1
Thankyou forpurchasing ourUPS, itissafeand liable,needsfewmaintenance.
Thismanualincludesinstructionsofsafetyinstallationand operation,theyhelpyourUPStohavethe
longest servicelife.Thismanual alsoaccountsthe UPSwork principleand relativefunctions.
Pleaseobeythe instructionsand notesstated inthismanual.Keep thismanualinasafeplace,consult
itbeforeoperation.
Safetyrules
Evenif notconnected tomainpower, high voltage maystillpresentsat UPS outlets.
If the externalbattery cordorpowercordneedstobe replaced, pleasecontact ourservicestation or
franchiserforreplacing toavoidfiredisastercaused byinsufficientcapacityof suchitems. Don't disposeof
battery orbatteriesgroup inafire, otherwise, itcan causeexplosion and harmtopeople.Don't open the
battery ordothe battery damage,forthe liquidspilled frombatteryisstronglypoisonousand do harmful to
body.
Pleaseavoidshort-circuit between battery anode and cathode; otherwise, thiswillcauseelectricshock or
fire.
Don't dismantlethe UPS cover,thereisdangerofelectricshock.
Don’t touchbatteries. Batteriesarenotisolated withthe input circuit,thereishigh voltage between the
battery terminalsand ground.
Don’t connect withthe electricequipment suchasblower, heater, drillingmachineetc.Theymaydamage
the UPS.
Note: POCASAreservesthe righttomakechangestoproduct described inthismanual at anytimeand
without noticeforreasonsofimprovement.
Notice:
Therepresentshigh voltage inUPS.Ifthereisanyabnormalproblempresent, pleaseconsult
the servicecenterand do notattempttorepairtheequipmentunderanycircumstances.The
addressofservicecenterhasbeen detailed on the warrantycard.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

2
Contents
1.Briefintroduction-------------------------------------------------------------------------------------------------------------------3
1.1.Technologyintroduction----------------------------------------------------------------------------------------------------3
1.2.Systemand model description--------------------------------------------------------------------------------------------4
1.3.Descriptionof commonlyused symbols--------------------------------------------------------------------------------4
1.4.Appearance--------------------------------------------------------------------------------------------------------------------5
1.5.Productspecification and performance---------------------------------------------------------------------------------6
2.Installation---------------------------------------------------------------------------------------------------------------------------8
2.1.Unpacking and inspection--------------------------------------------------------------------------------------------------8
2.2. Safetynotes--------------------------------------------------------------------------------------------------------------------9
2.3.The description offrontpaneland displaylamp--------------------------------------------------------------------10
2.4. Inputand output powerchordsand protectiveearthground installation--------------------------------------11
2.5.Operating procedureforconnectingthelong backuptimemodelUPSwiththe external
battery----------------------------------------------------------------------------------------------------------------------------------12
2.6.Paralleloperation-----------------------------------------------------------------------------------------------------------13
3.Operation and operating mode-----------------------------------------------------------------------------------------------14
3.1.Operation---------------------------------------------------------------------------------------------------------------------14
3.2.Operating mode-------------------------------------------------------------------------------------------------------------15
4.Notesforbatterydisposaland batteryreplacement---------------------------------------------------------------------19
5.Troublesshooting----------------------------------------------------------------------------------------------------------------20
Appendix:The corresponding formofthe LEDdisplay--------------------------------------------------------------------22
Appendix2:EMCgrade standards----------------------------------------------------------------------------------------------24
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

3
1. Briefintroduction
1.1.Technologyintroduction
ThisUPSisasophisticated pieceof equipment with16 bitMicroprocessorand advanced software
programming technology, high frequency SPWMiscreated tocontrolthe inverterof UPS.Thissimplifies
the control circuit, enhancesthe stabilityofUPS,alsoenablesthe UPS tohaveenhanced real-time
performancethat makesUPS respond the varietyof externalenvironmentrapidlyand insurethat thecontrol
circuitiscompact and reliable.
Digitalcontroltechnologytoavoidthe temperatureexcursion of hardwarespecification
Self-diagnosesbeforestartup helpUPStofind potential failuretoavoidanylosses
Doubleconversion on-line topology, whichmakesthe UPS apuresine wavemachine withconstant
frequency, constantvoltage,lownoiseand no interruption withmainspowerfluctuation,it protectthe user's
equipmentsideallyallthe time.
No transfertimewhen mainpowerfail ormainpowerrestore, meetsthe requirementsof precision
instruments.
Standardbypass function
WhenUPS meetsafault,it cantransfertobypass seamlesslyand provide alarm.
Advanced voltage compensation technology,makesthe wide inputvoltage range,reducing thebattery
usage, enhancing the adaptiveabilityagainst thebad mainspowervariation.
Advanced wide frequency inputtechnology
Wideinput frequency range of UPS givesUPS agood compatibilitywithgeneratorunderfield
circumstances.
The advanced PFCtechnologyon the input of UPS,improvesthe input powerfactorclosetounity, raises
the powerefficiency,removesthe harmonicnoisefromUPS toutility,lowersUPS operational costs, it's
reallyan environmental friendlyprotection powersupply.
Smart management function
Undermainspowerblackout, UPSwouldtransfertobattery mode tosupplypowertoloads, when battery
voltage islow, UPSwouldprotectitself and shutsdownautomatically.When mainpowerrestores, UPS
wouldbe turned on automaticallytosupplypowertoloads.
Coldstartfunction
Whenthereisno input, UPScan be turned on withbattery pack,tomeetthe user'semergency needs.
The coldstartfunctionisquitestrong. UPScan be coldstarted on fullload situation.
Fault operation prevention function
Everybuttonhasdelayfunction,onlywhen you pressand holdthe button foracertaintime,required
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

4
operation can be activated.
Smart management function
Undermainspowerblackout, UPSwouldtransfertobattery mode tosupplypowertoloads, when battery
voltage islow, UPSwouldprotectitself and shutsdownautomatically.When mainpowerrestores, UPS
wouldbe turned on automatically.
ViainternalorexternalSNMPcard,UPScan go on internet, you can monitorand manage theUPS status
through allkindsof network managementsystem.
1.2. System andmodeldescription
Honline seriesisan uninterruptiblepowersupplyincorporating double-conversion technology.It
providesperfectprotection specificallyforcomputerequipmentcommunicationsystemstocomputerized
instruments.
Itstrue online double-conversion design eliminatesallmainspowerdisturbances.Arectifierconvertsthe
alternating currentfromthe utilitypowertodirectcurrent. Thisdirectcurrentchargesthe batteriesand
powersthe inverter.Onthe basisofthisDC voltage,the invertergeneratesapuresinusoidalACvoltage,
whichisconstantlypowering the loads.
Computersand peripheralsarethuspowered entirelybythe UPS.Intheeventofpowerfailure,the
maintenance-free batteriespowerthe inverter.
Thismanual isapplicabletothe following models:
1)The H6KS ismodel withinbuiltbattery, hereinaftercalled6KS;
2)The H6KLisalong backup timemodel,whichisabletoconnectwiththe external batterybank,
hereinafter-called 6KL;
3)The H10KS isastandardmodel withinbuiltbattery, hereinafter-called 10KS;
4)The H10KLaisalong backup timemodel,whichisabletoconnectwiththe externalbattery bank,
hereinafter-called 10KL;
5)The H10KL3/1isathree-phaseinputand single-phaseoutput long backup timemodel,whichisableto
connect withthe external batterybank. Hereinaftercalled three-phase10KL.
6)The H15KL3/1isathree-phaseinputand single-phaseoutput long backup timemodel,whichisableto
connect withthe external batterybank. Hereinaftercalled three-phase15KL.
7)The H20KL3/1isathree-phaseinputand single-phaseoutput long backup timemodel,whichisableto
connect withthe external batterybank. Hereinaftercalled three-phase20KL.
1.3. Descriptionofcommonlyusedsymbols
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

5
The following symbolswillbe used inthismanualandmayappearduring the courseofyourpractical
applications.Therefore,all usersshouldbe familiarwiththemand understand theirmeanings.
Notation and Explanation
Notation Explanation
Alertyou topayspecialattention
Caution of high voltage
︱Turnon the UPS
Turnoffthe UPS
Idleorshut downthe UPS
Alternating current source(AC)
Directcurrent source(DC)
Protectiveground
Alarmsilence
Overload indication
Battery check
Recyclable
Do not disposewithordinarytrash
1.4.Appearance
Front displaypanel
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

6
Backviewof 6KLBackviewof 10KL/three phase10KL
Backviewof three phase15KL/three phase20KL
1.5. Productspecificationandperformance
1.5.1.Generalspecification (standardmodels)
Model H6KS H6KL H10KS H10KL
Powerrating 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 10KVA/7KW
Frequency(Hz) 50/60 50/60 50/60 50/60
Voltage (176-276)VAC (176-276)VAC (176-276)VAC (176-276)VAC
Input Current 31AMax 31AMax 50AMax 50AMax
Voltage 192/240VDC 192/240VDC 192/240VDC 192/240VDC
Battery Current 24AMax 24AMax 40AMax 40AMax
Output Voltage 220VAC/230VAC
220VAC/230VAC 220VAC/230VAC 220VAC/230VAC
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

7
Dimension(W×D×H)mm 260×570×717 260×570×717 260×570×717 260×570×717
Net weight(Kg) 75 35 80 38
Model Three-phase10KL Three-phase15KL Three-phase20KL
Powerrating 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Frequency(Hz) 50/60 50/60 50/60
Voltage (304-478)VAC (304-478)VAC (304-478)VACInput Current 50AMax 75AMax 100AMax
Voltage 192/240VDC 192/240VDC 192/240VDCBattery Current 40AMax 60AMax 80AMax
Output Voltage 220VAC/230VAC 220VAC/230VAC 220VAC/230VAC
Dimension(W×D×H)mm 260×570×717 260×570×717 260×570×717
Net weight(Kg) 39 52 52
1.5.2. Dimension &weight forUPSwithgalvanicisolation
Model H6KS H6KL H10KS H10KL
Powerrating 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 10KVA/7KW
Dimension(W×D×H)mm 700×430x845 700×430x845 700×430x845 700×430x845
Gross weight (Kg) 85 44 95 46
Model Three-phase10KL Three-phase15KL Three-phase20KL
Powerrating 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Dimension(W×D×H)mm 700×430x845 700×430x845 700×430x845
Gross weight(Kg) 48 60 60
1.5.3. Electrical performance
Input Frequency
Model Voltage 50Hz 60Hz Powerfactor
6K(S)/10K(S) Single-phase ±4Hz >0.98(full load)
Three-phase
10KS/15KS/20KS Three-phase ±4Hz >0.95(full load)
Output
Voltage
regulation Power
factor Frequency
tolerance Distortion
Overload capacity Current crest
rating
±1% 0.7lag
Synchronized
±4HzinLine
mode (ACmode)
±0.1% ofnormal
frequency in
battery mode
THD<2%
fullload
(linear
load)
105%-130% load transfersto
bypass mode after10 minutes
>130% load transfersto
bypass mode after1second
and shutdownthe output after
1minute
3:1maximum
1.5.4.Operating environment
Temperature Humidity Altitude Storage temperature
0℃-40℃20%-90% <1000M -15℃-40℃
Note:ifthe UPS isinstalled orused inaplacewherethe altitude isabovethan 1000m,the outputpower
must be derated inuse, pleaserefertothe following:
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

8
Altitude(M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating power 100%
95% 91% 86% 82% 78% 74% 70% 67%
2. Installation
2.1. Unpackingandinspection
1). Unpack the packaging and checkthe package contents.The shipping package contains:
lAUPS
lAusermanual
lAcommunication cable
lAbatterycable(for “L”modelsonly)
2).Inspectthe appearanceoftheUPStosee ifthereisanydamageduring transportation.Donotturnon
the unitand notifythe carrierand dealerimmediatelyifthereisanydamage orlacking of someparts.
3). Check if the equipmentisjust what you wanted topurchase. You can affirmthrough inspectingthe
modelnumberon backpanelof the equipment.
2.2. Safetynotes
1). Keep good aircirculation around UPS and farawayfromwater,flammablegasand corrosive.
2). Don't placeUPSon theslope and thereshouldkeep good aircirculation between in-vent onfrontpanel
bottomand fanoutventon back panel.
3). The environmenttemperaturearound UPSshouldkeep inarange of 0℃~40℃.
4). Therewillbe phenomena ofcondensing ifthe equipment isdismantled orinstalled underlow
temperature.The equipmentcan'tbe installed unless itisfull dry at internal and external ofthe equipment,
otherwise, therewillbe dangerofelectric.
5). The socketthat suppliespowertoUPS shouldbe placed nearthe UPS and easy.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

9
2.3.Thedescriptionoffrontpanel anddisplay lamp
●PowerON/OFF: toturnon the UPS simplybypressing the “ON”button on the frontpanel
continuouslyfor1second.Press the “OFF”button on the frontpanelcontinuouslyfor1second to
turnoffthe UPS.
●BypassLED(orange LED): wheneverthe bypassLEDisturned on, itshowsthat the loading current
issupplied directlyfromthe utilitypower.
●UtilitypowerLED(green LED):wheneverthe utilitypowerLEDisturnedon,itshowsthatthe utility
powerisnormal.
●InvLED(green LED):wheneverthe INVLEDisturned on,itshowsthatthe loading currentis
supplied fromutilitypowerorbattery viathe inverter.
●BatteryLED(orange LED):wheneverthebatteryLEDisturned on,itshowsthattheloadingcurrent
issupplied frombatteryvia the inverter.
●FaultLED(red LED):wheneverthe faultLEDisturned on,itshowsthattheUPSisinabnormal
condition.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

10
●#2-#6 LEDs(the #2LEDisorange and the #3-#6 LEDsaregreen):theseLEDsindicatethe
percentage ofthe load capacityinutilitypowermode orbattery capacitylevelinbatterymode.
2.4. Inputandoutputpower chordsandprotective earth groundinstallation
2.4.1. Notesforinstallation
1)The UPSmustbe installed inalocation withgood ventilation,farawayfromwater,inflammablegas
and corrosiveagents.
2)Ensurethe airventson the frontand rearof the UPSarenotblocked.Allowatleast0.5Mof spaceon
eachside.
3)Condensation towaterdropsmayoccurif theUPSisunpacked inaverylowtemperatureenvironment.
Inthiscaseitisnecessary towaituntilthe UPSisfullydried inside outbeforeproceeding installation and
use. Otherwisetherearehazardsofelectricshock.
2.4.2.Installation
Installation and wiring mustbe performed inaccordancewiththe localelectriccode and the following
instructionsbyprofessionalpersonnel.
Forsafety, pleasecut offthe mainspowerswitchbeforeinstallation.The battery breakeralsoneedstobe
cut off ifit isalong backup timemodel(“L”model).
1)Open the terminalblockcoverlocated on the rearpanelofthe UPS,pleaserefertothe appearance
diagram.
2)ForH6KS(L)UPS,itisrecommended toselectthe UL1015 10AWG(6mm2)wireorotherinsulatedwire
whichcomplieswithAWGstandardforthe UPSinput and output wirings.
The protectiveearthground wirereferstothe wireconnection between toe equipmentwhichconsumes
electricequipment and the ground wire. The wirediameterofprotectiveearthground wireshouldbe atleast
asabovementioned foreachmodeland green wireofgreen wirewithyellowribbon wireisused.
1)Afterhaving completed the installation, makesurethewiring iscorrect.
2)Pleaseinstallthe leakcurrentprotectivebreakeratthe outputpowerdistribution panelofthe UPS if
necessary.
3)Toconnectthe load withthe UPS,pleaseturnoffallthe loadsfirst, then performthe connection and
finallyturnon the loadsone byone.
4)No matterthe UPS isconnected tothe utilitypowerornot, the outputof the UPS mayhaveelectricity,
the partsinside the unitmaystill havehazardousvoltage afterturning offtheUPS.Tomakethe UPShave
no output, poweroff the UPS,and then disconnect the utilitypowersupply.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

11
5)Suggestcharging the batteriesfor8hoursbeforeuse.Afterconnection,turnthe inputbreakerinthe
“ON”position,the UPSwillcharge the batteriesautomatically.You can alsousethe UPS immediately
without charging the batteriesfirst, butthe backup timemaybe less than the standardvalue.
6)Ifitisnecessary toconnectthe inductanceload suchasamonitororalaserprintertothe UPS,the
start-up powershouldbe used forcalculating the capacityoftheUPS,asitsstart-up powerconsumption is
too bigwhen it isstarted.
Input and outputterminal blockwiring diagramof H6KS(L)/H10KS(L)
Importantnotes:if the UPSisused insinglemode,JP1and JP2mustbe connected by10AWG(6mm2);if
the UPS isused inparallelmode,the jumperbetween JP1and JP2must be removed.
Input and outputterminal blockwiring diagramof three-phase10KL
Importantnotes:if the UPSisused insinglemode,JP1and JP2mustbe connected by10AWG(6mm2);if
the UPS isused inparallelmode,the Jumperbetween JP1and JP2must be removed.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

12
Input and outputterminal blockwiring diagramof three-phase15KS/20KS
Importantnotes:if the UPSisused insinglemode,JP1and JP2mustbe connected by6AWG(25mm2);if
the UPS isused inparallelmode,the Jumperbetween JP1and JP2must be removed.
2.5.Operatingprocedure forconnectingthelongbackup time modelUPS withtheexternalbattery
1).The nominalDC voltage of externalbattery pack is240VDC.Eachbattery pack consistsof 20 piecesof
12Vmaintenancefree batteriesinseries.Toachievelongerbackup time,itispossibletoconnect
multi-battery packs, butthe principleof “sameVoltage,sametype”shouldbe strictlyfollowed.
2).The connectorofthe externalbattery cableisused toplug intothe externalbatterysocket of the UPS
The otherend of the externalbattery cableismade ofthree open wireswithring terminalstoconnectwith
the externalbatterypack(s).The procedureofinstalling battery bankshouldbecompliedwithstrictly.
Otherwiseyou mayencounterthehazardousofelectricshock.
A.ADC breakermust be connected between the batterypack and the UPS.The capacityof breakermust
be not less than the dataspecified inthe general specification.
B. Set the batterypack breakerin “OFF”position and connect the 20 piecesof batteriesinseries.
C.You mustconnectthe externalbattery cabletothebattery first, ifyou connectthe cabletothe UPS
first,you mayencounterthe hazardousofelectricshock. The positivepoleofthe batteryisconnected tothe
H10KL/three-phaseH10KLinparallelwithblue and brownwires;the negativepoleofthe battery is
connected tothe H10KL/three-phaseH10KLinparallelwithblackand whitewires;the green and yellow
ribbon wireisconnected tothe ground of the batterycabinet. Forthree-phase15KL/20KL, the connection of
batterywireisthesameasthatofinputandoutputwire,and agreenorgreenand yellowribbonwire
UL1015 6AWG(25mm2)mustbe connectedbetweentheinputprotectiveearthterminal andthebattery
cabinet.
3).Tocompletethe connection byplugging the connectorofthe externalbatterycableintothe external
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

13
battery socketofthe UPS.Do notattempttoconnectanyloadstothe UPSnow.Youshouldconnectthe
inputpowerwiretotherightposition first,and then setthe breakerofthe battery pack inthe ONposition.
Afterthat set the input breakerinthe ONposition,The UPS beginstocharge the batterypacksat the time.
The external batterycablediagramforH6KL/H10KL(thecablemayvaryfromdifferent “L”models)
2.6. Paralleloperation
2.6.1. Briefintroduction of the redundancy
N+Xiscurrentlythe mostreliablepowersupplystructure.Nrepresentsthe minimumUPSnumberthat
the totalload needs;Xrepresentsthe redundantUPSnumberthefaultUPSnumberthatthe systemcan
handlesimultaneously.The biggerthe Xis,the higherreliabilityofthe powersystemis.Foroccasions
wherereliabilityishighlydepended on, N+Xisthe optimalmode.
Aslong asthe UPSisequipped withparallelcables,upto3UPS canbe connected inparallel torealize
output powersharing and powerredundancy.
2.6.2. Parallel installation
1)Usersneed toastandard25-pincommunication cable,whichshouldhave25cores,corresponding
stitchesand shield,asthe UPSparallel cable.The lengthofthe parallelcableisappropriatetoless
than 3M.
2)Strictlyfollowthe stand-alone wiring requirement toperform the Input wiring ofeachUPS.
3)Connect the output wiresofeachUPS toan outputbreakerpanel.
4)DisconnecttheJumperon JP1andJP2oftheterminalblockfirst,andconnecteachoutputbreaker
toamainoutputbreakerand then tothe load.
※The requirement of theoutput wiring isasfollows:
lWhenthe distancebetween the UPSsinparalleland the breakerpanelisless than 20 meters,
the differencebetween the wiresofinput &output ofthe UPSsisrequired tobe less than 20%.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

14
lWhen the distancebetween the UPSsinparallelandthe breakerpanelisgreaterthan 20
meters, the differencebetween the wiresofinput&output ofthe UPSisrequired tobe less than
10%.
2.6.3.Operation and maintenance
1)Toperformthe generaloperation, followthe stand-alone operating requirement;
2)Startup:the unitstransfertoINVmode simultaneouslyastheystartup sequentiallyinutilitypower
mode:
Shutdown: the unitsshut downsequentially
inINVmode. When the last one completes
the shutdownaction, eachunit willshut down
the invertersimultaneouslyand transferto
bypass mode.
Parallel installation diagram
It iseasytooperatethe equipment,withno previoustraining.You justneed toread through thismanual
and operateaccording tothe instructionsinit. The meaning ofthe LEDindicators,pleaserefertothe
appendix1 “Displaypanel”.
3. Operation andoperating mode
3.1.Operation
3.1.1.Turnon the UPSwithutilitypowersupplied (inlinemode/ACmode)
Pleasefirstlyuseofinternal batterymodels.
1)Whenyou operatefirsttime,pleaseopen the battery breakercoverplateand turnonthebattery
breaker.Then closethe batterybreakercoverplate.
2)Afteryou makesurethatthe powersupplyconnectioniscorrect,setthe inputbreakerinthe “ON”
position first.Atthistimethe fan rotatesand the UPS suppliespowertothe load viathe bypass.The UPS
operatesinbypassmode.
3)Topoweron the UPS bysimplypressing the “ON”button continuouslyformorethan 1second.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

15
4)Whenbeingpowered on,the UPSwillperformself-diagnosis,withtheload/batterylevelLEDsturned
on and then offone afteranotherinascending order.Afewsecondslater,the INVLEDisturned on,the
UPS isalreadyrunninginutilitypowermode. Iftheutilitypowerisabnormal,theUPSwill operateinbattery
mode withoutoutputinterruption of theUPS.
3.1.2.Turnon the UPSwithno utilitypowersupplied (inbattery mode)
1)Press the “ON”button continuouslyformorethan 1second topoweron the UPS Forlong back up time
model(“S”model),pleasemakesurethatthe batterybreakerisin “ON”position.
2)During the courseofstarting up,the UPS hasthesameaction asifitisconnected toutilitypower
exceptthatthe utilitypowerLEDisnot turned on and the battery LEDisturned on instead.
3.1.3.Turnoffthe UPS withutilitypowersupplied (inlinemode/ACmode)
1)Press the “OFF”button continuouslyformorethan 1secondtoturnoffthe inverterofthe UPS
immediately.
2)Whenbeingpowered off,the UPSwill performself-diagnosis,the load/batterylevelLEDswill be
turned on and then offone afteranotherinascending order, then theINVLEDwill be turned offandbypass
LEDwillbe turned on.The UPSisworking inbypass mode.
3)Upon completionoftheabovetoturnitoff,outputofelectriccurrentof the UPS isstillpresent.Inorder
tocutoffthe outputfromthe UPS,simplycutoffthe utilitypowersupplyand the UPS willperform
self-diagnosis,finallynotanydisplayisshownon the displaypaneland no voltage outputisavailablefrom
the UPS output.
3.1.4.Turnoffthe UPS withon utilitypowersupplied (inbattery mode)
1)Press the “OFF”button continuouslyformorethan 1second topoweroff the UPS.
2)Whenbeingpowered off,the UPSwill performself-diagnosis,the load/batterylevelLEDswill be
turned on and then off one afteranotherinascending order.Finallynotanydisplayisshownonthe display
paneland on voltage isavailableformthe UPSoutput.
3.1.5. UPSself-test/mutetest operation
1).When UPS ison utilitymode,press and holdthe FUNCTIONbutton for1second, the buzzerwill
sound onceevery4seconds, the LEDlightslight aroundat the sametimeasthe UPS runsself-testing, and
itwilllastfor10 seconds.
2).When UPS ison batterymode,the buzzerstopsbeeping if you press and holdthe FUNCTIONbutton
for1second, and it willrestart tobeep if you press and holdthe ONbutton forone moresecond.
Suggestions:pleaseturnoffthe connected loadsbeforeturning onthe UPSand turnon the loadsone by
one afterthe UPSisworking inINVmode.Turnoff allof the connected loadsbeforeturning off the UPS.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

16
3.2.Operatingmode
3.2.1. Utilitymode
The displaypanelinutilitypowermode isshowninthefollowing diagram,the utilitypowerLEDand the
INVLEDareturned on,Theload levelLEDswill be turned oninaccordancewiththeloadcapacity
connected.
1)Ifthe batteryLEDisturned on and the utilitypowerLEDflashes,itindicatesthevoltageor
frequency ofthe utilitypowerhasexceeded the normal range, the UPSoperatesinbatterymode.
Fig3-1:Theutilitypowermode
2)Ifoutput overloaded, the load levelLEDswillbe turned on and alarm willkeep twiceeverysecond.
You shouldget ridofsomeunnecessary loadsone byone todecreasethe loadsconnected tothe
UPS less than 90% ofitsnominalpowercapacity.
Note: Pleasefollowthe following stepstoconnect the generator:
lActivatethegeneratorandwaituntil theoperation isstablebeforesupplyingpowerof the generatorto
the UPS (be surethatthe UPS isinidlemode).Then turnon the UPS according tothe start-up
procedure.Afterthe UPSisturned on, then the loadscan be connected totheUPS one byone.
lThe powercapacityofthe ACgeneratorshouldbe atleast twiceoftheUPS capacity.
3.2.2. Batterymode
The displaypanelinbattery mode isshowninthe following diagramFig3-2.The battery LEDand the
INVLEDareturned on.The displayed numberofthebattery levelLEDswill be turned on inaccordance
withthe battery capacity.Notethatthe load levelLEDsinutilitypowermode willindicatethe levelofthe
battery capacityinbattery modeinstead.
1)When the UPS isrunning inbattery mode,the buzzerbeepsonceevery 4again,the buzzerwillstop
beeping (insilencemode).Press the “ON”button onceagainformorethan 1secondtoresumethe alarm
function.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

17
Fig3-2: Batterymode diagram
2)When the batterycapacitydecreases,the numberofthe battery capacityLEDsturned on willbe
reduced.Ifthe battery voltage descendstothe alarmlevel,the buzzerwillbeep onceeverysecond to
remind the usersofinsufficientbatterycapacityand the UPS issoon going toshutdownautomatically.
Then the load operation shouldbe carried outpromptlyand the loadsshouldbe eliminated one byone.
3.2.3. Bypassmode
The displaypanelinbypassmode isshowninthe following diagramFig3-3.The utilitypowerLEDand
the bypassLEDarelit.The displayed numberofthe load LEDswill be turned on inaccordancewiththe
load capacityconnected.The UPSwillbeep onceevery2minutesinbypass mode.
lThe utilitypowerLEDflashes.It showsthatthe voltage orfrequency ofthe utilitypowerhas
exceeded the normalrange ofthe UPS.
Fig3-3: UPSbypass mode diagram
lOtherindicationson the displaypanelarethe sameinutilitymode.
lThe UPS doesnothavethe backup function when itisinbypassmode.The powerused bythe
load issupplied fromthe utilitypowerviainternalfilter.
3.2.4.Faultmode
Incasethe fault LEDisturned on whenthe UPS isinuse, it showsthat the UPS isoperating inabnormal
mode.Pleaserefertothe troubleshooting insection 6forderail.
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

18
3.2.5. Backup timeforthe standardmodel
The backup timeofthe long backup timemodel isdependenton the external batterypack capacityand
the load levelaswell asotherfactors.
The backup timeofstandardmodel mayvary fromdifferentmodelsand load level,pleaserefertothe
following:
Load capacityLoad capacity
H6KS(L)backuptimecurveH10KS(L)backup timecurve
3.2.6. Communication port
Intelligent slot
Thisseriesisequipped withan intelligent slot forweb power(optionalaccessory) orotheroptionalcardto
achieveremotemanagementofthe UPS through internet/intranet. Pleasecontactyourlocal distributorfor
furtherinformation,
RS232 Interface
The following arethe descriptionsand pinassignmentof RS232 DB-9port:
Baud rate: 2400bps
Databit:8bit
Ending bit:1bit
Paritybit:none
PDF 件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn

19
DB-9pinassignment:
Pinnumber Function description I/O
3 Rx Input
2 Tx Output
5 Gnd Ground
Optional AS400 interface
Thisoptional AS400 cardprovidesdry contactclosuresignal “OPEN”or “CLOSE”.
Following arethe pinassignment and the descriptionsofAS400 card:
PIN1:UPS failure(normallyopen, activeclose)
PIN2:Summary
PIN3:Ground
PIN4:Remoteshutdown
PIN5:Common
PIN6:Bypass active(relayclose)
PIN7:Battery low
PIN8:UPS on(relayclose)
PIN9:UtilityPowerfailure(normallyopen, activeclose)
3.2.7. Batterymaintenance
ThisseriesUPSonlyrequiresminimalmaintenance.The batteryused forstandardmodelsarevalue
regulated sealed lead-acidmaintenancefree battery.Thesemodelsrequireminimalrepairs.Theonly
requirementistocharge the UPS regularlyinordertomaximizethe expected lifeof the battery. When being
connected tothe utilitypower,whetherthe UPSisturned on ornot,the UPS keepscharging thebatteries
and alsooffersthe protectivefunction ofovercharging and over-discharging.
lThe UPS shouldbe charged onceevery4to6monthsifit hasnot been used foralong tine.
lInthe regionsofhotclimates,thebatteryshouldbecharged and discharged every2months.The
standardcharging timeshouldbe at least 12 hours.
lUndernormal conditions,the battery lifelasts3to5years.Incaseifthe battery isfound notingood
condition,earlierreplacementshouldbe made.Batteryreplacementshouldbe performed byqualified
personnel.
lReplacebatterieswiththe samenumberand sametypeofbatteries.
lDo notreplacethebatteryindividually.Allthe batteriesshouldbe replacedatthesametimefollowing
toe instructionsofthe batterysupplier.
Normally,the batteriesshouldbe charged and discharged onceevery4to6months.Charging should
beginafterthe UPSshutsdown automaticallyinthe courseofdischarging,the standardcharging timefor
the standardUPS shouldbe at least 12 hours.
RS232 interface
AS400 Interface