PMC M20d Series User manual

M20d Series
Temperature & SVG Controller
USER’S MANUAL
For
avoid wrong operation to make human injured or machine damage,
pleas
e read this instruction carefully before use the instrument.
Ver. 3.3a


-1-
WARRANTY
We warrant that this product will be free from defects in materials and workmanship for a period of two (2)
years from the date of shipment. If any such product proves defective during this warranty period, we, at our
option, either will repair the defective product without charge for parts and labor, or will provide a replacement
in exchange for the defective product.
This warranty shall not apply to any defect, failure or damage caused by improper use or improper or
inadequate maintenance and care. We shall not be obligated to furnish service under this warranty; a) to repair
damage resulting from attempts by personnel other than our representatives to repair or service the product; b)
to repair damage resulting from improper use or connection to incompatible equipment; or c) to service a
product that has been modified or integrated with other products when the effect of such modification or
integration increases the time or difficulty of servicing the product.
This warranty excludes replacement of fuses, triac, calibration, contact points and damage to the module
from the use of improper styles of fuses. The maximum allowable fuse rating is 15 amps. Lower ratings
may be used for improved protection.
SAFETY
Our products have been designed to be safe and simple to operate. As with any electronic equipment, you must
observe standard safety procedures to protect both yourself and the equipment.
Service and installation of this equipment should only be performed by qualified service personnel familiar
with high voltage electrical circuits.
All national and local electrical codes must be followed when connecting this equipment.
Only persons with knowledge of the system's operation and capabilities should operate the system.
Read all of these instructions before connecting power and turning on the system.
Unless specifically explained in this manual or directed by us, do not attempt to repair the system yourself.
Doing so could result in damage to the system, or serious personal injury.
Do not apply voltage to a terminal that exceeds the range specified for that terminal.
Do not connect thermocouples to any live areas of the heaters. Lock out and tag the controller and mold and
make sure there is electrical insulation between the thermocouple and any live areas.
Do not operate this product from a power source that applies more than the voltages specified.
Do not operate this product with covers or panels removed. All unused slots of a main frame must be
covered with the appropriately sized blank panels.
Do not operate this product when wet.
Do not operate this product in an explosive atmosphere.
CAUTIONS
When turning on the system, you should turn on all circuit breakers before power on the HMI. You may
experience communication issues if you do not obey this sequence.
After turning on the system, you should make sure that fans are running.
Never allow the fan outlets on the unit become blocked, This is where the system's cooling airflow exits. If
this area of the mainframe becomes cluttered and insufficient airflow or the system maybe damaged.
When switching off the system, you must wait 30 seconds before switching on. You may experience
communication issues if you do not wait the required 30 seconds.

-2-
Chapter 1 Introduction
1.1 M20 Series Mainframe Configurations
The M20 controller is made up of 4 different models of mainframes which change based on the number
of zones required. These are referred to as M20-XS, M20-S, M20-M, and M20-L.
All of the mainframes employ the same temperature control module M20-M2, and the same sequence
valve gate control module M20-V2.
Access to all users’ serviceable parts, including fuses, are done through the front of the controller by
loosening the upper and lower screws on each heat sink and using the attached tool or screw driver to
lever the module out.
The connectors for the mold-power and thermocouple cables, and the connectors for valve gate control
cables, are located at the rear of the mainframe.
Typical M20 Mainframes
M20-XS M20-S M20-M M20-L
1.2 Control Modules
M20-M2 temperature control module come standard with two zones at 15amps per zone.
M20-V2 sequence valve gate control module can control six valve gates each module.
The modules are fully interchangeable across all mainframe designs. The externally mounted heat sink
and integrated design reduce maintenance cost and downtime.
(1) Power indicator: green, lighted when power on.
(2)&(3) Zone A & Zone B status indicator:
green – stop; red – running;
blink fast – communicating with HMI;
green /red alternately: alarm
(1) Power indicator.
(2) Injection signal indicator.
(3) Output indicator.
M20-M2
M20-V2

-3-
1.3 Specifications
Model
M20-XS
M20-S
M20-M
M20-L
User Interface
Full color LCD touch screen
Display Size
7.0"
7.0" / 10.2"
10.2"
Max. Total Zones
24
32
80
120
Max. Temp. Zones
24
32
80
120
Max. Sequence Zones
24
24
24
Power Supply
3-Ph+E(4 wire) 200-240Vac
3-Ph+N+E(5 wire) 380-415Vac
Working Conditions
0~55℃(32~131℉), 10~80%RH (No condensing)
Storage Conditions
-20~70℃(-4~158℉), 10~80%RH (No condensing)
Temperature Control
Control Mode
Auto-PID / Manual
Measurement Range
0~500℃(32~932℉)
Output Control
Zero Cross / Phase Angle
Setting Range
0~450℃(32~842℉)
Thermocouple
J or K-Type,
software selectable
Temperature Unit
℉or ℃,
software selectable
Calibration Accuracy
±0.25% FS
Control Stability
±1digit-under steady state
Load Capacity
Rated 240Vac, 15A/zone
Overload Protection
Fuses on both heater legs
TC Connector
Varies options available
Soft-Start
Using low voltage for heater
dehumidify
Mold Power Connector
Varies options available
Sequence Valve Gate Control
Trigger Signal
DC24V or Dry contact
Trigger Mode
4 modes selected
Screw Position Signal
DC 0~10V
Screw Position Unit
mm or inch
Control Mode
Auto / Manual
Time Resolution
1s, or 0.1s, or 0.01s
Output Signal
DC24V, or AC220V
or Relay contact
Output Connector
Varies options available

-4-
1.4 Features
Cabinet
HMI
Temperature only, SVG only, or Combination
Full color LCD touch screen
Max. 120 zones
English/Spanish/Chinese
CE compliant
Fixed on mainframe or Stand-alone
Control Modules
Alarms & Protection
“All in one” control module
Sensor broken /reversed /shorted /mis-connected
2-zone per temperature module (15 Amp per zone)
Load broken /shorted /over-rated
6-gate per SVG module
Temperature over high /under low
Other Functions
Fuse blown
Stopping system remotely (optional)
Heating invalid
Standby system remotely (optional)
Triac breakdown
All zones’ temperature in tolerance output (optional)
Power supply over-voltage
Start sequence in group
Cabinet temperature over-setting
Sensor fault solution
Alarm output (optional)
1.5 Typical Thermocouple & Mold Power Connectors Wiring
Thermocouple & Mold Power Combination Wiring
Wiring Mode 1 Wiring Mode 2
Thermocouple & Mold Power Separated Wiring
Wring Mode 3 Wiring Mode 4

-5-
1.6 Typical Sequence Trigger & Output Connectors Wiring
SVG Input Wiring
SVG Output Wiring
Signal
Pins
Description
Type
Trigger
Input
1 & 2
Sees a closed condition or DC24V as a signal to start
the timer on the valve sequence
Normally Open Dry Contact
Or DC24V
Screw
Position
3 & 4
Accepts a voltage source input that relates to the main
screw position.
A calibration routine within the controller adjusts
actual input to actual screw position.
0 to 10 Volts
1.7 Typical Remote Input & Alarm Output Connectors Wiring
Remote Input Wiring
Alarm & Normal Output Wiring
Signal
Pins
Description
Type
Standby
Signal
1 & 2
After a delay time (adjustable) since the contact is
closed, the controller will work in standby mode until
AUTO button is pressed on HMI.
Normally open dry contact
Stop Signal
3 & 4
When the contact is closed, the controller will stop
running, same as pressing STOP button on HMI.
Normally open dry contact
Alarm
Output
1 & 2
Contact is closed when any alarm happens, and it will
be reset by silence button on the alarm history page.
Normally open dry contact
1A/250Vac
Normal
Output
3 & 4
Contact is closed when all zones’ temperature are in
normal output tolerance.
Normally open dry contact
1A/250Vac

-6-
1.8 System Wiring (only temperature control)
(power wiring depends on the voltage specification)

-7-
1.9 Power Wiring
3-Ph+N+E (5 wire) 380-415Vac
3-Ph+E (4 wire) 200-240Vac

-8-
Chapter 2 Inspection & Installation
2.1 Unpacking and Inspection
1. After unpacking, inspect the mainframe and check for any damage that may have occurred during
shipment.
2. Check the circuit breaker disconnect and neon phase voltage indicators for damage.
3. Check for proper operation of circuit breaker by flipping breaker on and off with no voltage applied.
4. Check connectors for any physical damage.
5. Check AC input power specification. The power specification label is located on the back cover of
the mainframe’s power input terminal block. The label indicates the input voltage configuration that
was prewired at the factory. Make sure it matches what you ordered.
6. Inspect the HMI and check for any damage that may have occurred during shipment.
7. Check power connector/cable and communication connector/cable of HMI for any physical damage.
2.2 Mounting the HMI (only M20-M Series)
1. Connect the HMI’s power cable and communication cable to corresponding plug on the mainframe.
2. Mount the HMI on the mainframe by screws provided.
Connecting the HMI (only Standalone HMI)
1. Place or mount the HMI on the position required.
2. Connect the HMI and the mainframe with communication cable.

-9-
2.3 Connecting the Power Cable (except M20-XS, M20-S Series)
1. Select the power input wire size according to the load power, and the national and local electrical
codes. (if required)
2. Remove the metal cover of the power input terminal block by removing screws around its perimeter.
3. Remove the plastic panel of the terminal block.
4. Insert power input cable through access hole provided on the cover. (if use this type cover)
5. Connect AC input cord to the input terminal block as shown on the inner-side of cover, for the input
voltage configuration you are attaching to.
6. Connect the earth cord to the ground terminal beside the input terminal block.
7. Cover the plastic panel on the terminal block.
8. Take up excess slack in cable and secure with strain relief clamp provided on the terminal block
cover. (if use this type cover)
9. Mount the metal cover of the power input terminal block on the mainframe.
(1) (2) (3)
(4) (5)
CAUTIONS!
Service and installation of this equipment should only be performed by qualified service personnel
familiar with high voltage electrical circuits.
All national and local electrical codes must be followed when connecting this equipment.
Should use O-type terminal on the power input cord connected to the terminal block.
Do not apply power to this cable or the unit when the back terminal block cover is removed.
Do not connect AC power input cord to your in-plant power distribution system until the back
terminal block cover is securely in place.
Make sure that the chassis has been earth grounded before applying power.

- 10 -
Chapter 3 Connecting the System to the Mold
3.1 Prior to Start Up
●Check that the system is completely disconnected from the power source.
●Clean up any water, oil, dirt, cleaning fluids etc. that may have spilled during a mold change or since
the last production run.
●Check all of the cable connections between the system and the mold (if required). Make sure all of the
cables are free from wear or damage.
●Check that the earth/ground connection is in good condition. Verify the system and the mold have the
same ground reference.
●Check if the wiring mode on mainframe is same as on mold.
●Confirm that the sequence valve gate control output meets the requirement of the valve.
●Confirm that the sequence trigger signal meets the requirement of the controller.
3.2 Verifying the Connection
1. Connect the thermocouple and mold power cables (if required).
2. Connect the sequence trigger signal cable and output cable (if required).
3. Using an Ohmmeter, touch one test lead to the mold and the other to the mold ground terminal on the
system. Resistance must be less than 1Ω.
4. Check all the circuit breakers and make sure they are in the OFF position prior to connection of the
controller to the power source.
3.3 Startup Procedure Checklist
1. Connect mold power & thermocouple cables, sequence control cables between the mold and
controller (if required).
2. Connect the controller to the power source.
3. Switch the circuit breakers ON.
4. Turn on the HMI, then select the language.
5. Log in the system (if required).
6. Load a mold setup (if required).
7. Checking the mold setup zone by zone on HMI.
8. Correct any faults found during diagnostics.
9. Touch “Run” to start the system.
10. Check that the controller is functioning correctly.
IMPORTANT!
When switching off the system, you must wait 30 seconds before switching on. You may experience
communication issues if you turn off and on the system incorrectly.

- 11 -
Chapter 4 Operator Interface
4.1 Main Interface
The main interface is used to monitor, log in the system and general operations.
4.1.1 Temperature Control
Icon Button Mode, 24-zone per page, Resolution 0.1 is not checked
Icon Button Mode, 42-zone per page, Resolution 0.1 is checked

- 12 -
● Function Button:Icon mode is the default setting, Text mode can be selected on system setting page.
● 24 or 42 zones per page:24-zone is the default setting, can be alternated on system setting page.
● Resolution:1 is the default setting, 0.1 can be selected on system setting page.
⑴Zone number. ;’
⑵Zone status: alarm information is in red, e.g. No.2 zone.
⑶Actual Temperature (PV):
● resolution 0.1 can be selected on system setting page.
● displayed in red in stop state, e.g. No.3 zone.
● if thermocouple is open, 999 is displayed, e.g. No.2 zone.
● if zone is turned off, OFF is displayed in red, e.g. No.4 zone.
● blinking when communication fails.
● click it to set zone’s parameters and operate it.
⑷Setpoint (SV):
● temperature unit can be selected between Celsius and Fahrenheit by Engineer’s parameter.
● displayed in red in stop state, e.g. No.3 zone.
● output percent setting will be displayed in manual mode, e.g. No.1 zone.
● click setting value, output percent and load current can be alternated to show in 42-zone page.
⑸Power output % .
⑹Sensor type: can be selected between J-type and K-type thermocouple by Engineer’s parameter.
⑺Load current.
[Run](green)/[Stop](red): Run or Stop temperature & valve gate control of all zones.
In Stop mode, shows Run; and in Run mode, shows Stop.
[Auto]: Place the temperature control of all zones in Auto mode.
[Standby]: Place the temperature control of all zones in Standby mode.
In this mode, the target is 70% of setpoint.
[PgUp]: Used to view the previous page.
[PgDn]: Used to view the next page.
On the last page, you will see [SVG]
[SVG]: Shift to the sequence valve gate control interface.
[Graph]: Used to view the real-time or history data curve.
[Alarm]: Used to view the alarm record.
[Group]: Enter the group/global setting, pattern/mold files management, and language selected .
[System]: Used to enter the system setting.
[Login]/[Logout]: Used to log in/out the system to achieve the different authority.

- 13 -
4.1.2 Sequence Valve Gate Control
(Icon Button Mode)
[Run](green)/[Stop](red): Run or Stop temperature & valve gate control of all zones.
In Stop mode, shows Run; and in Run mode, shows Stop.
[Auto]: Place the sequence valve gate control of all zones in Auto mode.
[Manual]: Place the sequence valve gate control of all zones in Manual mode.
In this mode, each valve gate can be opened or closed by manual.
[Temp]: Shift to the temperature control interface.
[Graph]: Used to view the open & close sequence setting of all gates.
[Group]: Enter the group/global setting, pattern/mold files management, and language selected .
[TEST]: Used to simulate the trigger signal to test all valve gates control.
[Login]/[Logout]: Used to log in/out the system to achieve the different authority.
⑴Gate Number.
⑵Working Status.
⑶Valve Gate Status:
Open, Close or OFF (when zone is set to off).
⑷Control Mode: Auto or Manual.
In Manual mode, touch it to open/close gate.
⑸Start Trigger Indicator: green--off, red--on.
⑹Output signal: 24V or 220V (selected on modules)
⑺Screw position: unit is mm or inch,
selected in screw position’s calibration.

- 14 -
4.2 USB Port
The USB port on the M20 series is intended to be used to copy pattern (mold) setup files to and from the
system. The screen for importing or exporting mold setups is displayed in the Group Setup Screen.
These mold setup files can be copied to other M20 controllers that support the same file type.
The USB port is also be used to export the historical data record (in csv format) from the system. The
screen for exporting data record is displayed in the History Data Curve Screen.
CAUTION!
Never power on with a device in the USB port.
Never connect a powered hub or other device to the USB port.
Removing the USB disk from the system during a read or write operation could cause data corruption
to the USB disk contents that could result in bad files or the entire drive from being usable.
The following warnings and restrictions should be observed when using the USB port:
Only supports USB disks that use a File Allocation Table (FAT or FAT32) format.
Only supports USB versions 2.0 and 1.1.
Use an empty USB disk or one that contain as few files as possible.

- 15 -
Chapter 5 Security & System Setting
5.1 Login / Logout the System
In order to avoid accidents happened, and protect the system data, different level operators have different
authorities.
To achieve the corresponding authority, the operator should login the system by his or her user name and
password before operation.
And he or she should logout the system after finishing operations, in order to avoid other people
mis-operate the controller by his or her name.
In the absence of user login status, the main interface displays [Login]. Touch it to open
the Login screen, select the corresponding user name and input password to login the system.
In the status of the user login, the main interface shows [Logout]. Touch it and the system
opens a dialog box to confirm your operation. You can click [Yes] to logout the system.
User’s Authorities List
User Group
Authorities
Remarks
Non-Login
Select language.
View data curve, alarm records.
Mute when alarms.
Authorized to Change Setpoint
All authorities above.
Run/Stop system or zone.
Auto/Standby system.
Change the zone temperature setpoint.
Everyone Can Change Setpoint
Operators
All authorities of Non-Login.
Choose control mode.
View module types and status.
Set system time/ auto-pager time.
Set authority for operators not to login.
Check the system log.
Clear all data records.
Select display resolution, button mode, etc.
Set temperature setpoint or unit globally.
Run/Stop/Set setpoint in group.
Initial password is "1"
for the user “Operator”.
Engineers
All authorities of Operators.
Modify all parameters of zones.
Set sensor default solutions.
Set heating speed related.
Set data save interval time.
All operations in global setting.
Initial password is "654321"
for the user “Engineer”.
Administrators
All authorities of Engineers.
Manage the users and authorities.
Select OAID display, used to maintenance.
Auxiliary functions setting.
Initial password is "87654321"
for the user “Director”.
The user “Administrator”
is reserved.

- 16 -
5.2 System Setting
Touch [System]on the main interface of temperature control, then you can enter the System
Setting Screen.
5.2.1 Security
● Authorization: You can manage the users, include add, copy and delete user.
You can also check the user’s properties.
The user’s name allows to be edited.
There 3 User Groups: operators, engineers and administrators.
Each group has different authorities. And you can create more than one user in each group.
Operators: Authorized to use the functions related to production process.
Engineers: Authorized to use all functions except manage users and Clear or Auto-generate
the Module’s ID.
Administrators (the user same named cannot be deleted): All authorities.
● Change Password: You can change the password for the current user.

- 17 -
● Authorized to Change Setpoint / Everyone Can Change Setpoint:
Touch it to change the authority setting for operators not login.
Display Authorized to Change Setpoint:
It means current setting is Everyone Can Change Setpoint.
Operators not login the system can run/stop the system, and change the setpoint.
Display Everyone Can Change Setpoint:
It means current setting is Authorized to Change Setpoint.
Only the operators login the system can run/stop the system, and change the setpoint.
5.2.2 Time
For the system time initialization, the setting method is:
1) Click the parameters required to set, then you can input the value by small keyboard on the screen.
2) Click the [OK], and you can finish the modification.
NOTE: If there is no response after you click the parameter values, it indicates that this parameter cannot
be modified.
5.2.3 Cabinet Temperature & ID
Display the current max. cold-junction temperature (ambient temperature in the cabinet) of all modules,
and its zone number.
5.2.4 System
● Data Saved Interval: After the setting time, the system saves the data automatically.
0 min. means not to save the data, and you cannot see the history curve.
● Auto Pager Time: After the setting time, main interface displays the next page automatically.
0 sec. means not to auto pager.
● System Log: By clicking it, you can check the system operation log.

- 18 -
5.2.5 Other ( blue - unchecked, green - checked)
● Keep the data: Zones’ work state (Auto or Manual, and power output % in manual mode) will be the
same as before power off when re-start and run the system.
● Button text: Function Buttons will be showed by TEXT mode instead of ICON mode.
● OAID display: Zone’s original ID displayed, used for maintenance.
● Resolution 0.1: Present temperature’s display resolution is 0.1.
5.2.6 Control Modules
Display the communication status of each module and its type.
● Reset Cumulative Run Time: used for remote communication.
5.2.7 Auxiliary Functions ( blue - unchecked, green - checked)
Touch , you can enter Aux-function configuration page.
Appointed zone’s number:
Its power supply voltage will be displayed in status bar on main interface.
Over voltage halt:
When the power supply voltage is high alarm, the system will stop running.
Remote stop control:
When the system receives external stop signal, it will stop running.
Remote standby control & Standby (delay) time:
After a standby (delay) time since the system receives external standby
signal, it will work in standby mode until AUTO button is pressed on HMI.
Mold test: reserved..
5.2.8 42-zone / 24-zone Display in One Page
Touch , you can alternate 24-zone and 42-zone displayed in one page.
5.2.9 Clear Operation Log & Historical Data
Touch [Clear], you can clear all operation log and all historical curve data.
5.2.10 Sensor Fault Solution
You can appoint a zone as another zone’s sensor fault reference. Generally, the sensors of these two zones
are near to each other.
When the sensor of Major ID is failed, the controller will use the temperature of Related ID to simulate
the failed one, and finish the temperature control of Major ID.
This function can be enabled or disabled according to requirements.
This manual suits for next models
4
Table of contents