPLOSION, ELECTRIC SHOCK, OR FIRE.
21. CAUTION: MAKE SURE THE BATTERY SYSTEM HAS THE PROPERLY RATED VOLTAGE,
AMP-HOURS, AND TYPE FOR THIS CHARGING SYSTEM.
SAVE THESE INSTRUCTIONS
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.

ATLAS 5 of 44 User’s Manual
1. INTRODUCTION
The ATLAS is a modular switch mode (high frequency) battery charger / power supply platform designed for
railroad signal and communication, as well as other industrial stationary / reserve power applications.
ATLAS is convection cooled with no fans or other moving parts and designed to provide maximum reliability in
industrial environments. The modular architecture provides redundancy and maximizes uptime, and the
system controller combines the simplicity of rotary switches to adjust the float voltage with sophisticated
communication, alarming, and logging options. The universal AC input enables the charger to be used with a
wide range of AC voltages and frequencies, and the system features high energy efficiency and power factor.
As is illustrated in Figure 1-1, an ATLAS system includes a chassis. The chassis has a User Interface Module
(UIM) that serves as the system controller and user interface and an access panel for the AC input and DC
output terminals. Chassis are available with four (4) or two (2) slots for Intelligent Power Modules (iPMs).
Figure 1-1: ATLAS System Components
Both 12 Vdc, 400W, 20A and 24 Vdc, 400W, 10A iPMs are available. Figure 1-2 shows the corresponding
maximum system DC output current for a given number of iPMs. An ATLAS system can be set to charge
batteries within a voltage range of 1.00 to 20.00 volts (12 Vdc nominal system) or 10.00 to 40.00 volts (24 Vdc
nominal system) for nickel-cadmium (Ni-Cd), valve regulated lead-acid (VRLA), and flooded/vented lead-acid
batteries. The values shown throughout this manual in the instruction tables and figures are for generic use
and may be different from the actual values programmed in your unit. Customized settings are available,
contact a Lester Electrical service agent at 1-402-477-8988.

ATLAS 6 of 44 User’s Manual
Number of iPMs
Maximum System DC Output Current (A)
12 Vdc iPMs
24 Vdc iPMs
1
20
10
2
40
20
3
60
30
4
80
40
Figure 1-2: Number of iPMs and the Corresponding Maximum System DC Output Current
2. THEORY OF OPERATION
The charger has an "IE" profile which is (1) a constant-current bulk/start phase followed by (b) a constant-
voltage float phase. When the charger is first started, if the battery pack voltage is below the charger float
voltage value, it will output a constant current in the bulk phase. The constant current value is controlled by
the “Max DC Output Current” setting available via the charger web server using the Ethernet port.
When the battery pack nears the charger float voltage value, the charger will transition from the bulk phase
into the float phase. The output current will decrease in order to maintain a constant float voltage. The
charger float voltage value is controlled by either (1) the “NUMBER OF CELLS” and “VOLTS PER CELL”
rotary switches on the UIM or (2), if the “NUMBER OF CELLS” rotary switches are set to “00”, the “Number of
Cells” and “Float Voltage Per Cell” settings available via the charger web server control the float voltage value
(see Section 11.3 for valid ranges). The constant float voltage will be maintained indefinitely to keep the
battery pack fully charged.
The charger web server, which is detailed in Section 11, includes other settings, such as battery temperature
compensation, that can be adjusted per the requirements of the battery pack and overall system.
3. RECEIVING AND INSTALLING THE CHARGER
WARNING: NEVER PLACE ANYTHING ON TOP OF THE CHARGER WHILE OPERATING. DAMAGE
TO THE CHARGER OR BATTERIES COULD OCCUR.
WARNING: THE CHARGER MUST BE SET UP FOR THE PROPER USER SPECIFICATIONS BEFORE
STARTING THE INITIAL CHARGE.
WARNING: CHARGERS CAN IGNITE FLAMMABLE MATERIALS AND VAPORS. DO NOT USE NEAR
FUELS, GRAIN DUST, SOLVENTS, THINNERS, OR OTHER FLAMMABLES.
WARNING: REPLACE WORN, DAMAGED, OR CUT ELECTRICAL CORDS AND CONNECTORS
IMMEDIATELY.
Proper installation of the charger is important in order to achieve good charger performance and to prevent
damage to the charger and batteries.
When a charger is received, a check for possible in-transit damage should be made. If any damage is found,
it should be reported as a claim to the carrier.
The dimensions for the charger and mounting brackets are shown in Figure 3-1 (4-slot chassis) and Figure 3-
2 (2-slot chassis).
To permit free air flow for convention cooling, allow 2 inches (2") minimum between the charger sides and
other equipment and 4 inches (4") minimum on top of the charger. Do not mount the charger above other
heat generating equipment.
The charger can be mounted on a shelf, countertop, floor, wall, or rack. The charger case includes four (4)
cushioned feet that are designed to prevent marring of mounting surface and to absorb vibration. The
charger includes adjustable mounting brackets that provide highly flexible mounting options. See Figure 3-1
(4-slot chassis) or Figure 3-2 (2-slot chassis) for details.

ATLAS 7 of 44 User’s Manual
Wall or Shelf Mounting
The charger can be fastened to a wall for wall or shelf mounting, by attaching the mounting brackets to the
last two side mounting screw holes near the rear of the charger. Then, 1/4" bolts or lag screws can be
installed in each of the (4) key slots or by using the top and bottom 0.281 diameter round holes in the
mounting brackets (4 bolts total).
Rack Mounting
The 4-slot chassis can be mounted to a standard Electronic Industries Association (EIA) 19” (483mm) rack
system. The 2-slot can also be mounted to a standard EIA 19” rack system using an optional mounting
bracket. An industry standard 3/8" square hole rack, 12-24 UNC cage nuts, and 12-24 UNC rack screws are
recommended. A 12-24 screw should be installed through each of the 2 highest slots and 1 of the 2 lowest,
0.218" X 0.312" slots in both of the 2 mounting brackets (a total of 6 screws minimum). The 12-24 screws
should be tightened to 40 in--lb. If other sizes and/or types of fasteners are used, the quantity, location and
tightening torque should be designed as recommended by the manufacturer to be at least as strong as the
above recommendation. By adjusting the locations of the mounting brackets along the 1/2" spacing of screw
holes along the side of the charger, many different mounting configurations are possible, from flush mounted
to forward mounted.
The patterns of the mounting bracket rack mounting holes and slots are shown in Figure 3-1 (4-slot chassis).
Figure 3-1: Dimensions for 4-Slot Chassis and Mounting Brackets

ATLAS 8 of 44 User’s Manual
Figure 3-2: Dimensions for 2-Slot Chassis and Mounting Brackets

ATLAS 9 of 44 User’s Manual
4. AC INPUT
WARNING: FAILURE TO PROPERLY CONNECT THE AC VOLTAGE CONDUCTORS COULD CAUSE
SERIOUS DAMAGE TO THE CHARGER.
WARNING: DO NOT OPERATE THE CHARGER WITHOUT PROPER GROUNDING. IMPROPER
GROUNDING CAN RESULT IN THE RISK OF AN ELECTRIC SHOCK.
CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK OR FIRE, DISCONNECT AC POWER
FROM THE CHARGER BEFORE INSTALLING OR REMOVING UNIT.
WARNING: DO NOT TOUCH THE CHARGER'S TERMINALS OR AN ELECTRICAL SHOCK COULD
OCCUR. A VOLTAGE IS PRESENT ON THE DC TERMINALS EVEN AFTER THE AC IS DISCONNECTED
BECAUSE OF THE ENERGY STORED IN THE CAPACITORS.
The charger has an AC input rating of 100-240 volts, 50-200 hertz, single-phase. The charger has an AC
operating range of 90-264 volts, 45-205 hertz. Below 100 volts, the charger may reduce output power.
Use an appropriate size wire for the AC input. Quarter-inch (1/4") ring terminals are required for proper
connection to the AC input binding posts (A.A.R.) located on the front of the charger. Open the access door
cover on the front of the charger. Route the AC wires and/or conduit in accordance with the National
Electrical Code and all local codes and ordinances. Dress field installed Class 2 or Class 3 circuits at
least 1/4 inch (6.3 mm) away from power, light, or Class 1 circuits. Connect the AC input terminals on
the two right-most posts, as marked on the A.A.R. terminal board, inside of the access door. Connect the AC
ground to the terminal lug provided, as also marked on the inside of the access door. Close the access door
after tightening all of the binding post nuts.
5. DC OUTPUT
WARNING: DO NOT TOUCH THE CHARGER'S TERMINALS OR AN ELECTRICAL SHOCK COULD
OCCUR.
WARNING: BATTERIES GENERATE EXPLOSIVE GAS. CHARGE ONLY IN WELL VENTILATED
AREAS. TO PREVENT ARCING OR BURNING NEAR BATTERIES, DO NOT DISCONNECT THE DC
CHARGING CONNECTOR(S) FROM THE BATTERIES WHEN THE CHARGER IS OPERATING. IF THE
CHARGE CYCLE MUST BE INTERRUPTED, UNPLUG THE AC POWER CORD BEFORE
DISCONNECTING THE DC OUTPUT CONNECTOR(S) FROM THE BATTERIES. KEEP SPARKS, FLAME,
AND SMOKING MATERIALS AWAY FROM BATTERIES. TO REDUCE THE RISK OF FIRE, DO NOT USE
THE CHARGER NEAR FLAMMABLE MATERIALS OR VAPORS.
Use Table 5-1 to select the appropriate gauge and length DC output cable for your application. Maximum
wire gauge is 4 AWG to fit the openings for the DC wiring above the binding posts (A.A.R.). Dress field
installed Class 2 or Class 3 circuits at least 1/4 inch (6.3 mm) away from power, light, or Class 1
circuits.
Quarter-inch (1/4") ring terminals are required for proper connection to the DC output binding posts (A.A.R.)
located on the front of the charger. Open the access door cover on the front of the charger. Connect the DC
output terminals on the two left-most posts, with positive (+) on the left and negative (-) on the right, as
marked on the A.A.R. terminal board, inside of the access door. Check to make sure that the polarity of the
DC output wires are the same as those connected to the battery. The charger will not operate in a reversed
polarity condition. If the DC polarity is reversed, the main DC output fuse will protect the charger from internal
damage. Correct the reversed wires and replace the fuse. Close the access door after tightening all of the
binding post nuts.

ATLAS 10 of 44 User’s Manual
Maximum DC Cable Length per Wire Gauge
Wire Gauge
(AWG)
Rated Voltage / Chassis Size
Maximum Output
Current in Amps
Maximum Length
in Feet
12
24V / 2-slot
20
14
10
12V / 2-slot
40
10
24V / 2-slot
20
20
24V / 4-slot
40
10
8
12V / 2-slot
40
18
24V / 2-slot
20
36
24V / 4-slot
40
18
6
12V / 2-slot
40
29
24V / 2-slot
20
58
12V / 4-slot
80
15
24V / 4-slot
40
29
4
12V / 2-slot
40
46
24V / 2-slot
20
92
12V / 4-slot
80
23
24V / 4-slot
40
46
Table 5-1: Maximum DC Cable Length
6. BATTERY TEMPERATURE SENSOR
WARNING: IT IS IMPORTANT TO MOUNT THE TEMPERATURE SENSOR ON THE BATTERIES
FOR PROPER TEMPERATURE COMPENSATION. IF THIS CANNOT BE DONE, LOCATE THE SENSOR
AS LOW AS POSSIBLE IN THE BUNGALOW, ENCLOSURE, OR CABINET.
The external battery temperature sensor is an optional way of extending battery life by using temperature
compensation. One end of the temperature sensor cable has a three-pin plug that plugs into a receptacle
labeled “BATTERY TEMP SENSOR” on the UIM (see Figure 7-1). The other end of the cable has the
temperature sensor sealed in a terminal.
The terminal-type sensor should be attached to a negative (-) battery post near the center of the battery pack.
If the threaded stud is long enough above the battery jumper nut, attach the sensor with another nut. Torque
this nut to proper specifications. If the stud is too short, the nut holding the jumper wire will need to be
removed. Open or remove the load and charging circuits to the batteries. Remove the nut holding the jumper
and add the sensor, then torque the nut to the proper specifications. Then close or connect the load and
charging circuits back to the batteries.
Securely fasten the temperature sensor cable to protect the sensor from being torn from the battery.
Secure the sensor cable to a fixed object to ensure the sensor will not be pulled loose. Use a cable tie mount
on the battery or on the adjacent battery, if necessary.

ATLAS 11 of 44 User’s Manual
7. USER INTERFACE MODULE (UIM)
7.1. User Interface Module (UIM)
Below are descriptions of the user interface items found on the UIM. Figure 7-1 identifies these user interface
items.
Number of Cells Rotary Switches
Used to manually set the number of battery cells. See Section 11.3 for valid ranges. Setting to “00” enables
control via the web server.
Volts Per Cell Rotary Switches
Used to manually set the float voltage per cell. See Section 11.3 for valid ranges. Not used if t he “NUMBER
OF CELLS” rotary switches are set to “00”, which enables float voltage control via the web server.
UIM Status LED
Green LED. See the UIM LEDs table for possible states.
Alarm LED
Red LED. See the UIM LEDs table for possible states.
AC Present LED
Blue LED that is on when AC power is present.
Confirm Local Presence Button and LED
Pressing the button enables setting/alarm changes to be saved via the web server for a set amount of time.
This ensures that the changes are being made locally and provides the highest level of possible security.
Alarm Relay Terminals
Form C, dry contacts. Configurable per alarm via the web server by selecting the K1 relay in the alarm
settings menu.
Relay Terminal Remote Wiring
The terminal strip has OPEN, COMMON, and CLOSED relay contacts for remote wiring. COMMON to
CLOSED has continuity when no alarms or faults for the K1 relay are active. To insert a 28 to 12 AWG wire
striped 5 to 6mm, use a small screw driver to push the white tab at the top upwards. Insert the wire and verify
good contact. The relay contacts are rated for 1A at 30Vdc or 0.5A at 120Vac.
Battery Temperature Sensor Connector
Can be connected to a battery temperature sensor in order to temperature compensate the charge profile.
Enabled/disabled, compensation value, min compensation limit, and max compensation limit configurable via
the web server. The reference temperature for compensation is 25ºC or 77ºF.
Ethernet Connector
Provides local or remote access to the internal charger web server via a standard Internet browser. The web
server is used to check the status of the charger (DC amps, AC volts, etc), control the charger (on/off, manual
equalize, etc), configure settings/alarms, and view/download the history log. NTP time synchronization and
SNMP alarming are also supported.
Remote DC Voltage Connector
Can be wired directly to the battery pack in order to measure the voltage without any DC cable drop.
Enabled/disabled via the web server. This option allows for a more accurate float voltage at higher current
levels.
The UIM is powered by both AC and DC power so as to remain powered on when AC power is lost. This
allows all alarms and the UIM to function as desired. Removal of both the AC and DC power and then return
of either power source will allow for the UIM LED's to do a power up sequence and reboot the UIM.

ATLAS 12 of 44 User’s Manual
Figure 7-1: User Interface Items on the UIM
7.2. Digital Meter
When the multi-function digital meter option is ordered, it is mounted on the front of the charger. The meter
displays both the charger output voltage and current. The top red number displays the output voltage, which
is measured internal to the charger. Because it is measured internal to the charger, it will differ from the
voltage measured at the battery pack due to the voltage drop of the cabling between the charger and battery
pack. It will also differ from the “Battery Voltage” displayed on the web server “Dashboard” for the same
reason. The bottom green number displays the output current of the charger, so depending on the
application, the battery pack and load may share this current. Figure 7-2 illustrates the digital meter.
Figure 7-2: Optional Digital Meter

ATLAS 13 of 44 User’s Manual
8. CHARGER OPERATION
WARNING: TO REDUCE THE RISK OF AN ELECTRIC SHOCK, CONNECT ONLY TO A SINGLE-
PHASE, PROPERLY GROUNDED (3-WIRE) AC SOURCE. REFER TO GROUNDING INSTRUCTIONS.
CAUTION: MAKE SURE THE BATTERY IS A RECHARGEABLE BATTERY WITH THE PROPER
RATED VOLTAGE FOR THIS CHARGER.
DANGER: TO PREVENT ELECTRICAL SHOCK, DO NOT TOUCH UNINSULATED PARTS OF THE
CHARGER AC INPUT OR DC OUTPUT TERMINALS, AC INPUT OR DC OUTPUT WIRING, OR BATTERY
TERMINALS. MAKE SURE ALL ELECTRICAL CONNECTORS ARE IN GOOD WORKING CONDITION.
DO NOT USE CONNECTORS THAT ARE CRACKED, CORRODED, OR DO NOT MAKE ADEQUATE
ELECTRICAL CONTACT. USE OF A DAMAGED OR DEFECTIVE CONNECTOR MAY RESULT IN A
RISK OF OVERHEATING OR ELECTRIC SHOCK.
WARNING: BATTERIES GENERATE GASES WHICH CAN BE EXPLOSIVE. TO PREVENT ARCING
OR BURNING NEAR BATTERIES, DO NOT DISCONNECT THE CHARGER DC OUTPUT FROM THE
BATTERIES WHEN THE CHARGER IS OPERATING. KEEP SPARKS, FLAME, AND SMOKING
MATERIALS AWAY FROM BATTERIES.
WARNING: ALWAYS SHIELD EYES WHEN WORKING NEAR BATTERIES. DO NOT PUT
WRENCHES OR OTHER METAL OBJECTS ACROSS BATTERY TERMINALS OR THE BATTERY TOP.
ARCING OR EXPLOSION OF THE BATTERY CAN RESULT!
WARNING: DO NOT DISCONNECT THE CHARGER DC OUTPUT FROM THE DC WIRING WHILE A
CHARGE CYCLE IS IN PROGRESS. THE RESULTING ARCING AND BURNING COULD CAUSE THE
BATTERIES TO EXPLODE.
Check the “NUMBER OF CELLS” and “VOLTS PER CELL” rotary switches on the UIM to verify their
settings against the specifications of the batteries (see Section 11.3 for valid ranges). If the
“NUMBER OF CELLS” rotary switches are set to “00”, which enables software control of the float
voltage value, refer to Section 11.3 in order to verify the “Number of Cells” and “Float Voltage Per
Cell” setting values via the charger web server (see Section 11.3 for valid ranges).
The float voltage should be set to the battery manufacturer’s specified voltage at 25 °C (77 °F).
Refer to Section 11 in order to verify other charger web server settings, such as the battery
temperature compensation values.
The charger does not have a hardware power switch. When AC input power is applied to the
charger, the DC output will start after a short delay unless the UIM Output Control has been turned
off.
The bi-color LED on the iPM(s) provides DC output status information along with iPM fault status
information. It also specifies where in the charge profile the system currently resides (start/bulk, float,
or equalize). See Section 9.2 for details.
To stop the charger, disconnect the AC power source or use t he “Output Control” button available on
the charger web server “Dashboard” (see Section 11.1).

ATLAS 14 of 44 User’s Manual
9. LED INDICATORS
9.1.UIM LEDs
The table below outlines the functionality of the UIM LEDs. See Figure 7-1 as a reference to the location of
the LEDs on the UIM.
AC
PRESENT
UIM
STATUS
CONFIRM
LOCAL
PRESENCE
ALARM
Description
Blue
Green
White
Red
AC Input
Power
Off
AC input power is not present.
Solid
AC input power is present.
Power Up
Solid / Off
Solid / Off
Solid / Off
Solid / Off
LEDs turn on and then off
independently on power up as an
LED test.
UIM Status
Off
UIM is not functioning properly.
Solid
UIM is functioning properly.
Confirm
Local
Presence
Off
Confirm Local Presence (CLP)
timer is not active. Web server
changes cannot be saved. CLP
button must be pressed in order
to activate the CLP timer.
Solid
Confirm Local Presence (CLP)
timer is active. Web server
changes can be saved.
Alarms &
Faults
Off
No alarms or faults are active.
Fast
Blink
Fast
Blink
Switch settings are out of range;
Number of Cells, Volts per Cell, or
Number of Cells * Volts per Cell
are either too high or too low (see
Section 11.3 for valid ranges).
Solid
At least one alarm is active with a
priority of “Major” or “Minor”.
Alarms configured with a priority
of “Warning” do not activate the
“Alarm” LED.

ATLAS 15 of 44 User’s Manual
9.2.iPM Bi-Color LED
The table below outlines the functionality of the iPM bi-color LED. When both green and red LEDs are on, the
color appears amber.
iPM Bi-Color LED
Description
Green
Red
Amber
Power Up
Solid / Off
Solid / Off
LEDs turn on and then off independently on power
up as an LED test.
DC Output
Status
Off
DC output is off. Either (1) AC input power is not
present, (2) the output has been manually turned
off via the UIM web server, or (3) the systems
"Power Saving Mode" has been enabled and the
iPM is not currently active (other iPMs in the
system are still active).
Slow
Blink
DC output is in constant-current bulk/start mode.
Solid
DC output is in constant-voltage float mode.
Alarms &
Faults
Solid
An iPM fault is active. DC output is off.
Slow
Blink
The iPM is unable to communicate with the UIM,
so the iPM is operating using the last
configuration it received from the UIM before
communication ceased.
Fast Blink
DC output is off due to a limit being exceeded
(max iPM temperature, etc). The DC output will
turn back on when the limit is no longer being
exceeded.
Equalizing
Slow
Blink
DC output is in equalize mode. The charger
output is in constant-current bulk/start mode while
equalize mode is active.
Solid
DC output is in equalize mode. The charger
output is in constant-voltage float mode while
equalize mode is active.
10.ETHERNET COMMUNICATION
The Ethernet port is located on the UIM (see Figure 7-1). It can be used to locally or remotely communicate
with the internal charger web server via a direct local connection to a laptop computer accessed via a
standard Internet browser or a networked connection to a remote or local laptop or desktop computer, smart
phone, or tablet via a standard Internet browser. Enable JavaScript within the Internet browser you plan
to use per the browser instructions (JavaScript is typically enabled by default). The Internet browser
must also support HTML5, which all popular modern browsers do (Internet Explorer is not
recommended).
10.1. Direct Local Communication
The charger Ethernet port is auto crossover, auto MDI-X, so it can be directly connect to a local laptop
computer via either (1) a standard Ethernet cable or (2) a crossover Ethernet cable. See Section 10.3 for
Manual (Static) Mode configuration instructions for direct local communication. The charger can then be
accessed via a standard Internet browser.

ATLAS 16 of 44 User’s Manual
10.2. Networked Remote or Local Communication
The charger Ethernet port can be connected to an Ethernet switch or router via a standard Ethernet cable in
order to add the charger to network. See Section 10.3 for Manual (Static) Mode configuration instructions for
networked communication. See Section 10.4 for Automatic (DHCP) Mode configuration instructions for
networked communication. Once the charger has been added to a network, it can be accessed via a remote
or local laptop computer, desktop computer, smart phone, or tablet via a standard Internet browser.
10.3. Manual (Static) Mode
The standard settings from the factory are “Manual (Static) Mode” with an “IP Address” of “10.10.10.210” and
a “Subnet Mask” of “255.255.255.0”. Your charger may have been factory-configured with alternate
settings. If this is the case, the charger may include a “Quick Start Guide” that lists these settings or
you may need to get these settings from your organization’s management.
Direct Local Communication
In order to establish direct local communication with a laptop computer, after connecting the charger Ethernet
port to the laptop Ethernet port, follow the steps below on a laptop computer. (The steps below are for
Windows 7. If you are using a different version of Windows or a different operating system, the steps will
vary).
Navigate to:
oStart >> Control Panel (View by: Category) >> Network and Internet >> Network and Sharing
Center >> Change Adapter Settings
-OR-
oStart >> Control Panel (View by: Large Icons or View by: Small Icons) >> Network and
Sharing Center >> Change Adapter Settings
Right-click on “Local Area Connection” and select “Properties”
Select “Internet Protocol Version 4 (TCP/IP v4)” and click the “Properties” button
Select “Use the following IP address:”
Enter an “IP address:” of “10.10.10.XXX”, where “XXX” is any 3-digit number other than “210” (for
example, “10.10.10.220”)
Enter a “Subnet mask:” of “255.255.255.0”
Press the “OK” button
Figure 10.3-1: Laptop Computer Ethernet Port Settings –Manual (Static) Mode

ATLAS 17 of 44 User’s Manual
Open an Internet browser (Windows Internet Explorer, Google Chrome, etc) and enter “10.10.10.210”
or “uim” in the address bar. Note: If Internet Explorer is used it must be version 10 or higher.
Figure 10.3-2: Accessing the Internal Charger Web Server via a Standard Internet Browser
10.4. Changing the Ethernet Port Settings
The “Ethernet Port” section on the “Configuration >> Ethernet Settings” page is shown in Figure 10.4-1. The
following settings can be viewed and/or changed per your direct or networked communication requirements.
Physical Address
oThis is the MAC address of the charger Ethernet port, which is read-only
Address Mode
o“Manual (Static)” (see Section 10.3) or “Automatic (DHCP)” (see Section 10.5)
IP Address
Subnet Mask
Gateway Address
Primary DNS Address
Secondary DNS Address

ATLAS 18 of 44 User’s Manual
Figure 10.4-1: Ethernet Port Section of the Configuration >> Ethernet Settings Page
10.5. Automatic (DHCP) Mode
When the charger is being connected to a network, it will often need to be configured for Automatic (DHCP)
Mode. In order to do so, first follow the instructions in Section 10.3 to directly connect a laptop or desktop
computer to the charger. Then, navigate to the “Ethernet Port” section on the “Configuration >> Ethernet
Settings” page and change the “Address Mode” setting value to “Automatic (DHCP)”, as shown in Figure
10.5-1.
Figure 10.5-1: Ethernet Port Section of the Configuration >>
Ethernet Settings Page –Automatic (DHCP) Mode

ATLAS 19 of 44 User’s Manual
10.6. Restoring the Factory-Default Ethernet Port Settings
If you are unable to communicate with a charger after changing the setttings within the “Ethernet Port” section
on the “Configuration >> Ethernet Settings” page, you can restore the factory-default “Ethernet Port”settings
by following the steps below
Remove AC and DC (battery) power from the charger.
Press and hold the “CONFIRM LOCAL PRESE NCE” button on charger UIM.
Re-apply AC and or DC (battery) power to the charger while continuing to hold the “CONFIRM
LOCAL PRESENCE” button until the charger completes booting up (UIM LED startup sequence has
finished.).
The “Ethernet Port” settings have now been restored to the factory -defaults.
Follow the steps in Section 10.3 again.
11.WEB SERVER
The internal charger web server can be accessed via a standard Internet browser on a local or remote laptop
or desktop computer, smart phone, or tablet. See Section 10 for connectivity instructions.
Web server changes can only be made after the "CONFIRM LOCAL PRESENCE" button has been physically
pressed on the UIM. Pressing this button starts a timer. After this time has expired, the "CONFIRM LOCAL
PRESENCE" button must be pressed again to make additional web server changes.
11.1. Dashboard
System
The header for the “System” section on the “Dashboard” page displays the system alarm status as is
illustrated in Figure 11.1-1.
Figure 11.1-1: System Section Header on the Dashboard Page Displays the System Alarm Status

ATLAS 20 of 44 User’s Manual
Below are descriptions of the items displayed in the “System” section of the “Dashboard” page.
Name
Description
Site Name
"Site Name" setting value on the web server "Configuration >>
System Settings" page.
Serial Number
Serial number of the chassis/UIM.
UIM Firmware
Firmware version on the UIM.
Webserver Firmware
Firmware version of the web server on the UIM.
Battery Voltage
DC voltage at end of DC cable or the remote battery sense cable.
DC Output Current
Total DC output current of the system.
DC Output Power
Total DC output power of the system.
AC Input Voltage
AC input voltage.
Battery Temperature
Battery pack temperature.
If the "Remote Battery Temperature" setting on the web server
"Configuration >> System Settings" page is enabled then the Battery
Temperature will be displayed if no temperature sensor faults.
If the battery temperature sensor is disconnected or has failed then
"Fault" will be displayed.
If the "Remote Battery Temperature" setting on the web server
"Configuration >> System Settings" page is disabled then "Disabled"
is displayed.
Internal Charger Temperature
Internal charger temperature at the UIM.
Float Voltage Controlled By
Location of float voltage control.
Rotary Switches: rotary switches on the UIM.
Web: settings on the web server "Configuration >> Charge Settings"
page in the "Charge Profile" section.
DC Voltage Sensing
Location of the DC voltage sensing.
Local: charger DC output terminals at the end of the DC cable. This
dependent on proper output cord settings. See if the web server
"Systems Settings" page to setup "DC Cable Gauge" and "DC Cable
Length".
Remote: "REMOTE DC VOLTAGE" input on the UIM. This will be
displayed if the "Remote Battery Voltage" setting on the web server
"Configuration >> System Settings" page is enabled and sensed
properly.
Configured via the "Remote Battery Voltage" setting on the web
server "Configuration >> System Settings" page.
Local (Remote Fault): This will be displayed if the "Remote Battery
Voltage" setting on the web server "Configuration >> System
Settings" page is enabled but not sensed for some reason.
Confirmed Local Presence Time
Remaining
The amount of time remaining in minutes that web server changes
can be made. After this time has expired, the "CONFIRM LOCAL
PRESENCE" button on the UIM must be pressed again to make
additional web server changes.
Table of contents
Other Pivot Power Supply manuals
Popular Power Supply manuals by other brands

Hama
Hama Universal-Ultrabook/Notebook-Power Operating instruction

GRAUPNER
GRAUPNER POWER SUPPLY 13.8V 0-12A manual

Cosel
Cosel STA5000T-R instruction manual

Albalá Ingenieros
Albalá Ingenieros PSU2000C02 manual

Jinbo
Jinbo JLV-12240K Specifications & user's guide

RP GROUP
RP GROUP microControl plus Setup and Commissioning Guide