Polon-Alfa G-40 Manual

G‐40DETECTORBASE
PG‐40BASEINDUSTRIALFOOTING
InstallationandMaintenanceManual
IK‐E287‐001GB
IIIGEdition

TheG‐40BaseandPG‐40BaseIndustrialFootingcoveredbythepresentoperationmanualcomplywiththe
requirementsoftheAT‐0112‐0298/2011TechnicalApprovalissuedbytheScientificandResearchCentre
forFireProtection(CNBOP).
TheG‐40BaseandPG‐40BaseIndustrialFootinghavebeenapprovedwiththeCertificateofConformity
No.2789/2011confirmingtheircompliancewiththeTechnicalApprovalissuedbyCNBOP.
TheCertificatemaybedownloadedfromthemanufacturer’swww.polon‐alfa.plwebsite.
ThenationaldeclarationofcomplianceNo.2PI/E287/2011dated15.12.2011isavailableonrequestfrom
themanufacturer.
Readthemanualcarefullybeforeassemblingandoperationofthebaseandthebaseindustrialfooting.
Anynonconformitywiththeinstructionscontainedinthemanualmaybeharmfulormaycauseviolationof
thelawinforce
POLON‐ALFAbearsnoresponsibilityforanydamageresultingfromusageinconsistentwiththemanual.
Theproductcontainspartsthatcanbedangerousforhumanhealth.
Wasteproductsshallbepassedtothenearestwasteelectricand
electronicequipmentcollectionpoint.
NOTE:Themanufacturerreservestherighttochangespecificationsofproductsatanytime
withoutpriornotice.

IK-E287-001GB 2
1PURPOSE
TheG‐40detectorbaseisdesignedfortheconnectionof40modelrangedetectorsinthedetectinglinesof
conventionalcontrolpanelsor4043and4046modelrangedetectorsinthedetectinglinesofthePOLON
4000seriesaddressablecontrolpanels.
Thebasesareintendedforconnectingfiredetectionlinewiresroutedonthewallplaster(surface
mounting)orunderit(semi‐flushedmounting)–thewiresareplacedinaspecialductofmaxheightat10
mm).TheG‐40detectorbasesarededicatedfordryceilingmounting.
InordertoinstalltheG‐40baseonaceilingwheresteamcondensationoccursorwhenitismountedon
horizontalsuspensionstrands,additionalPG‐40baseindustrialfootingshouldbeused.ThePG‐40base
industrialfootingisdedicatedforconnectiontodetectionlinewires(thewireisplacedinsideaductofmax
externaldiameteratØ18mm)routedontheplaster(surfacemounting).
ItispossibletoutilisetheG‐40baseasasuspendedoneusingtheinterconnectingPG‐40baseindustrial
footingequippedwiththePG7sealingglandandthePSGWceilingsuspendedbase.Thesuspendedpartof
thebaseshouldbemountedona4‐cordcableof2x2x0.8size.BoththePG7sealingglandandthePSGW
ceilingsuspendedbasearenotstandardequipmentofthebaseandshouldbeorderedseparately.
InthecaseoftheG‐40baseinstallationinplaceswhereriskitcanbeendangeredbyamechanicaldamage
(i.e.sportshall–ballstrike,lowrooms–hitwithaladder)itisrecommendedtousethespecialOZ‐40
protectioncover.
Additionally,itispossibletofixtheP‐40specialmaskingring,orderedseparately,inordertomaskthebase
visiblepart.
Note:
IftheG‐40baseinmountedinthePG‐40industrialfooting,theP‐40maskingringisnotapplicable.
2TECHNICALSPECIFICATIONS
G‐40DETECTORBASE
DetectorsinteroperatingwithG‐40base 40,4043and4046modelrangedetectors
DiameterofdetectionlinewiresØ4.5÷Ø5.5mm
Maxdiameterofcablewires≤1mm
Mass≤0.1kg
DimensionsØ107mm;height=28.5mm
Fasteningholesspacing63mm
PG‐40BASEINDUSTRIALFOOTING
Interoperatingbase G‐40base
DetectionlinewirediameterØ4.5÷Ø5.5mm
Mass≤0.1kg
DimensionsØ112mm;height=26mm
Height(PG‐40withG‐40)43mm
Fasteningholesspacing127mm

IK-E287-001GB 3
3DESIGNDESCRIPTION
TheG‐40baseismadeofwhiteplastic–onrequestitmaybemanufacturedindifferentcolours.
Thebaseconsistsofabodyembracingthemainconnector(withself‐clampinglatchestoconnectdetection
linewires)andanadditionalconnectortofixthewirescreens.
ThebasemaybeadditionallyequippedwiththeP‐40maskingring(optional).
ThemechanicalstructureoftheG‐40baseisshowninFig.1andFig.2.
Fig.1G‐40baseelementsmainview
Fig.2G‐40detectorbasemechanicaldesign

IK-E287-001GB 4
ThePG‐40baseindustrialfootingismadeofawhiteplastic–onrequestitmaybemanufacturedin
differentcolours.ThePG‐40baseindustrialfootingisahomogenousmoulding–optionallyitisequipped
withthePG7sealinggland.
ThemechanicalstructureofthePG‐40baseindustrialfootingisshowninFig.3aandFig.3b;assembling
instructionsforthesuspendedbasearepresentedinFig.4.
ThemechanicalstructureoftheOZ‐40protectioncoverisshowninFig.5.
Fig.3aPG‐40baseindustrialfootingmechanicaldesign
Fig.3bPG‐40baseindustrialfootingandPG7sealingglandmainview

IK-E287-001GB 5
Fig.4G‐40suspendedbaseassembling
Fig.5OZ‐40protectioncover

IK-E287-001GB 6
4G‐40BASEINTEROPERATIONWITHDETECTIONLINE
TheG‐40basesateintendedforinteroperationwiththemodelrange40detectorsinconventional
detectionlinesandwiththe4046/6000rangedetectorsinthePOLON4000systemcontrolpanelsdetection
lines.Thefig.7depictsthewayofconnectionofthebaseintothePOLON4000systemdetectionline.The
fig.8showshowthebasesshouldbeinstalledinconventionalcontrolpaneldetectionlines.
Continuityofadetectionlineisobtainedonlyintheeventalldetectorsareplacedintheirbases.Theline
continuitymaybeachievedwhentheE287‐04.00jumper(Fig.6)isplacedintothedetectorconnector.The
jumperisoptionalandshouldbeorderedseparately.
Fig.6Jumper
Fig.7G‐40baseinstallationindetectionlinesofPOLON4000firealarmcontrolpanels

IK-E287-001GB 7
Fig.8G‐40baseinstallationinconventionalcontrolpaneldetectinglines
5INSTALLATION
5.1Initialinstallation
ThePG‐40baseindustrialfootingshouldbemountedontheceilingwithtwoscrewsplacedinextension
anchorbolts(Ø6mmboltsarerecommended).Itisadvisedtodrilltheanchorboltholesusingapattern
with127mmholespacing.Improperholespacingmayresultinthebaseindustrialfootingdeformation
whenthescrewsarestronglytightened.
ThePG‐40baseindustrialfootingcanbeinstalledonahorizontalsteelstring(Ø8mmdiameter
recommended)usingclampingbands.

IK-E287-001GB 8
ThePG‐40suspendedversionisinstalledwithahelpofthePG7sealinggland‐Ø13mmdiameterhole
shouldbedrilledinthedetectorbodywhereacableofmaxØ7diameterisplacedto.ThePSGWceiling
suspendedbaseistobeusedforceilingmounting.
5.2Baseinstallation
TheG‐40baseinstallationmethodmustcomplywiththetypeofthebasiswherethedetectoristobe
mounted:
‐inthecaseofbrickorconcreteceilingsitisenoughtoattachthebasewithtwoscrewsand
expansionanchorbolts(Ø6mmboltsarerecommended
‐inthecaseofplasterboarditisforbiddentofastenthebasedirectlytotheplasterboardwith
screws;itisrecommendedtousespecialboltsintendedforplasterboard
‐inthecaseofsuspendedceilingitcanbenecessarytouseadditionalwashersofappropriate
diameter
‐thebaseistobejoinedwiththePG‐40baseindustrialfootingusinglatches.
Itisadvisedtodrilltheexpansionanchorboltholesusingapatternof63mmholespacing.Improperhole
spacingmayresultinthebaseindustrialfootingdeformationwhenthescrewsarestronglytightened.
Forwireconnectionaflatscrewdriver(maxedgewidthat3.5mm)useisrecommended,itshouldbe
pushed(seeFig.9)intotheproperconnectorhole.Thenthewireclosertotheceilingshouldbeplacedinto
theholeandthescrewdrivershouldbetakenoff.Itisadvisedtouseashort,bendedWAGOtypescrew
driver(3.5x0.5mm,cat.No.210‐258)thatisavailableforpurchaseatPOLON‐ALFA).Thewirefixingplaces
aremarkedontheconnectorbody.Wiresscreensshouldbeinsertedintotheadditionalconnector(the
jointtobeclampedwithfingers);thentheconnectorshouldbeplacedbetweentherailsinsidethe
rectangularhollowofthebase.
5.3.TheOZ‐40protectioncoverinstallation
TheOZ‐40protectioncoverismountedontheceilingwithtwoscrewsandexpansionanchorbolt(Ø8mm
boltsrecommended).Theboltholespacingshouldbeat124±4mm.Thebaseshouldbefixedtothecover
withtwoM4nuts.Whenthedetectorisinstalledinthebase,thegratingshouldbefastenedwiththreeM4
x10nuts.
Fig.9WireintroducingtoG‐40connector

IK-E287-001GB 9
6MAINTENANCE
Thebaseanditsindustrialfootingrequirenoservicingafterinstallationsincetheybotharemonitoredby
thefirealarmcontrolpanel.Periodicalinspectionsofbasesandindustrialfootingsarecarriedout
simultaneouslywithperiodicaldetectors’maintenance.
7STORAGE
TheG‐40detectorbasesandPG‐40baseindustrialfootingsshouldbestoredinclosedroomsatambient
temperaturebetween0oCto+40oCandrelativehumiditybetween40%and80%,(freeofcausticgases
andvapours).Detectorbasesandbaseindustrialfootingsshouldnotbeexposedtodirectsunandheating
elementsinfluence.
Thestorageperiodofthedetectorbasesandbaseindustrialfootingsintransportpackagesshouldnot
exceed24months.
8TRANSPORTATION
TheG‐40basesandPG‐40baseindustrialfootingsshouldbecarriedinclosedspacesoftransportmeansat
thetemperaturesfrom‐25oCto+70oCandrelativehumiditynotexceeding95%inproperpackagesthat
meetappropriatetransportregulations.
IK‐E287‐001GB/08.2008/05.2012
This manual suits for next models
1
Table of contents
Other Polon-Alfa Security Sensor manuals
Popular Security Sensor manuals by other brands

PSM
PSM LD161 installation guide

Crow
Crow SH-SIRINT-8F instruction manual

Safe Signal
Safe Signal WFDN Installation and maintenance instructions

NOYAFA
NOYAFA NF-5120 instruction manual

MSA Latchways
MSA Latchways Personal Rescue Device User instructions

Fire Innovations
Fire Innovations MOHAWK Instructions for use