Connect the product
NOTE! During installation Dimmer 1–10 V
outputs are not activated.
Use the app to configure before use.
Based on normal cable lengths and commonly available light fixtures
on the market.
*
Install the product in the appliance box behind the
push button/box lid or secure it with a Mounting clip
(MNT-01, not included) on the wall or DIN rail.
CTR-01 has a relay with an interrupting rating of 16 A with
a resistive load. Different loads have different input current
when switching on and voltage spikes when switching off.
The following table is recommended for different types of
lighting loads in order to ensure maximum service life.*
Maximum current 16 A.
Control inputs 1 and 2 can be used for control using:
- Push button (preset)
- Light switch
- Motion sensor (with neutral conductor)
The inputs can also be used to wirelessly control one
or more products from Plejd. A double click can be used
to activate lighting scenes.
The settings are easy to adjust in the app.
Control inputs 1 2
Load PF Rated output VA A
Halogen/incandescent (230 V) 13,500 W 3,500 16
LED loads 0.9 800 W 1,000 4
Fluorescent lamp uncompensated 0.3 700 W 2,300 10
Fluorescent lamp compensated 0.85 1,500 W 1,750 8
Low-voltage halogen electronic 0.8 1,500 W 1,750 8
Low-voltage halogen convenonal 0.95 1,200 W 1,200 5
Low-energy lamps 0.6 500 W 800 4
Support
Download the app and follow the instructions
Hand over the Plejd system
Hand over the Plejd system to your customer by writing
the system code on the included sticker . You’ll find the
code in the app once you have completed the installation.
Place the sticker in the distribution box and give the
welcome folder to the customer.
In the event of any technical questions, please contact
Plejd customer service.
HI!
1
2
3
Download the Plejd app via the App Store or Google Play.
After supplying power to the unit by following the relevant
wiring diagram, use the app to complete the installation.
This requires Internet connection and Bluetooth®on your
phone/tablet. You do not need any additional equipment
to get started.
It’s simple to configure all relevant settings in the Plejd app.
The app can be used to schedule the lighting using the
astro/time schedule, control lighting, and wirelessly sync
control switches and scenes.
Koppling för 0-10V bus
(utan brytning av
matning ll last)
Koppling för 1-10V bus
(med brytning av
matning ll last)
L
N
L
out
N
CTR-01
Koppling för
icke-dimbar last
(endast brytning av
matning ll last)
L
N
N L 1 2
L
L
N
Koppling för 0-10V bus
(utan brytning av
matning ll last)
Koppling för 1-10V bus
(med brytning av
matning ll last)
L
N
L
out
N
CTR-01
Koppling för
icke-dimbar last
(endast brytning av
matning ll last)
Coupling for 0–10 V bus
(without switching off
load to power supply)
Coupling for 1–10 V bus
(with switching off load
to power supply)
Coupling for
non-dimmable load
(only switching off load
to power supply)
1–10 V bus0–10 V bus
L
N
Koppling för 0-10V bus
(utan brytning av
matning ll last)
Koppling för 1-10V bus
(med brytning av
matning ll last)
L
N
L
out
N
CTR-01
Koppling för
icke-dimbar last
(endast brytning av
matning ll last)
L
N
N L 1 2
LN L 1 2
LN L 1 2
L
Load