2
Thankyou forpurchasing ourUPS,itissafeand liable,needsfewmaintenance.
Thismanualincludesinstructionsofsafetyinstallationand operation,theyhelpyourUPStohavethe
longest servicelife.Thismanual alsoaccountsthe UPSwork principleand relativefunctions.
Pleaseobeythe instructionsand notesstated inthismanual.Keep thismanualinasafeplace,consult
itbeforeoperation.
Safetyrules
Evenif notconnected tomainpower, high voltage maystillpresentsat UPS outlets.
If the externalbattery cordorpowercordneedstobe replaced, pleasecontact ourservicestation or
franchiserforreplacing toavoidfiredisastercaused byinsufficientcapacityof suchitems.Don't disposeof
battery orbatteriesgroup inafire, otherwise, itcan causeexplosion and harmtopeople.Don't open the
battery ordothe battery damage,forthe liquidspilled frombatteryisstronglypoisonousanddo harmfulto
body.
Pleaseavoidshort-circuit between battery anode and cathode; otherwise, thiswillcauseelectricshock or
fire.
Don't dismantlethe UPS cover,thereisdangerofelectricshock.
Don’t touchbatteries. Batteriesarenotisolated withthe input circuit,thereishigh voltage between the
battery terminalsand ground.
Don’t connect withthe electricequipment suchasblower, heater, drilling machine etc.Theymaydamage
the UPS.
Note: POCASAreservesthe righttomakechangestoproduct described inthismanual at anytimeand
without noticeforreasonsofimprovement.
Notice:
Therepresentshigh voltage inUPS.Ifthereisanyabnormalproblempresent, pleaseconsultthe
servicecenterand do notattempttorepairthe equipmentunderanycircumstances.The address
of servicecenterhasbeen detailed on the warrantycard.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

3
Contents
1.Briefintroduction-------------------------------------------------------------------------------------------------------------------4
1.1.Technologyintroduction-----------------------------------------------------------------------------------------------------4
1.2.Systemand modeldescription--------------------------------------------------------------------------------------------5
1.3.Description ofcommonlyused symbols---------------------------------------------------------------------------------5
1.4.Appearance--------------------------------------------------------------------------------------------------------------------6
1.5.Productspecification and performance---------------------------------------------------------------------------------8
2.Installation----------------------------------------------------------------------------------------------------------------------------8
2.1.Unpacking andinspection--------------------------------------------------------------------------------------------------9
2.2. Safetynotes--------------------------------------------------------------------------------------------------------------------9
2.3.The descriptionoffrontpanel and displaylamp---------------------------------------------------------------------10
2.4.UPSinput connection------------------------------------------------------------------------------------------------------11
2.5.UPSoutputconnection----------------------------------------------------------------------------------------------------12
2.6.Externalbattery connection----------------------------------------------------------------------------------------------13
3.Operation and operating mode------------------------------------------------------------------------------------------------14
3.1.Operation---------------------------------------------------------------------------------------------------------------------14
3.2.Operating mode-------------------------------------------------------------------------------------------------------------15
4.Notesforbatterydisposaland batteryreplacement---------------------------------------------------------------------20
5.Troubleshooting-------------------------------------------------------------------------------------------------------------------21
Appendix: EMCgrade standards------------------------------------------------------------------------------------------------23
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

4
1. Briefintroduction
1.1.Technologyintroduction
ThisUPSisasophisticated pieceof equipment with16 bitMicroprocessorand advanced software
programming technology,high frequency SPWMiscreated tocontrol the inverterof UPS.Thissimplifiesthe
controlcircuit,enhancesthe stabilityofUPS,alsoenablesthe UPS tohaveenhanced real-timeperformance
thatmakesUPS respond the varietyofexternalenvironmentrapidlyand insurethatthe controlcircuit is
compact and reliable.
Digital controltechnologytoavoidthe temperatureexcursion of hardwarespecification
Self-diagnosesbeforestartup helpUPStofind potential failuretoavoidanylosses
Doubleconversion on-line topology, whichmakesthe UPS apuresine wavemachine withconstant
frequency, constantvoltage,lownoiseand no interruption withmainspowerfluctuation,it protectthe user's
equipmentsideallyallthe time.
No transfertimewhen mainpowerfailormainpowerrestore, meetsthe requirementsof precision
instruments.
Standardbypass function
WhenUPS meetsafault,it cantransfertobypass seamlesslyand provide alarm.
Advanced voltage compensation technology, makesthe wide inputvoltage range, reducing the battery
usage, enhancing the adaptiveabilityagainst the bad mainspowervariation.
Advanced wide frequency inputtechnology
Wideinput frequency range of UPS givesUPS agood compatibilitywithgeneratorunderfield
circumstances.
The advanced PFCtechnologyon the input of UPS,improvesthe input powerfactorclosetounity, raises
the powerefficiency,removesthe harmonicnoisefromUPS toutility,lowersUPS operationalcosts, it's
reallyan environmental friendlyprotection powersupply.
Smart management function
Undermainspowerblackout, UPSwouldtransfertobattery mode tosupplypowertoloads, when battery
voltage islow, UPSwouldprotectitself and shutsdownautomatically.When mainpowerrestores, UPS
wouldbe turned on automaticallytosupplypowertoloads.
Coldstartfunction
Whenthereisno input,UPScan be turned on withbattery pack,tomeetthe user'semergency needs.The
coldstartfunction isquitestrong. UPS can becoldstarted on fullload situation.
Fault operation prevention function
Everybuttonhasdelayfunction,onlywhen you pressand holdthe button foracertaintime,required
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

5
operation can be activated.
Smart management function
Undermainspowerblackout, UPSwouldtransfertobattery mode tosupplypowertoloads, when battery
voltage islow, UPSwouldprotectitself and shutsdownautomatically.When mainpowerrestores, UPS
wouldbe turned on automatically.
Viainternalorexternal SNMPcard,UPScan go on internet, you can monitorand manage the UPS status
through allkindsof network managementsystem.
1.2. System andmodeldescription
Honline seriesisan uninterruptiblepowersupplyincorporating double-conversiontechnology. Itprovides
perfect protection specificallyforcomputerequipmentcommunication systemstocomputerized instruments.
Itstrue online double-conversion design eliminatesallmainspowerdisturbances.Arectifierconvertsthe
alternating currentfromthe utilitypowertodirectcurrent. Thisdirectcurrentchargesthe batteriesand
powersthe inverter.Onthe basisofthisDC voltage,the invertergeneratesapuresinusoidalACvoltage,
whichisconstantlypowering the loads.
Computersand peripheralsarethuspowered entirelybythe UPS.Intheeventofpowerfailure,the
maintenance-free batteriespowerthe inverter.
Thismanual isapplicabletothe following models:
1)H1KS, H2KS, H3KSarestandardmodelswithinbuiltbattery.
2)H1KL,H2KL,H3KLarelong backup timemodels,whichareabletoconnectwiththeexternal battery
bank.
1.3. Descriptionofcommonlyusedsymbols
The following symbolswillbe used inthismanualandmayappearduring thecourseofyourpractical
applications.Therefore,all usersshouldbe familiarwiththemand understand theirmeanings.
Notation and explanation
Notation Explanation
Alertyou topayspecialattention
Caution of high voltage
Turnon the UPS
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

6
Turnoffthe UPS
Idleorshut downthe UPS
Alternating current source(AC)
Directcurrent source(DC)
Protectiveground
Alarmsilence
Overload indication
Battery check
Recyclable
Do not disposewithordinarytrash
1.4.Appearance
Front displaypanel
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

7
H2/3KS rearpanel
EXT.BATTERY
COMPUTER
INTERFACE
INTELLIGENTSLOT
BREAKER
NETWORK/FAX/MODEM
SUGERPROTECTION OUT
IN OUTPUT
FAN
INPUT
OUT
IN
H1KLrearpanel
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

8
H2/3KLrearpanel
1.5. Productspecificationandperformance
1.5.1.Generalspecification(standardmodels)
Model H1KS(L) H2KS(L) H3KS(L)
Voltage 220VAC
Frequency 46Hz-54Hz/56Hz-64Hz
Input Amperage(maximum)
12A 20A 30A
Powerrating 1KVA/0.7KW 2KVA/1.4KW 3KVA/2.1KW
Voltage 220VAC(±2%)
Output Frequency 50/60Hz±0.2
Batteries
Numberand type 3*12V7AH/None 8*12V7AH/None 8*12V7AH/None
1.5.2. Dimensionsand weights
Model H1KS/H1KL H2KS/H2KL H3KS/H3KL
Dimensions(W*H*D)(mm) 145*400*220 192*460*340 192*460*340
Net weight 14/7 34/13.5 34/14
2. Installation
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

9
2.1. Unpacking andinspection
1).When unpacking the UPS,pleasepayattention tothe packing mode and theannexinwhichincludes
user-manual, warrantycard, input powercable, output wiring socket. Thereshouldalsohavean external
battery connection cableifthe model of yourequipmentisoflong backup type.
2). Inspect yourmachine tosee whetherit'sdamaged in the transportation.If damaged orsomeparts
missing, pleasedon't start up yourUPS.
3). Checkifthe equipmentisjustwhat you wanted topurchase. You canaffirmthrough inspecting the model
numberon backpanelof the equipment.
2.2. Safetynotes
1). Keep good aircirculation around UPS and farawayfromwater,flammablegasand corrosive.
2). Don't placeUPSon the slope and thereshouldkeep good aircirculation between in-vent on front panel
bottomand fan outventon back panel.
3). The environmenttemperaturearound UPSshouldkeep inarange of 0℃~40℃.
4).Therewillbe phenomena ofcondensing iftheequipmentisdismantled orinstalled underlowtemperature.
The equipmentcan't be installed unless itisfulldryatinternaland externalof the equipment,otherwise,
therewillbe dangerof electric.
5). The socketthat suppliespowertoUPS shouldbe placed nearthe UPS and easy.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

10
2.3.Thedescriptionoffrontpanel anddisplay lamp
Description of the front panel
LCD panelsection
●The firstline isthe numericsection, and isconsistedoftwosmallnumericsectionsand the related unit
section on the right side.Itisused todisplaythe numerical value ofthe certainitemon the second line.
●The second line isthe section ofthe itemswhichinclude input, battery,output,load and temperature,etc.
●The thirdline isthe figuresection whichisconsisted withtwoparts, thepartson the leftshowsthe
working statusofUPS, thepartson the right showsthe load capacity(on the top)and batterycapacity(on
the bottom)byschematicfigure.
LEDpanelsection
●PowerON/OFF: toturnon the UPS simplybypressing the “ON”button on the frontpanel
continuouslyfor1second.Press the “OFF”button on the frontpanelcontinuouslyfor1second to
turnoffthe UPS.
●BypassLED(orange LED): wheneverthe bypassLEDisturned on, itshowsthat the loading current
issupplied directlyfromthe utilitypower.
●UtilitypowerLED(green LED):wheneverthe utilitypowerLEDisturnedon,itshowsthatthe utility
powerisnormal.
●InvLED(green LED):wheneverthe INVLEDisturned on,itshowsthatthe loading currentis
supplied fromutilitypowerorbattery via the inverter.
●BatteryLED(orange LED):wheneverthebatteryLEDisturned on,itshowsthattheloadingcurrent
issupplied frombatteryviathe inverter.
●FaultLED(red LED):wheneverthe faultLEDisturned on,itshowsthattheUPSisinabnormal
condition.
●#2-#6 LEDs(the #2LEDisorange and the #3-#6 LEDsaregreen):theseLEDsindicatethe
percentage ofthe load capacityinutilitypowermode orbattery capacitylevelinbattery mode.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

11
Description of thebuttons
Buttons’function:
lON/OFF button
Press andholdforsometimetoturnon/off the UPS.
lFUNCTIONbutton
Press andholdforsometimeon utilitymode:UPSrunsaself-testfunction.
Press andholdforsometimeon batterymode:mutefunction.
lINQUIRINGbutton
Press forshorttime:indicatethe itemsofthesecond rowitemsectionorderly.Press and holdforsome
time:circularlyand orderlydisplaythe itemsfromINPUT,BATTERY,OUTPUT,LOAD&TEMPERATURE
every2seconds.
Whenyou press and holdthe button forsometimeagain,it will turntostaticoutput status.
2.4. UPSinputconnection
Whenconnectpowercable,pleaseusesuitablesocketwithover-currentprotection.The rating forH1KS(L)
shouldbe above6A, forH2KS(L)shouldbe above12A,forH3KS(L)shouldbe above16A.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

12
UPS input connection
2.5. UPSoutputconnection
1). Output of H1KS(L)usesocket only, pleasedirectlyplug the load cableintothe output socket.
2).OutputofH2KS(L)and H3KS(L)not onlyprovide socketbutalsoofferhigh-currency outputwiring socket,
whichmakeoutput wiring becomeeasy.
UPS model Output socket Wiring socket
H1KS(L) 3 None
H2/3KS(L) 4 Yes
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

13
UPS outputconnection
2.6. Externalbattery connection
1). Choosecorrect batteryvoltage according tothe model
The batteriescan't be moreorless connected, otherwiseUPS will work abnormal orbe damaged.Battery
voltage forH1KLis36VDC;forH2KLis96VDC;forH3KLis96VDC.
2). One end of externalbattery cableisconnected toUPS;the otherend isopen styletwocablesused to
connect tobattery pack.The process ofconnecting battery isveryimportant.Operatormust obeythe
instructions.
Long backup externalbattery connection
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

14
A.Firstconnect battery group inseriesand ensurecorrect batteryvoltage.
B.Extended battery cablemustbe connected tobatteryfirst(do notconnecttoUPSfirst; otherwisetherewill
be dangerof(electricshock). Red cableconnectwithbattery anode “+”and black cableconnectwith
cathode”–“.
C. Don't connectanyload toUPS,put through utilitytoUPS afterthe input wirehasbeen connected well.
D. Afterplug the battery extended cableintoUPS battery socket, the connection iscompleted,atthe same
timeUPS startstocharge batteries.
3. Operation andoperating mode
3.1.Operation
3.1.1.Operation on utilitymode
1). Onceutilityisplugged in,the internalchargerstartstocharge batteries, atthispointthe yellowLEDis
on and LCD statusfigureshowsblock LINE”and “BATTERY”and the outputvoltage iszero,whichmeans
UPS hasno output.
2). Press and holdthe ON/OFFbutton formorethan 2secondstoturnon the UPS,then it willturnon the
internal inverter.
3). Onceturned on,the UPSwillperformaself-testfunction,when the green LEDlightson, LCD status
figureshowsblock “LINE”and “INV”and “BATTERY”,thatmeansUPS isworking inutilitymode.
3.1.2. Startup UPS byDC when utilityisdisconnected
1).When utilityisdisconnected, press and holdthe ON/OFFbutton formorethan 2secondstocoldstart
the UPS.
2). The coldstart isthe sameoperation aswhen UPS isstarted withthe utilityin, and LCD statusfigure
showsblock “BATTERY”and “INV”,whichmeansUPS isworking inbattery mode.
3.1.3.Turnoff UPSinutilitymode
1). Press and holdthe ON/OFFbutton formorethan 2secondstoturnoff the UPS,then it willturnoff the
internal inverter.
2)When turning off the UPS,UPS willrun aself-testfunction,green LEDwillbe off and yellowLEDwillbe
on, LCD statusfigureshowsblock ”LINE”and “BATTERY”, whichmeansUPS hasno output butstillcharge
the battery.
3.1.4.Turnoff UPSinbatterymode
1). Press and holdthe ON/OFFbutton formorethan 2secondstoturnoff the UPS.
2).When turningoff the UPS,UPSwillrunaself-test function,UPShasnooutputoncethereisno display
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

15
on front panel.
3.1.5. UPSself-test/mutetest operation
1).When UPSison utilitymode, press andholdthe FUNCTIONbutton for1second,the buzzerwillsound
onceevery4seconds, the LEDlightslightaround at thesametimeasthe UPS runsself-testing, and itwill
lastfor10 seconds.
2).When UPS ison batterymode,the buzzerstopsbeeping if you press and holdthe FUNCTIONbutton
for1second, and it will restart tobeep if you press and holdthe ON/OFF button forone moresecond.
*Off–charging model
Whenutilityison and the UPSisnotswitched on, then the LCD statusfigurewill showblock “LINE”and
“BATTERY”, without output. The UPSwillcharge the battery inthismode.
Off-charging mode
3.2.Operatingmode
3.2.1. Utilitymode
Onutilitymode, theindication and displaysareasfollowing figures:
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

16
Utilitymode
Green LEDison, LCD statusfigureshowsblock "LINE"and "BATTERY"and "INV".
1).Ifthe INPUT lettersinthe itemsection (thesecond rowon LCD display) flashes,itindicatesthe line and
neutralareincorrect.
2). Ifload capacitygraph inthe graphicsection (thethirdrowon LCD display) flashes, yellowLEDison
and the buzzerbeepsoncehalf second, itremindsthat UPS carriesover100% load and you shouldremove
the unnecessary load untilthe displayed load isbelow100%.
3).Ifbattery capacitygraph inthe graphicsection (the thirdrowon LCD display) flashes,yellowLEDison,
itremindsthat UPSisdisconnected withbatteriesorbattery voltage islow, and you shouldfirstlycheck
whetherthe battery connection isok, ifyes, the batteriesmaybe fault and need tobereplaced.You can
pressthe FUNCTIONbutton for1second todo the manualself-test, formoredetailspleaserefertothe
troubleshooting table.
3.2.2. Batterymode
Onbatterymode,the indication and displaysareasfollowing figure:
Battery mode
Green LEDison, LCD statusfigureshowsblock “BATTERY”and “INV”
1). Onbatterymode,the buzzerwillbeep onceevery 4secondstoprovide an audiblealarm, press and
holdthe function button formorethan 1second,the buzzerwillstop beeping,press and holdthe FUNCTION
button forone moresecond, the buzzerwillbeep again.
2). If battery capacitygraph inthe graphicsection(the thirdrowon LCD display)flashes, yellowLEDison,
the buzzerbeepsonceevery second,it meansthe battery voltage isdischarged tominimumprotection
voltage,and remindsusersthat the batterycapacityisdiminished and shouldsavealldataand worksand
then switchoff the equipments.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

17
3). You can test UPS backup function bydisconnectingthe utility.
4). Ifthe INPUTlettersintheitemsection (the second rowon LCD display) flashes, it meansthe input
voltage orfrequency isbeyond the extension.
3.2.3.Faultmode
The frontpanelindication and displayisasfollowing:
Fault mode
Red LEDison.The digitalsection indicatesthe fault code. Formoredetailspleaserefertotheabnormal
processtable.
3.2.4. Backup timeforthe standardmodel
The backup timeofthe long backup timemodel isdependenton the externalbattery packcapacityand the
load levelaswell asotherfactors.
The backup timeofstandardmodel mayvary fromdifferentmodelsand load level,pleaserefertothe
following:
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

18
3.2.5. Communication port
Intelligent slot
Thisseriesisequipped withan intelligent slot forweb power(optionalaccessory) orotheroptionalcardto
achieveremotemanagement ofthe UPSthrough internet/intranet.Pleasecontact yourlocaldistributorfor
furtherinformation,
RS232 Interface
The following arethe descriptionsand pinassignmentof RS232 DB-9port:
Baud rate: 2400bps
Databit:8bit
Ending bit:1bit
Paritybit:none
DB-9pinassignment:
Pinnumber Function description I/O
3 Rx Input
2 Tx Output
5 Ground GND
Optional AS400 interface
Thisoptional AS400 cardprovidesdry contactclosuresignal “OPEN”or “CLOSE”.
RS232 interface
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

19
The following arethe pinassignment and the descriptionsofAS400 card:
PIN1:UPS failure(normallyopen, activeclose)
PIN2:Summary
PIN3:Ground
PIN4:Remoteshutdown
PIN5:Common
PIN6:Bypass active(relayclose)
PIN7:Battery low
PIN8:UPS On(relayclose)
PIN9:UtilityPowerfailure(normallyopen, activeclose)
3.2.6. Batterymaintenance
ThisseriesUPSonlyrequiresminimalmaintenance.The batteryused forstandardmodelsarevalue
regulated sealed lead-acidmaintenancefree battery.Thesemodelsrequireminimalrepairs.Theonly
requirementistocharge the UPS regularlyinordertomaximizethe expected lifeof the battery.When being
connected tothe utilitypower,whetherthe UPSisturned on ornot,the UPS keepscharging the batteries
and alsooffersthe protectivefunction ofovercharging and over-discharging.
lThe UPS shouldbe charged onceevery4to6monthsif it hasnot been used foralong tine.
lInthe regionsofhotclimates,thebatteryshouldbecharged and discharged every2months.The
standardcharging timeshouldbe atleast 12 hours.
lUndernormal conditions,the battery lifelasts3to5years.Incaseifthe battery isfound notingood
condition,earlierreplacementshouldbe made.Batteryreplacementshouldbe performed byqualified
personnel.
lReplacebatterieswiththe samenumberand sametypeofbatteries.
lDo notreplacethebatteryindividually.Allthe batteriesshouldbereplacedatthesametimefollowing
toe instructionsof the battery supplier.
Normally,the batteriesshouldbe charged and discharged onceevery4to6months.Charging should
beginafterthe UPSshutsdownautomaticallyinthe courseofdischarging,the standardcharging timeforthe
standardUPS shouldbe atleast 12 hours.
AS400 Interface
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

20
4. Notes forbattery disposal andbattery replacement
●The battery of standardunitisofvalveregulated, maintenancefree.Itcan attainexpectantlifeonlyby
keeping frequent charging. Regardless ofUPS on oroff when UPS connectstoutilitypower, the battery is
charged allthe timeand UPSoffersprotection forover-charge and over-discharge.
●Normallythe battery lifeisthree tofiveyearsand the battery must bereplaced ahead oftimeoncethere
presentsanyabnormal status. The batteryreplacement must onlybe performed byqualified personnel.
●It isinadvisabletoreplaceasinglebattery.Operatorshouldobeythe instruction of battery distributor
whenreplacing allbatteries.
●The batteriesshouldbe charged and discharged onceeveryfourtosixmonths. AfterUPS discharged to
off,the batteriesshouldbe recharged. The charge timeofstandardunit must be morethan 12 hours.
●The battery must be charged and discharged onceeverytwomonthsinhigh-temperaturearea.The
charge timeofstandardunitsmust be morethan twelvehours.
1.Ifitisnecessary toreplaceanyconnection cables,pleasepurchasethe originalmaterialsfromthe
authorized distributorsorservicecenters, soastoavoid overheat orspark resulting infiredue toinsufficient
capacity.
2. Do not disposeofbatteriesorbatterypacksinafire,theymayexplode.
3.Do notopen ormutilatebatteries,released electrolyteishighlypoisonousand harmful tothe skinand
eyes.
4. Do not short the positiveand negativeof the battery electrode, otherwise, itmayresultinelectricshock
orfire.
5.Makesurethatthereisno voltage beforetouching the batteries. The batterycircuitisnotisolatedfrom
the inputpotential circuit. Theremaybe hazardousvoltage betweenthe battery terminalsand ground.
6. Even though the input breakerisdisconnected, the componentsinside the UPS arestillconnected with
the batteries,and therearepotentialhazardousvoltages.Therefore,beforeanymaintenanceand repairs
work iscarried out, switchoffthe breakerofthe battery pack ordisconnectthe jumperwireofconnecting
betweenthe batteries.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
Other manuals for H1KS
1
This manual suits for next models
5
Table of contents
Other Pocasa UPS manuals
Popular UPS manuals by other brands

PowerWalker
PowerWalker VFI 1000RT LCD manual

Atronix
Atronix Extended Battery Pack Pro user manual

Tripp Lite
Tripp Lite OmniSmart OMNISMART1400 Specification sheet

Tripp Lite
Tripp Lite SmartOnline SU16000RT4U owner's manual

Tripp Lite
Tripp Lite SmartPro SMX5000XLRT3U specification

Tripp Lite
Tripp Lite Digital UPS Systems 200703079 owner's manual