pleiger 362MC User manual

Pleiger Elektronik GmbH & Co. KG
D-58456 Witten - Im Hammertal 51
D-58423 Witten - P.O.Box 32 63
Telephon +49 (0) 23 24 * 3 98- 0
Telefax +49 (0) 23 24 3 98- 3 89
www.pleiger-elektronik.de
info@pleiger-elektronik.de
PLEIGER ELECTRONICS 362MC
Operation
Installation
Connection
Technical data
Hardware extensions
Functional extensions
Commissioning help
Edition: 6/2007
Subject to modifications

Pleiger Elektronik
GmbH & Co. KG
Page: 2 Manual for 362MC Edition: 6/2007 Subject to modifications
Contents Page
1Introduction ..................................................................................................... 4
2Display and operating elements ..................................................................... 5
2.1 Display .................................................................................................... 6
2.2 Operation ................................................................................................ 6
3Operating modes ............................................................................................ 7
3.1 Automatic mode ...................................................................................... 7
3.1.1 Setpoint entry ................................................................................ 7
3.2 Switching between Manual/Automatic ..................................................... 8
4Manual / Emergency manual mode ................................................................ 8
5Commissioning extension .............................................................................. 9
5.0 Password entry ....................................................................................... 9
5.1 Additional Menu selection with QuickSet ................................................. 11
5.2 Commissioning menu ............................................................................. 12
5.3 Setpoint menu ......................................................................................... 13
5.3.1 Explanatory note on setpoints ....................................................... 14
5.3.2 Explanatory note on the switching filter ......................................... 14
5.3.3 Explanatory note on the limit value alarm ...................................... 14
5.4 Controller profile menu ............................................................................ 15
5.4.1 Entering parameters for two controllers ........................................ 15
5.4.2 Entering parameters for one controller only .................................. 15
5.5 Controller parameters menu ................................................................... 16
5.5.1 Explanatory note on controller types ............................................. 17
5.5.2 Explanatory note on controller structure ....................................... 19
5.5.3 Explanatory note on controller output parameters ........................ 20
5.6 Input menu .............................................................................................. 21
5.6.1 Explanatory note on calibration ..................................................... 22
5.6.2 Explanatory note on scaling .......................................................... 22
5.7 Output menu ........................................................................................... 23
5.8 Display menu .......................................................................................... 24
5.8.1 Explanatory note on controller inputs/outputs ............................... 24
6Monitoring functions and error messages ...................................................... 25
6.1 System monitoring functions................................................................... 25
6.1.1 Explanatory note on Param error .................................................. 25
6.1.2 Explanatory note on ROM error and RAM error ............................ 25
6.1.3 Explanatory note on the Reset function for the controller.............. 26
6.1.4 Explanatory note on Watchdog error............................................. 26
6.2 Sensor monitoring functions ................................................................... 26
7Service interface ............................................................................................. 27
7.1 Service programme McDiag ................................................................... 27
8Installation ...................................................................................................... 28
9Connection ..................................................................................................... 29
9.1 Terminal assignments ............................................................................. 29
9.2 Connection of supply voltage .................................................................. 30
9.3 Connection of the switching outputs ....................................................... 30
9.3.1 Connection with AC switching output contacts ............................. 30
9.3.2 Connection with floating switching output contacts ...................... 30
9.4 Connection of the alarm output ............................................................... 31
9.5 Connection of the binary inputs ............................................................... 31
9.6 Connection of the remote resistance-type sensor .................................. 31

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 3
Contents Page
9.7 Connection of a U/I measured-value transmitter ..................................... 31
9.8 Connection of the PT100 sensor............................................................. 32
9.9 Connection of a I -value transmitter at the 1st analogue input.................. 32
9.10 Connecting cable ................................................................................... 32
10 Technical data ................................................................................................ 33
Appendix A: Reference overview
Appendix A1: Overview of menu structure for standard functions ...................... 34
Appendix A2: Parameters from A to Z for standard functions ............................. 35
Appendix A3: Value assignments from A to Z for standard functions .................. 36
Appendix A4: Error displays and messages from A to Z ..................................... 37
Appendix A5: Symbols employed in this manual ................................................ 37
Appendix B: Hardware extensions for the 362MC
Appendix B1: Hardware extension - 2nd relay set ................................................ 38
Appendix B2: Hardware extension - Analogue outputs ........................................ 39
Appendix B3: Hardware extension - RS485/RS422 communication interface.... 40
Appendix C: Functional extensions for the 362MC
Appendix C1: Special function - Trend compensation ......................................... 41
Appendix C2: Functional extension - Disturbance compensation ....................... 43
Appendix C3: Functional extension - Setpoint programme ................................. 47
Appendix C4: Functional extension - Differential actual value ............................. 51
Appendix D: Commissioning help
Appendix D1: Steps for commissioning .............................................................. 52
Appendix D2: Profile memories and factory presets ........................................... 53
Appendix D3: Programme entries table for setpoint programmes ...................... 57
362MC Delivery configurations ...................................................................... 58

Safety Instructions
Pleiger Elektronik GmbH & Co. KG Fon +49 2324 398 330
D-58456 Witten ●Im Hammertal 51 Fax +49 2324 398 389
www.pleiger-elektronik.de pe@pleiger.de
General information
This manual contains instructions and drawings for correct handling and using the equipment. Please
observe all instructions of this manual carefully.
Please note that not respecting the information, using the equipment not according the regulations be-
low, wrong installation or incorrect handling could influence personal or plant safety seriously!
This manual is part of this operation resource. Keep the manual safe for later use. The manufacturer re-
serves the right to change performance data, specification data or the design layout without an advance
notice.
Transportation and storage instructions
The equipment must be inspected upon reception for damages that may have occurred
during transportation or handling. If damages are obviously, inform the carrier and the
manufacturer immediately. Dropped components must not be applied because invisible
damages may influence the reliability.
Installation and electrical connection
The equipment has to be installed by qualified personnel only, that is familiar with the
safety requirements and potential risk. Please note the special safety requirements be-
longing the point of installation, generally accepted rules of technology, the connection
instruction in this manual and the available imprint on the component.
Intervention into the component
If malfunctions occur or something is dubious please contact the manufacturer. Intervention into the com-
ponent could heavily affect the safety of person and plant and will lead to termination of liability and caveat
emptor.
Intended use
To use the equipment is approved only if the instructions of this manual are complied and the use is
appropriate to the type label and to an application it is intended to.
In the field the technical specifications and denoted limit values have to be generally maintained. This
applies particular with regard to voltage, temperature and other noted environmental conditions. The use
beyond the specified and approved edge conditions could put life at risk, damage the component or cause
secondary damages to the plant.
Not intended use
Every use of the component that is not equal to the use described in chapter „intended use“ is obtained
as not intended use. Damages that result from not intended use and / or result from unauthorised inter-
vention on the component, not according to this manual, or not using original spare parts the claim for
warranty and liability of the manufacturer expires.
Use in safety related vital functions
It is the responsibility of the user to perform a risk analysis of the whole installation and to define potential
safety related functions.
It is the responsibility of the user to take care of appropriate measures to achieve the safeness in safety
related vital functions.
Technical Support:
+49 2324 398 333
service@pleiger-elektronik.de

Pleiger Elektronik
GmbH & Co. KG
Page: 4 Manual for 362MC Edition: 6/2007 Subject to modifications
1 Introduction
The Pleiger multi-function controller 362MC combines a large number of controller functions in a single
compact housing designed for installation in a control panel. A powerful microcontroller, a large parameter
memory and a two-line alphanumeric display support simple and swift operation and commissioning of the
controller.
The 362MC incorporates the following controller functions in one unit:
Two-point controller
Three-point controller with separate parameter sets for both outputs
Three-point step controller, with optional feedback of controller output
Continuous controller
Cascade step controller
Two independent control loops can be operated with one controller unit, provided that the controller is per-
missible for the application concerned.
The 362MC incorporates a large number of special features, such as:
an actual-value display and manual controller output adjustment which function
independently of the microcontroller to enable manual emergency operation for
switching controllers, even in the event of processor failure;
a large non-volatile parameter memory to enable storage of up to 50 different controller
configurations for frequently required applications;
a two-line alphanumeric LCD display for process data and easily comprehensible operating
prompting;
a serial service interface which is accessible via the front panel of the controller, to enable
connection of a terminal or a PC to the Pleiger service programme 362McDiag.
In addition to the user-friendly operating and display functions, the 362MC does, of course, also provide
additional control functions to enable the safe and reliable control of complex systems, such as
differential trend compensation via the second measuring sensor, for enhanced control of
systems with large dead times;
switch-over to a second setpoint via an external signal;
inputs for an external setpoint and for logical adjustments and interlocks.
The 362 MC can be supplied in a configuration geared specifically to the application concerned, by means
of different voltage variants (230V-AC, 115V-AC), different measurement ranges (0-200°C, 0-500°C,
0-100%) and different component variants for the inputs (PT100, 4-20mA, 0-10V) and outputs (relays
with supply voltage or floating contacts).
Hardware extensions are also available, such as
a 2nd relay group for switching outputs,
a module with 2 analogue outputs - 0(4)-20mA or 0-10V,
a module with RS 485/422 serial data interface
and functional extensions, such as
additive disturbance compensation weighted via any characteristic with five interpolation
points for advance compensation of the controlled system,
setpoint programmes for time-dependent setpoint adjustments and
difference input for actual values, e.g. for differential pressure control of pumps.
In the appropriate configuration, the single 362MC unit is thus able to replace the Pleiger controllers and
supplementary modules 361-D, 362-D, 366-D and 366-V.

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 5
2 Display and operating elements
The 362MC controller incorporates a 2½-digit LED actual-value display for the 1st controller which is
clearly legible at a distance. For special applications, the display is also available as a 3½-digit variant
(with decimal digit or for special measuring ranges). The 362MC additionally features an two lines LCD
process data and parameter display. During normal operation of the controller, this display is employed to
display various process variables. The display also provides easily comprehensible operator prompting for
all entry operations.
Eight buttons are integrated in the foil of the front panel to control the display, to enter data, to switch the
operating mode and to activate emergency manual mode. The buttons are arranged in three groups.
A practical, replaceable labelling field is provided under the foil for identification of the measuring point.
After removing the front frame and
lifting the lower part of the foil, the
fuse for switching outputs and the
connector for the service interface
are also accessible after installation
of the controller. The labelling field is
simple to replace.
Fuse F2 Connector for service interface Front frame
LED actual-value display
LED Auto Actual value X of 1st controller
ON = Automatic mode without decimal place
OFF= Manual / Emergency (1st analogue input direct;
manual mode PT100 input in °C,
4-20mA input in %)
LCD display lines 1 + 2
(Operating display and
Switching output buttons operator prompting)
+ = actuator OPEN
- = actuator CLOSED
(only by Emergency
manual mode)
Selection + entry buttons
Man and Auto buttons = Select+ increase value
Man = Manual / Emergency = Select+decrease value
manual mode Prgm=Select+save
(only together with Exit) Exit =Cancel+abort
Auto = Automatic mode (Exit+Man=Manual /
Emergency manual mode)
Labelling field
for identification of
measuring points

Pleiger Elektronik
GmbH & Co. KG
Page: 6 Manual for 362MC Edition: 6/2007 Subject to modifications
Menu 1 Menu 2 Menu n
Parameter
1
Parameter
2
Parameter
n
Value
Param. 2
Value+1
Value-1
Save
value
Menu selection
Parameter entry
Example of
operational display
Line 1
Line 2
2nd L1
2nd L2
On power up, the
362MC always
displays the type and version no.
2.1 Display
On power up, the controller always displays the type and version no. first of all, before
switching to menu 1, the operational display. Here the process data are shown in the
two-line LCD display. Display lines 1 and 2 are visible in normal operating
mode. By pressing the Prgm button, the display can be switched to a
second mode (2nd line 1 and 2nd line 2)
for as long as the button is held.
The user can assign the process data
in the operational display to the lines via
the commissioning menu Display (5.8).
2.2 Operation
Operation of the controller, configuration and setting of the controller
parameters are carried out with operator prompting in 3 selection levels.
Menu selection constitutes the highest selection level. In normal
operating mode the menu selection remains hidden and the process
data are shown on the LCD display. The desired menu is selected via the and buttons.
The menu name is now shown in the 1st line of the LCD display instead of the process data . Each menu
groups together entry items and parameters which are closely linked. The Prgm button can be used to
branch to the desired menu and the parameter selection function. The desired parameter is selected
here in the same manner, using the and buttons.
The 1st line of the display shows the name and the 2nd line the value of the selected parameter. If the
selected value now requires to be altered, the Prgm button must be pressed to branch to the parameter
entry function. Here the value can
be altered with the and buttons.
The value is entered and saved via
the Prgm button.
If the Exit button is pressed at any
point, the current selection will be
aborted. From the parameter entry
function the system will branch back
without altering the set value to
the parameter selection function,
from parameter selection the system
will always branch back to he menu
selection function, and from menu
selection menu 1 - the operational
display - will always be activated.
Should no button be pressed over a
period of 60 seconds during the
selection or entry process, the
operational display will be
re-activated automatically.
Menu name
Parameter name
Parameter value
Value entry
Example of display
at selection and entry

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 7
3 Operating modes
The 362MC incorporates two operating modes - Automatic and Manual / Emergency manual mode. A
modified menu is provided for each operating mode. Both operating modes offer an extended version of
the menu for commissioning purposes. This extension to the menus for configuration and
parameterisation of the controller is protected by a password to prevent unauthorised use.
3.1 Automatic mode
The green Auto LED lights up; the controllers are operating in a closed-loop system. The setpoints can
be altered via the setpoint entry or the commissioning menus can be activated via the menu selection
function, provided that the valid password has been entered.
3.1.1 Setpoint entry
After selecting the Setpoint Entry
menu under the menu selection
option in Automatic mode, the
setpoints and the alarm limits of
both controllers can be altered.
The 1st character of the name
displayed under the entry option
denotes the number of the controller - 1 or 2.
The letter A or B appears as the final character,
to distinguish between the main setpoint (A)
and the second setpoint (B) that becomes active
in the case of external setpoint switching.
The value for the lower alarm limit
of each controller is indicated by -
and the value for the upper alarm
limit is indicated by +.
See also Explanatory note on limit alarm (5.3.3).
This presentation of the setpoint entry procedure is based on the assumption that both controllers have
been configured as fixed setpoint controllers with setpoint type fixed value. The 1st controller setpoint is
101.0°C for Setp A and Setp B, irrespective of the setpoint switching function. 82.0°C is defined under
Setp A for the 2nd controller.
When external setpoint switching applies, Setp B is set at 65.0°C. When a different setpoint type is
configured, the setpoint entry display has a different appearance.
In the case of the setpoint type external setpoint (extern), an external value connected
at the input becomes the setpoint. It is thus not possible to alter this value by entering a
different value.
When the controller is implemented with a setpoint programme, the user
can switch between the stored programme numbers 1 to 5 (in this example 2).
See also Functional extensions (Appendix C3).
Display example
with password
entry to the
commissioning
menu
Operational display Setpoint menu Password menu
Menu selection in automatic mode
Value+1
Value-1
Save
new value
Alter value

Pleiger Elektronik
GmbH & Co. KG
Page: 8 Manual for 362MC Edition: 6/2007 Subject to modifications
The buttons are provided only for the manual adjustment of switching
outputs on the 1st controller in Emergency manual mode, and have no other functions.
3.2 Switching between Manual/Automatic
Manual / Emergency Manual mode will only be activated if the user presses the Man and Exit button
simultaneously. This eliminates the possibility of Automatic mode being deactivated unintentionally or by
mistake. The green AUTO LED turns off, and the text MANUAL is shown in the 1st line of the LCD display
in alternation with the process value. Manual operation of the outputs and emergency manual mode for the
switching output of the 1st controller are active.
Automatic mode is activated again by pressing the Auto button. The green LED marked Auto lights up.
4 Manual / Emergency manual mode
When Manual / Emergency manual mode is active, buttons - and + are used to adjust the
1st controller´s switching output. When the + button is pressed, the output is switched to +, as a result
of which the connected actuator is operated in OPEN direction. When the - button is pressed, the
output is switched to -, as a result of which the actuator is operated in CLOSED direction.
This Emergency manual mode for the 1st controller operates irrespective of whether the micro-
controller is operational. The 2½-digit actual-value LED display of the 1st controller is also available for
Emergency manual mode independently of the microcontroller.
Manual mode is activated via the Manual menu to enable adjustment of a continuous controller output
of the 1st controller or to adjust a controller output of the 2nd controller. This menu can only be activated in
Manual mode, following the operational display.
Outputs are adjusted immediately. The percentage output value of a analogue output is altered from its
current value in accordance with the value entered by the user and is output directly. The switching output
on the 2nd controller is adjusted for as long as the button remains depressed.
Operational display Setpoint menu Password menu
Menu selection in Manual / Emergency manual mode
alternate
each second
Manual menu
Value+1
to output
Linear output
adjust
1st controller
Switching or linear output
Value-1
to output
Emergency manual
adjust
with
2nd controller
Switching or linear output
Switching output
adjust

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 9
5 Commissioning extension
The menu selection option of the 362MC can be extended for the purposes of commissioning the con-
troller. The extended functions for altering the configuration or parameterisation are available in both
Automatic and Manual / Emergency manual mode. The menu extension is accessible after entering the
password. This password lock serves to provide protection against unauthorised use.
5.0 Password entry
If no password has been entered (PW-lock=On), the password lock will be deactivated
to enable access to the extended commissioning menu by entering the currently valid password.
To this end, digits 1 to 4 have to be set to the stored
value for the password, in each case beginning from a
value of 0.
After input of the 4th digit, shown in the example here as password 1234, the value is compared against
the stored password. If the entered value corresponds to the stored password, the password lock will be
deactivated (PW-lock=Off); if the entered value does not correspond to the stored password, the pass-
word lock will remain active.
The password status is retained when the voltage supply for the controller is switched on and off.
On delivery, the password 0362 is stored for the 362MC.
Please alter this password to protect your specific settings.
Setpoint menu Password menu
Value+1
Value-1
Digit 1
Value entry
Value+1
Value-1
Digit 2
Value entry
Value+1
Value-1
Digit 3
Value entry
Value+1
Value-1
Digit 4
Value entry
compare
value
(example)

Pleiger Elektronik
GmbH & Co. KG
Page: 10 Manual for 362MC Edition: 6/2007 Subject to modifications
When the password entry function is selected while the password lock is deactivated (PW-lock=Off), the
password lock can be activated again or the stored password can be altered.
Activation of the password lock
When this function is selected, the current status:
password lock OFF or password lock ON, is shown in the
2nd line of the display. On activation of the password lock,
the system exits the commissioningmenu again.
Changing the password
A new password is selected and
entered as already described in
detail under Password entry.
Any number >=0000 and <=9999 is
permissible as the value for the
password.
Display menu
Activation of the password lock
Password
lock
OFF
Password
lock
ON
Value+1
Value-1
Digit 1
Value entry
Digit 2 to 4
Value entry
save
new
password
Changing the
password
Password menu

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 11
5.1 Additional Menu selection with QuickSet
for Controller 362MC from SER.NO 0605
An additional parameter menu is integrated in the Controller 362MC from Serial-No 0605 (Delivery the from
middle of 2006) and includes the most important adjustments for the commissioning of the control
process.
The QuickSet can be directly selected in Automatic mode or in Manual mode by pressing the Exit button.
The parameter selection and parameter entry is done in the same way as in the other menus for
parameters.
The desired parameter is selected, using the and buttons, the Prgm button must be pressed to
branch to the parameter entry function and here the value can be altered with the and buttons. The
value is entered and saved via the Prgm button. If the Exit button is pressed, the current selection will be
aborted.
(See also 2.1 Display and 2.2 Operation)
In the following table the inputs and parameters of the menu QuickSet are listed. For more information in
detail see also the stated pages.
The QuickSet is installed additionally.
All other operations, functions, parameters and
inputs of the Controller are as usual and without changes.
Value+1
Value-1
Save
new value
Alter value
+
together
Operational display
Automatic mode
Operational display
alternate
each second
Manual mode

Pleiger Elektronik
GmbH & Co. KG
Page: 12 Manual for 362MC Edition: 6/2007 Subject to modifications
Many of the range limits (min/max value) stated in the following tables are dependent
on the scaling selected for the physical variables via the parameters Scale-0 and
Scale-F. See also explanatory note on scaling (5.6.2).
5.2 Commissioning menu
After entering the password (PW-lock=Off), the menu extensions can be selected for commissioning,
both in Automatic and Manual / Emergency manual mode, after entering the setpoint menu.
The following tables for the commissioning menus show the parameter (name), the value range (min/
max) and an appurtenant explanation (meaning/comment), together with the memory location in the
profile ( = profile controller 1, = profile controller 2) and a symbol to denote ! Adjustment in
Manual mode only !
Comment at Ts min: Too long Ts min will result a permanent control deviation.
Too short Ts min may overburden the actuator.
Parameter Value (min Meaning Comment
max) see Details
1Setp A 0.0°C Setpoint input if Setp. type A = fixed value
200.0°C see Setpoint menu 5.3 (Parameter each controller)
Kr -999.0 P gain see also Commissioning (D1)
999.0 see Controller parameters 5.5 (Parameter each contr. + parameter set)
Tn 10s Reset time for I component see also Commissioning (D1)
10000s see Controller parameters 5.5 (Parameter each contr. + parameter set)
Ts min 0.1s min. switching duration for switching output Comments at Ts min see down the table
100.0s see Controller parameters 5.5 (Parameter each contr. + parameter set)
Prof-No 1 Select controller profile Load practicable profile for operation
50 see Controller profiles 5.4 (and save with Save as function)
Line 2 1Feed+Y 2nd line of the LCD display Example with position feedback
see Display menu 5.8 (without = 1Out+Y)
Inputs and parameters of the menu QuickSet
Operational display
Example: Menu selection in Automatic mode
Setpoint menu Password menu
Menu extensions
for commissioning
Controller
profile menu
Controller
parameter menu
Input
menu
Display
menu
Output
menu

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 13
Parameter Value (min Meaning Comment
1st Controller max)
1SpTypA1SpTypA
1SpTypA1SpTypA
1SpTypA
fixedfixed
fixedfixed
fixed Setp. type A = fixed value See also Functional extension
extern extern
extern extern
extern = external input Setpoint programme (Appendix C3)
1Setp A1Setp A
1Setp A1Setp A
1Setp A 0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Setpoint A for type A=fixed Setpoint here e.g. 0-200°C; see also
200.0°C200.0°C
200.0°C200.0°C
200.0°C extern for type A=extern Explanatory note on setpoints (5.3.1)
1SpTypB1SpTypB
1SpTypB1SpTypB
1SpTypB
fixedfixed
fixedfixed
fixed Setp. type B = fixed value The second setpoint, B, is only
extern extern
extern extern
extern = external input active when an external switching
1Setp B1Setp B
1Setp B1Setp B
1Setp B 0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Setpoint B for type B=fixed input has been parameterised for
200.0°C200.0°C
200.0°C200.0°C
200.0°C extern for type B=extern 2Setp in the Input menu.
1T-Lowp1T-Lowp
1T-Lowp1T-Lowp
1T-Lowp 0.0s 0.0s
0.0s 0.0s
0.0s Low pass filter time See also Explanatory note on
999.9s 999.9s
999.9s 999.9s
999.9s for setpoint switching switching filter (5.3.2)
1Alarm-1Alarm-
1Alarm-1Alarm-
1Alarm- -99.0°C-99.0°C
-99.0°C-99.0°C
-99.0°C Alarm limit= Setp.-abs.value 1Alarm- Lower alarm limit (ActVal < Setp)
0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Alarm OFF See also Explanatory note on
200.0°C200.0°C
200.0°C200.0°C
200.0°C Alarm limit= 1Alarm- limit value alarm (5.3.3)
1Alarm+1Alarm+
1Alarm+1Alarm+
1Alarm+ -99.0°C-99.0°C
-99.0°C-99.0°C
-99.0°C Alarm limit= Setp.+abs.value 1Alarm+ Upper alarm limit (ActVal > Setp)
0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Alarm OFF See also Explanatory note on
200.0°C200.0°C
200.0°C200.0°C
200.0°C Alarm limit= 1Alarm+ limit value alarm (5.3.3)
Parameter The following parameters for the 2nd controller are displayed only when
2nd Controller 2 controllers are selected in the Profile menu.
2SpTypA2SpTypA
2SpTypA2SpTypA
2SpTypA
fixedfixed
fixedfixed
fixed Setp. type A = fixed value See also Functional extension
extern extern
extern extern
extern = external input Setpoint programme (Appendix C3)
2Setp A2Setp A
2Setp A2Setp A
2Setp A 0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Setpoint A for type A=fixed Setpoint here e.g. 0-200°C; see also
200.0°C200.0°C
200.0°C200.0°C
200.0°C extern for type A=extern Explan. note on setpoints (5.3.1)
2SpTypB2SpTypB
2SpTypB2SpTypB
2SpTypB
fixedfixed
fixedfixed
fixed Setp. type B = fixed value The second setpoint, B, is only
extern extern
extern extern
extern = external input active when an external switching
2Setp B2Setp B
2Setp B2Setp B
2Setp B 0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Setpoint B for type B=fixed input has been parameterised for
200.0°C200.0°C
200.0°C200.0°C
200.0°C extern for type B=extern 2Setp in the Input menu.
2T-Lowp2T-Lowp
2T-Lowp2T-Lowp
2T-Lowp 0.0s 0.0s
0.0s 0.0s
0.0s Low pass filter time See also Explanatory note on
999.9s 999.9s
999.9s 999.9s
999.9s for setpoint switching switching filter (5.3.2)
2Alarm-2Alarm-
2Alarm-2Alarm-
2Alarm- -99.0°C-99.0°C
-99.0°C-99.0°C
-99.0°C Alarm limit= Setp.-abs.value 2Alarm- Lower alarm limit (ActVal < Setp)
0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Alarm OFF See also Explanatory note on
200.0°C200.0°C
200.0°C200.0°C
200.0°C Alarm limit= 2Alarm- limit value alarm (5.3.3)
2Alarm+2Alarm+
2Alarm+2Alarm+
2Alarm+ -99.0°C-99.0°C
-99.0°C-99.0°C
-99.0°C Alarm limit= Setp.+abs.value 2Alarm+ Upper alarm limit (ActVal > Setp)
0.0°C 0.0°C
0.0°C 0.0°C
0.0°C Alarm OFF See also Explanatory note on
200.0°C200.0°C
200.0°C200.0°C
200.0°C Alarm limit= 2Alarm+ limit value alarm (5.3.3)
5.3 Setpoint menu
In addition to the described setpoint entry function (3.1.1), the setpoint types, SetpTyp,
and the filter times, T-Lowp, can be parameterised here in the commissioning menu.
In case of the special version 0-500°C the maximum values for the temperature are
changed to 500°C instead of 200°C.
Negative values for the alarm parameters relate to system deviations
(relative to the setpoint); positive values for the alarm parameters relate
to fixed alarm limits; alarm parameter = 0 = limit monitoring OFF.
We urgently recommend you to alter the parameters marked with the symbol
in the tables belonging to this description in Manual mode only. This will avoid
unintentional activation of the actuator.

Pleiger Elektronik
GmbH & Co. KG
Page: 14 Manual for 362MC Edition: 6/2007 Subject to modifications
Measuring sensor Measuring Parameters Comment
for example: range Scale-FScale-F
Scale-FScale-F
Scale-F Scale-0Scale-0
Scale-0Scale-0
Scale-0 DimDim
DimDim
Dim SetpSetp
SetpSetp
Setp
PT100 0 to 500°C 500,0 0,0 °C 0 - 500,0 °C The required hardware
Pressure sensor -1 to 5 bar 6,0 -1,0 B -1,0 - 5,0 bar configuration for the
Displacement sensor 0 to 300 mm 300,0 0,0 mm 0 - 300,0 mm installed 362MC is to be
Rotation angle sensor 0 to 100% 100,0 0,0 % 0 - 100,0 % observed.
If no other error: Alarm relay energised = actual value within alarm limits;
Alarm relay not energised = limit value alarm;
see also Monitoring functions and error messages (6).
W
t
Tf
Alarm ON
Alarm OFF
Alarm ON
5.3.1 Explanatory note on setpoints
The table for the Setpoint menu shows a permissible range from 0-200°C for setpoints Setp A and
Setp B of each controller. This range is valid for PT100 inputs in standard configuration. Additional
setpoint ranges can also be set, in each case adapted via the scaling factor to the employed measuring
sensors and the physical variables to be controlled.
These settings are carried out in the Input menu via parameters Scale-F, Scale-0 and Dim.
Several examples of other value ranges are shown in the following table.
See also Input menu (5.6)
5.3.2 Explanatory note on the switching filter
In order to avoid discontinuous transient conditions and overshoot
during setpoint switching, a switching low pass filter of the 2nd order
can be parameterised on the 362MC.
The time for the switching filter is set via the parameter Tf = T-Lowp.
5.3.3 Explanatory note on the limit value alarm
Alarm limits can be parameterised to monitor the actual values and
a permissible system deviation. These impose a lower alarm limit
and an upper alarm limit on the permissible control band. If the
actual value violates a fixed alarm limit for longer than 5s or a
relative alarm limit for longer than 60s, the alarm will be activated.
When an alarm is activated, the alarm relay is de-energised (Alarm ON)
(closed-circuit principle) and the current display is switched to the
error display. This display remains active until the alarm is
acknowledged via the Exit button. The alarm relay is energised
again (Alarm OFF) when the actual values is insite the control band.
For example:
Point 0: The 1st actual value attains the control band for the 1st time.
Alarm OFF; the alarm display function is started.
Point 1: The upper alarm limit is violated! The alarm is activated
(Alarm ON) and the error indication ActV++ is displayed.
Point 2: The upper alarm range is left again.
Alarm OFF; the alarm relay is energised.
Point 3: The lower alarm limit is violated. The alarm is activated
(Alarm ON) and the error indication ActV is displayed.
Point 4: The lower alarm range is left again.
Alarm OFF; the alarm relay is energised.
Operational
display
Error
display
or
Alarm
acknowledge
alternate
each second
only
Operational display
Error display

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 15
Parameter Value (min Meaning Comment
max)
DsplCtrDsplCtr
DsplCtrDsplCtr
DsplCtr
only 1only 1
only 1only 1
only 1 Display controller = only controller 1 activ Entry point marked
1 of 2 1 of 2
1 of 2 1 of 2
1 of 2 Display controller = displ. controller 1 of 2 Entry point marked
2 of 2 2 of 2
2 of 2 2 of 2
2 of 2 Display controller = displ. controller 2 of 2 Entry point marked
The parameters which are stored
Prof-NoProf-No
Prof-NoProf-No
Prof-No 1 1
1 1
1 Select controller profile for operation in a controller profile and are thus
50 50
50 50
50 Value = profile no. 1 to no. 50 available for subsequent selection
are indicated as follows
Save asSave as
Save asSave as
Save as 1 1
1 1
1 Save current controller profile as for controller 1 and
50 50
50 50
50 value = profile no. 1 to no. 50 for controller 2.
5.4 Controller profile menu
On the 362MC, all the necessary settings for a controller are grouped together in
so-called profiles. Each profile thus contains all the parameters for a specific application.
The parameter memory of the 362MC contains 50 memory locations for different profiles, enabling
previously tested commissioning values to be stored as profiles for a large number of applications. The
commissioning procedure is then started by selecting the appropriate profile for the control task
concerned.
To this end, one of the controllers are first of all selected in the Profile menu via the parameter DsplCtr,
this controller´s profile is selected via Prof-No and its parameters are subsequently displayed and
altered in the following menus. Selection and entry points are marked accordingly on the display of the
362MC. The tables belonging to this description state which parameters are stored in which control menu.
5.4.1 Entering parameters for two controllers
It is to be noted here that
- only the parameters of one profile and thus of one controller are displayed;
- the two controllers must always be assigned different profiles via Prof-No.
During commissioning, the display should thus be set specifically to the controller which is to be put into
operation; e.g. from DsplCtr = 1 of 2 for the 1st controller to DsplCtr = 2 of 2 for the 2nd controller and
vice-versa. It is not necessary to enter the profile no. assigned to the controller under Prof-No again
for this purpose.
5.4.2 Entering parameters for one controller only
When the 362MC is used for one controller only, DsplCtr should be switched to 1 only.
This precludes any switching. The parameters for the 2nd controller will no longer be displayed.
If you save the selected profile to an available Prof-No via the Save as function
before commissioning, the parameters which have been altered in the course of
commissioning will be stored for you in this new profile. If possible, do not alter the
profile memory locations containing the factory presets, so as to ensure that you will
be able to access these profiles if necessary.
With regard to the entry of parameters for the 2nd controller, the selection and entry
point is displayed as * to indicate controller 2 instead
of -> to indicate controller 1.

Pleiger Elektronik
GmbH & Co. KG
Page: 16 Manual for 362MC Edition: 6/2007 Subject to modifications
See also Functional extensions - Disturbance compensation (C2) and Setpoint programme (C3)
in the Parameter Value (min Meaning Comment
profile each controller max)
CtrlTypCtrlTyp
CtrlTypCtrlTyp
CtrlTyp
2PntPW2PntPW
2PntPW2PntPW
2PntPW 2-Point controller with feedback See also Explanatory note on
3PntPW3PntPW
3PntPW3PntPW
3PntPW 3-Point controller with feedback controller types (5.5.1)
2Point2Point
2Point2Point
2Point 2-Point controller without feedback
3Point3Point
3Point3Point
3Point 3-Point controller without feedback
Step Step
Step Step
Step 3-Point step controller
Cont Cont
Cont Cont
Cont Continuous controller
CscStepCscStep
CscStepCscStep
CscStep Cascade step controller
Werte
ParSet ParSet
ParSet ParSet
ParSet 1 1
1 1
1 Parameter set selection The values of both parameter sets for
2 2
2 2
2 No. 1 or 2 of the controller concerned each controller are stored in the profile.
Parameter (1)/(2)The selected parameter set of the
(each set) selected controller is displayed.
StructStruct
StructStruct
Struct P P
P P
P Structure = P action only See also Explanatory note on
PI PI
PI PI
PI = PI action controller structure (5.5.2)
PD PD
PD PD
PD = PD action D component is always relative to
PID PID
PID PID
PID = PID action the system deviation and damped;
PD2 PD2
PD2 PD2
PD2 = PD action D2 component is always relative to
PID2 PID2
PID2 PID2
PID2 = PID action the controlled variable and damped.
Kr Kr
Kr Kr
Kr -999.0 -999.0
-999.0 -999.0
-999.0 P gain See also Explanatory note on
999.0 999.0
999.0 999.0
999.0 controller structure (5.5.2)
Tn Tn
Tn Tn
Tn 10s 10s
10s 10s
10s Reset time for I component See also Explanatory note on
10000s 10000s
10000s 10000s
10000s controller structure (5.5.2)
Tv Tv
Tv Tv
Tv 0.1s 0.1s
0.1s 0.1s
0.1s Derivative action time for D component See also Explanatory note on
1000.0s1000.0s
1000.0s1000.0s
1000.0s controller structure (5.5.2)
Vd Vd
Vd Vd
Vd 1.0 1.0
1.0 1.0
1.0 max. D gain for D component See also Explanatory note on
1000.0 1000.0
1000.0 1000.0
1000.0 controller structure (5.5.2)
T driveT drive
T driveT drive
T drive 5.0s 5.0s
5.0s 5.0s
5.0s Actuator operating time for step controller See also Explanatory note on
1000.0s1000.0s
1000.0s1000.0s
1000.0s controller output parameters (5.5.3)
Ts min Ts min
Ts min Ts min
Ts min 0.1s 0.1s
0.1s 0.1s
0.1s min. switching duration for switching output See also Explanatory note on
100.0s 100.0s
100.0s 100.0s
100.0s controller output parameters (5.5.3)
T cyclT cycl
T cyclT cycl
T cycl 0.1s 0.1s
0.1s 0.1s
0.1s min. cycle time for 2-Point and 3-Point See also Explanatory note on
100.0s 100.0s
100.0s 100.0s
100.0s controller with feedback controller output parameters (5.5.3)
DeadbdDeadbd
DeadbdDeadbd
Deadbd -1.0% -1.0%
-1.0% -1.0%
-1.0% Deadband for switching and continuous See also Explanatory note on
5.0% 5.0%
5.0% 5.0%
5.0% controller controller output parameters (5.5.3)
Hyst Hyst
Hyst Hyst
Hyst 0.0% 0.0%
0.0% 0.0%
0.0% Hysteresis for 2-Point and 3-Point See also Explanatory note on
10.0% 10.0%
10.0% 10.0%
10.0% controller controller output parameters (5.5.3)
Ymin Ymin
Ymin Ymin
Ymin -100% -100%
-100% -100%
-100% min. controller output See also Explanatory note on
100% 100%
100% 100%
100% controller output parameters (5.5.3)
Ymax Ymax
Ymax Ymax
Ymax -100% -100%
-100% -100%
-100% max. controller output See also Explanatory note on
100% 100%
100% 100%
100% controller output parameters (5.5.3)
Kw Kw
Kw Kw
Kw 0.0 0.0
0.0 0.0
0.0 Setpoint gain See also Explanatory note on
10.0 10.0
10.0 10.0
10.0 controller output parameters (5.5.3)
5.5 Controller parameters menu
This menu includes all the control-related parameters of the 362MC. In this menu the
controller type CtrlTyp is defined, the parameter set ParSet to be displayed and
possibly altered is selected and the structure of the controller Struct is set.
The parameters are then displayed directly in the same menu and, where appropriate, altered. The
menu thus ensures a complete overview of all values relating to the controller each time it is activated.

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 17
Controller 362MC Typ: 2PntPW Actuator Controlled system
W xd Y X
PID
Controller 362MC Typ: 2Point Actuator Controlled system
W xd Y X
PID
PID
Controller 362MC Typ: 3PntPW Actuator Controlled system
W xd Y X
PID
Controller 362MC Typ: 3Point Actuator Controlled system
W xd Y X
5.5.1 Explanatory note on controller types
The controller type CtrlTyp can be defined separately for each of the 362MC´s two controllers.
2-Point controller = switching controller with 2 switching output states, relay+ ON and relay+ OFF.
The 2-Point controller with feedback 2PntPW operates internally as a continuous controller with
down-line pulse-width modulator and switching output. Its output corresponds to the ratio of ON period
to OFF period of relay+ of assigned relay set 1 or 2.
In the case of the 2-Point controller without feedback 2Point the pulse-width modulator is replaced by
a threshold switch with hysteresis.
3-Point controller = switching controller with 3 switching output states, relay+ ON, relay+ and relay OFF
and relay- ON. The 3-Point controller with feedback 3PntPW operates internally as a continuous
controller with two down-line pulse-width modulators and two switching outputs. Its output corresponds
to the ratio of ON period to OFF period of relay+ if the controller output is positive and relay- if negative,
both relay+ and relay- being from assigned relay set 1 or 2.
In the case of the 3-Point controller without feedback 3Point the pulse-width modulator is replaced by
a threshold switch with hysteresis.
The two switching outputs can be parameterised separately, whereby the controller and output+ use the
complete 1st parameter set (1) and output- uses only the separate loop gain, Kr, and the parameters for
the switching outputs of the 2nd parameter set (2). See table:

Pleiger Elektronik
GmbH & Co. KG
Page: 18 Manual for 362MC Edition: 6/2007 Subject to modifications
PID I
PID
Kw2
Controller 362MC Typ: CscStep
Actuator Controlled system
+ Part A Part B
W xd Y1V Y2U X
- -
Parameter with
3-Point controller for with parameter
1st Parameter set 3-Point- CtrlTyp, Struct, Kr, Tn, Tv, Vd, Deadbd, Hyst, Ymin,Ymax, Kw (1)
switching output +
2nd Parameter set switching output -Kr, Deadbd, Hyst, Ymin,Ymax (2)
PID
Controller 362MC Typ: Step Actuator Controlled system
W xd Y X
I
Controller 362MC Typ: Cont Actuator Controlled system
W xd Y X
PID
This enables adaption of the 3-Point controller to two different actuators for outputs + and -. External pa-
rameter switching is not applicable here.
3-Point step controller = step controller for I-actuators with 3PntPW output
In conjunction with the down-line integrating actuator, the internal controller Step simulates a continu-
ous controller and has a 3-Point output with feedback. It is thus only suitable for use in combination with
integrating actuators, such as motor actuators.
(The operational characteristics of Step correspond to those of Pleiger controller 362-D)
Continuous controller = controller with continuous output.
The controller output of the continuous controller Cont is supplied to the assigned analogue output.
The required hardware configuration of the 362MC is to be observed.
(The operational characteristics of Cont correspond to those of Pleiger controller 361-D).
Cascade step controller = internal interconnection of 2 controllers to create the cascade controller
CscStep. Controller output Y1 of the primary controller, with setpoint W and actual value X, is injected
into the secondary controller as setpoint V. In addition to the controlled setpoint V, the secondary 3-Point
step controller also receives secondary actual value U to form output Y2.
With setpoint gain KW2 of the secondary controller can be employed, for example, to bypass the primary
controller during commissioning (Kr1=0 switches PID off, Kw2 results in W=V).

Pleiger Elektronik
GmbH & Co. KG
Edition: 6/2007 Subject to modifications Manual for 362MC Page: 19
CtrlTypCtrlTyp
CtrlTypCtrlTyp
CtrlTyp 2PntPW2PntPW
2PntPW2PntPW
2PntPW 3PntPW3PntPW
3PntPW3PntPW
3PntPW Step Step
Step Step
Step Cont Cont
Cont Cont
Cont
CscStepCscStep
CscStepCscStep
CscStep when controller
or or prim. contrl. sec. contrl. of type
2Point2Point
2Point2Point
2Point 3Point3Point
3Point3Point
3Point (Cont) (1)(Step) (2)
StructStruct
StructStruct
Struct P P
P P
P P P
P P
P P P
P P
P P P
P P
P these structures
PI PI
PI PI
PI PI PI
PI PI
PI PI PI
PI PI
PI PI PI
PI PI
PI PI PI
PI PI
PI PI PI
PI PI
PI are possible
PD PD
PD PD
PD PD PD
PD PD
PD PD PD
PD PD
PD PD PD
PD PD
PD
PID PID
PID PID
PID PID PID
PID PID
PID PID PID
PID PID
PID PID PID
PID PID
PID PID PID
PID PID
PID PID PID
PID PID
PID
PD2 PD2
PD2 PD2
PD2 PD2 PD2
PD2 PD2
PD2 PD2 PD2
PD2 PD2
PD2 PD2 PD2
PD2 PD2
PD2
PID2 PID2
PID2 PID2
PID2 PID2 PID2
PID2 PID2
PID2 PID2 PID2
PID2 PID2
PID2 PID2 PID2
PID2 PID2
PID2 PID2 PID2
PID2 PID2
PID2 PID2 PID2
PID2 PID2
PID2
Y
t
Kr
Tn
PI-Structure
Y
t
Kr
Tv/Vd
PD-Structure
Y
t
Kr
Tn
Tv/Vd
PID-Structure
Y
t
Kr
P-Structure
When the cascade step controller CscStep is selected, the primary continuous controller always uses
the 1st parameter set (1) and the secondary 3-Point step controller uses the 2nd parameter set (2).
5.5.2 Explanatory note on controller structure
The parameterisable structures for the presented controller types are shown in the following table. On
selecting a controller type, the display always shows only the structures which are parameterisable in
accordance with this table!
P controller (proportional-action controller)
In the case of the P controller, a value of the controller output Y is
directly proportionally assigned to each value of the system deviation
xd. The assigned value is set via the gain factor Kr (P gain).
Xp is frequently used instead of Kr. Xp=100 / Kr
PI controller (proportional-plus-integral action controller)
In the case of the PI controller, the value of controller output Y is set
proportional to the system deviation xd (P component), and the
I component, which corresponds to the time integral of the system
deviation, is added to this value. The I component is set via reset time
Tn, which corresponds to the time in which the I component effects a
change in the controller output of a magnitude corresponding to the
P component.
PD controller (proportional-plus-differential action controller)
In the case of the PD controller, a D-component corresponding to the
time differential of the system deviation is added to the controller
output component (P component) which is proportional to system
deviation xd. The D component is set via derivative action time Tv,
which specifies how much earlier the step response of a PD controller
corresponds to a value which is attained by a P controller. A low pass
with the time constant T=Tv / Vd is employed to limit the bandwidth of
the differential element.
PD2 controller (proportional-plus-differential action controller)
This functions in the same manner as the PD controller, whereby the
D2 component corresponds not to the time differential of system
deviation xd but to the time differential of controlled variable X.
PID controller (PI controller with added D component)
PID2 controller (PI controller with added D2 component)
Regarding the D component, see also:
Special function - Trend compensation (Appendix C1).
Other manuals for 362MC
1
Other pleiger Controllers manuals