DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page 5/9
6.0 Timers
DES-P is equipped with the following timers:
•Stop Solenoid on time
•Fuel supervision time
•LLOP Supervision Time
•HWT supervision time
•RWL supervision time
•Hooter Reset Time
•Service Time Hour
•Ch- Alt on contact timer
•Crank Time
•Over Speed Supervision Time
7.0 Switches Description
DES-P has 4 switchs on its front panel. Switch can have more than one functions assigned to them.
The table below describes the operation of these.
S.No. Switch Symbol Switch Function Description
1
©
Next Normal operation mode: In this mode, it is used to
change the parameters being displayed on LCD.
Programming Mode: Next key is used to select the next
parameter to be programmed.
2
®
Increment Programming Mode: It is used to increment the value
of the parameters under programming.
Normal operation mode: It is used to Start the Engine
3
-
Decrement Programming Mode: It is used to decrement the value
of the parameter under programming.
Normal operation mode: It is used to Stop the Engine
4 R Reset Reset key resets the Hooter and Fault signals.
The first press shall reset the hooter and next shall reset
the faults. A long press of 1 Sec shall reset both.
5 R&
©
Programming
Mode Entry Press “R” Key and than press “
©
” while the “R” Key is
pressed to enter the programming mode.
8.0 Operation.
DES-P is an engine monitoring and supervisor unit.
The engine can be Started/Stopped from the front panel of DES-P or externally by means of key
Switch etc. The Start / stop from the front or remote is one touch operation, meaning that once the
switch is pressed the Crank/ fuel solenoid shall be operational till the “Crank Time / Stop Sol Time”
, as programmed, has expired . DES-P automatically detects that the engine on conditions by
monitoring engine speed . On detection of any of these faults for the pre-programmed duration the
engine is automatically shut down and fault along with run hour is recorded in non-volatile memory.
The run hour time of engine is recorded in internal non-volatile memory.
9.0 Setting Procedure
DES-P has provision to program the operating parameters, resetting the service hours and viewing
the last 20 fault history.
Press R &
©
switches simultaneously.
The LCD shall display, “Enter Para Mode”
To enter parameter setting mode press
©
.
To go to next menu press
®
.
The LCD shall display “View Fault Records”.
This menu can be entered by pressing
©
.
To go to next menu press
®
.
The LCD shall display “Reset Service Hours”.
This menu can be entered by pressing
©
.
Pressing
®
, shall reset the service hours. Pressing
-
shall terminate the menu.