PM Procom DES-P User manual

OPERATING INSTRUCTIONS DES-P
MRM PROCOM®Pvt Ltd
ISO-9001-2008 certified organization
Works:
Unit1 : E 41/5, Okhla Industrial Area, Phase II New Delhi -110020
Unit2: T-13, Okhla Industrial Area, Phase II New Delhi -110020
Ph: 011-30883538-41, 9810344265, 9310883837, Fax: 0-1130883536
Email: pankajgupta@mrmprocom.com, mrmprocom@gmail.com,
Web: www.mrmprocom.com

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 2/9

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 3/9
Index
1.0 Introduction
2.0 Protection, Supervision Salient features
3.0 Measurement & Display
4.0 Annunciations
5.0 Contacts
6.0 Timers
7.0 Switches Description
8.0 Operation
9.0 Setting Procedure
9.1 Parameter Settings
9.2 Fault History Viewing
9.3 Service Hour Resetting
9.4 Programming Solenoid Mode
10.0 Faults
10.1 Internal Faults
10.2 External Faults
10.3 Fault Reset
12.0 Terminal description
13.0 Model selection
14 .0 Specifications
15.0 Connection Diagram

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 4/9
1.0 Introduction
•16 Bit RISC, state of art,
microcontroller based System.
•True RMS measurement of all
measured parameters with 1% accuracy
of measured value (Not full scale)
•Backlit LCD Display for easy reading
and parameter settings. No need to
consult the manual while programming
the unit.
•All the inputs, such as Generator and
Battery voltages are fully isolated,
providing the freedom to design a
totally isolated system. This avoids and
prevents malfunctioning/ burning of the
unit.
•Fully operational up to 4V. Can
withstand a voltage dip up to 0V for
1sec.
•All system parameters are user
programmable
•Measurement and display of LLOP,
Fuel Level and HWT
•Records last 20 faults
•Suitable for all types of engines
•All digital inputs are optically isolated
for enhanced reliability
•All outputs are through potential free
contacts for system stability and
reliability
•All contacts are protected by TVS to
strengthen the EMI/EMC capabilities of
the unit.
•Housed in 92X92mm Din Standard
housing.
2.0 Protection, Supervision Salient features
•Oil Pressure
•HWT
•RWL
•Emergency
•Low Fuel
•Charging Alternator Fail/V-Belt
•Choice of selective sensor measurement
display
3.0 Measurement & Display
DES-P equipped with LCD display and displays
•Battery Voltage
•Generator Run Hour
•RPM
•Oil Pressure in KG/cm2
•Water Temp in degree centigrade
•Fuel Level in %
•Programmed settings
•Service Hour
Normally the display auto scrolls and displays a set of parameter for 10 seconds, but any time the
Next key (Ï) can be pressed to select the next parameter window.
4.0 Annunciations
DES-P is equipped with the following annunciations for system status and faults:
•LLOP
•HWT
•Low Fuel
•RWL
•Charging Alternator/ V-Belt
•Emergency
5.0 Contacts
The following digital Output are provided. Annunciation contacts are available in models requested
with Annunciation features.
•Crank (NO Contact)
•Solenoid (NO Contact)
•Hooter (NO Contact)
•Electrical Feed for Charger ON (+12V)

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 5/9
6.0 Timers
DES-P is equipped with the following timers:
•Stop Solenoid on time
•Fuel supervision time
•LLOP Supervision Time
•HWT supervision time
•RWL supervision time
•Hooter Reset Time
•Service Time Hour
•Ch- Alt on contact timer
•Crank Time
•Over Speed Supervision Time
7.0 Switches Description
DES-P has 4 switchs on its front panel. Switch can have more than one functions assigned to them.
The table below describes the operation of these.
S.No. Switch Symbol Switch Function Description
1
©
Next Normal operation mode: In this mode, it is used to
change the parameters being displayed on LCD.
Programming Mode: Next key is used to select the next
parameter to be programmed.
2
®
Increment Programming Mode: It is used to increment the value
of the parameters under programming.
Normal operation mode: It is used to Start the Engine
3
-
Decrement Programming Mode: It is used to decrement the value
of the parameter under programming.
Normal operation mode: It is used to Stop the Engine
4 R Reset Reset key resets the Hooter and Fault signals.
The first press shall reset the hooter and next shall reset
the faults. A long press of 1 Sec shall reset both.
5 R&
©
Programming
Mode Entry Press “R” Key and than press “
©
” while the “R” Key is
pressed to enter the programming mode.
8.0 Operation.
DES-P is an engine monitoring and supervisor unit.
The engine can be Started/Stopped from the front panel of DES-P or externally by means of key
Switch etc. The Start / stop from the front or remote is one touch operation, meaning that once the
switch is pressed the Crank/ fuel solenoid shall be operational till the “Crank Time / Stop Sol Time”
, as programmed, has expired . DES-P automatically detects that the engine on conditions by
monitoring engine speed . On detection of any of these faults for the pre-programmed duration the
engine is automatically shut down and fault along with run hour is recorded in non-volatile memory.
The run hour time of engine is recorded in internal non-volatile memory.
9.0 Setting Procedure
DES-P has provision to program the operating parameters, resetting the service hours and viewing
the last 20 fault history.
Press R &
©
switches simultaneously.
The LCD shall display, “Enter Para Mode”
To enter parameter setting mode press
©
.
To go to next menu press
®
.
The LCD shall display “View Fault Records”.
This menu can be entered by pressing
©
.
To go to next menu press
®
.
The LCD shall display “Reset Service Hours”.
This menu can be entered by pressing
©
.
Pressing
®
, shall reset the service hours. Pressing
-
shall terminate the menu.

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 6/9
9.1 Parameter Mode
Sl.
No Display Explanation of parameter Factory
setting Setting Range
1 Engine Max
RPM Max. permissible RPM, above this the
RPM is treated unhealthy & the
Generator is stopped.
1650 300-3000
2 Engine O/RPM
Delay The time for which the Generator RPM
should, continuously be unhealthy to
generate a fault condition.
10Sec 1-999 Sec.
4 Engine Vbelt
RPM Max. permissible Vbelt RPM, above this
the RPM is treated unhealthy & the
Generator is stopped.
300 300-600
5 V belt Delay The time for which the Vbelt RPM
should, continuously be unhealthy to
generate a fault condition.
10Sec 1-999 Sec.
6 Available
Sensor This select the installed sensors in the
Gensets. The display shall only display
the parameters for the sensor installed
and uninstalled sensor data shall not be
displayed. The protection for the function
with no measurement sensor installed
shall be through switch. Eg. If Oil
pressure sensor is not installed the unit
shall provide protection for LLOP
through oil pressure switch and not
through the oil pressure sensor (linear
measurement)
All sensors All sensors,
Fuel &HWT,
Fuel & LLOP,
LLOP & HWT,
Fuel Only,
HWT Only,
LLOP Only,
No sensor
7 Fuel Level in % Level of fuel at which the Engine shall
shut down 11% 10-100%
8 Low Lube
Pressure Level of LLOP at which the Engine shall
shut down 1.0 Kg
/Cm2 0-8.5 Kg /Cm2
9 High Water
Temp Temperature of water at which the
Engine shall shut down 95 0-150
Degree centigrade
10 Sensor Type Select sensor as in accordance with enine
A A,B
11 Fuel << delay Monitoring time of Fuel Fault 5 Sec 1-999Sec
12 LLOP delay Monitoring time of LLOP Fault 5 Sec 1-999 Sec
13 HWT delay
Monitoring time of HWT Fault 5 Sec 1-999 Sec
14 Rad. Water
Delay Time for which Radiator water level has
to be active before issuing shut down
command
5 Sec 1-999 Sec
15 Hooter Reset
Time/
Heater On time
Time for which the Hooter is active if not
reset manually/ Time for which heater is
to be switched on before crank
30 Sec 1-999Sec
16 Stop Sol On
Time Time for which the fuel solenoid is
activated for shutting the engine 20Sec 1-100Sec
17 Gen Pick Up
Vol Voltage of generator above which the
generator is assumed to be ON. 100V 80-150V
18 Service Time
Hr Time, in hours, after which the service is
due. 250Hrs 1-999 Hrs

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 7/9
19 Disp Auto Scroll Setting ON will enable Auto Scroll of
display.
OFF: No scroll and next parameter can
be viewed by pressing next
ON ON/OFF
20 Emer Sol Time This setting is to protect the fuel solenoid
in case the Stop button or Emergency is
kept pressed. In such a case the solenoid
shall be released after this time.
22 Sec 1-100Sec
21 RPM Ratio Gear ratio multiplier for charging
alternator. 1.00 0.5-1.5
22 Crank Time Maximum Permissible Crank Time 5 Sec 1-25 Sec
* This parameter can be disabled while programming
9.2 Fault History.
To view the last 20 fault history enters in this mode as explained above. Maximum of last 20
faults along with Run Hour stamp shall be displayed on the LCD. The first row shall display
the fault and the next row shall display the run hour at which the fault has occurred. The next
fault can be viewed by pressing “NEXT”. The mode shall exit to normal mode after the last
fault recording is displayed. Absence of any fault recoding shall not display any fault data.
9.3 Resting Service Hours.
Service due, warning is issued by DES-P, by flashing the Ser LED. This LED shall keep
flashing till it is not reset by entering this mode. Pls refer Para 9 for procedure to reset service
hour
9.4 Programming Solenoid Mode
For changing the solenoid mode first press (R) (reset) button, than press + button while
the reset button is pressed.
Fuel Solenoid: In this mode fuel solenoid contact changes from Open to Close at the
time of cranking and remains close till the engine is running. For stopping the generator
this contact opens.
Stop Solenoid: In this mode fuel solenoid contact remains open at the time of cranking
and till the genset is running. For stopping the engine this contact closes for a user
programmed time.
Don’t change the mode while engine is running. It’s a good practice to switch OFF and
than switch ON the battery supply after changing this mode.
10.0Faults
There are two categories of faults
Internal Faults
External faults
10.1 Internal Faults
Internal faults are the faults, which do not need any external signals and are detected by the system
itself. They are:
LLOP
Fuel
HWT
10.2 External Faults
Those faults which cannot be sensed by the unit itself (these faults are not reflected by the engine
directly) and are to be provided externally. They are:
RWL

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 8/9
10.3 Fault Reset
All internal faults can be reset by pressing (R) switch after the generator is stopped. In case the
engine fails to stop “STOP KEY” can be pressed for manual attempt to stop engine.
11.0 Terminal description
Terminal Number Description
1 Not Connected
2 Not Connected
3 Not Connected
4 Not Connected
5 LLOP Sensor
6 HWT Sensor
7 Fuel Sensor
8 RWL
9 Charging Alternator Input
10 Auxiliary supply +ve
11 Auxiliary supply -ve
12 Crank NO Contact
13 Solenoid NO Contact
14 Charging Alternator On
15 Hooter
16 Common for All Contacts
17 Remote Start
18 Remote Stop
19 Not Connected
20 Not Connected
21 Not Connected
22 Not Connected
23 Not Connected
24 Not Connected
12.0 Model Selection
The nomenclature for selecting the model is as follows:
DES-P
13.0Specifications
Surge 1.2/50Usec 2.5KV
Battery Voltage Suitable for 12V/24 VDC System
Min. voltage to power on 9V
Min Running Voltage after Power on 4V
Max. Battery Voltage 35V
DC Interruption time 1 Sec.
Digital Output + 12V
Cut out Dimensions 92mm X 92mm
Depth 120mm
Digital Input Level Battery –Ve except Charging Alt, which is
battery + Ve

DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 9/9
14.0 Connection Diagram :
It is our endeavour to constantly upgrade our products, hence specifications are subject to
change without any notice.
1
2
3
4
5
6
7
8
9
10
11
12
1
3
1
4
1
5
1
6
1
7
1
8
19
20
21
22
23
Not Connected
Not Connected
Not Connected
Not Connected
Oil Pressure
Sensor/Switch
Water Temp.
Sensor/Switch
Low Fuel
Sensor/Switch
RWL Switch
Ch Alt +Ve /
Wpoint
DC Battery
+Ve
DC Batter
y
-Ve
Crank /start
Solenoid /Stop
Charging
Alternator ON
Hooter
Common for
12,13,14,15
Remote Start
Remote Stop
Not Connected
Not Connected
Not Connected
Not Connected
Not Connected
23
Not Connected
Table of contents
Popular Controllers manuals by other brands

Kessler
Kessler SECOND SHOOTER PLUS user guide

Carrier
Carrier 50CO Series Installation, operation and maintenance instructions

maturo
maturo NCD manual

ABB
ABB RHD250 operating instructions

Leantechnik
Leantechnik Lifgo 5.0 INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE

Huawei
Huawei SmartACU2000D Series quick guide