Polypipe UFH8ZMP User manual

User’s manual
UFH8ZMP - 8 Zone RF Premium
Wiring Centre
EN
www.polypipeufh.com
User’s manual
UFH8ZMP - 8 Zone RF Premium
Wiring Centre

2
User’s manual

3
UFH8ZMP
Table of contents
I. Safety 4
II. Description of the device 5
II.a) Principle of operation 5
III. Controller installation 6
III.a) First start-up 7
IV. Wireless communication 13
V. Main screen description and view 14
VI. Controller function 16
VI.a) Block diagram of the menu 16
VI.b) Manual operation 17
VI.c) Zones 17
VI.d) Language 19
VI.e) Display contrast 19
VI.f) Fitter’s menu 19
VI.g) Software version 19
VII. Protections and alarm 20
VIII. Software update 21

4
User’s manual
I. Safety
Before using the device for the fi rst time the user should read the following regulations
carefully. Not obeying the rules included in this manual may lead to personal injuries
or controller damage. The user’s manual should be stored in a safe place for further
reference. In order to avoid accidents and errors it should be ensured that every person
using the device has familiarized themselves with the principle of operation as well as
security functions of the controller. If the device is to be sold or put in a diff erent place,
make sure that the user’s manual is there with the device so that any potential user has
access to essential information about the device.
The manufacturer does not accept responsibility for any injuries or damage resulting from
negligence; therefore, users are obliged to take the necessary safety measures listed in
this manual to protect their lives and property.
WARNING
• High voltage! Make sure the regulator is disconnected from the mains before performing
any activities involving the power supply (plugging cables, installing the device etc.)
• The device should be installed by a qualifi ed electrician.
• Before starting the controller, the user should measure earthing resistance of the
electric motors as well as the insulation resistance of the cables.
• The regulator should not be operated by children
WARNING
• The device may be damaged if struck by a lightning. Make sure the plug is disconnected
from the power supply during storm.
• Any use other than specifi ed by the manufacturer is forbidden.
• Before and during the heating season, the controller should be checked for condition of
its cables. The user should also check if the controller is properly mounted and clean
it if dusty or dirty.
Changes in the merchandise described in the manual may have been introduced
subsequent to its completion on February 28th 2016. The manufacturer retains the right
to introduce changes to the structure. The illustrations may include additional equipment.
Print technology may result in diff erences in colours shown.
We are committed to protecting the environment. Manufacturing electronic devices imposes
an obligation of providing for environmentally safe disposal of used
electronic components and devices. Hence, we have been entered into a
register kept by the Inspection For Environmental Protection. The crossed-
out bin symbol on a product means that the product may not be disposed
of to household waste containers. Recycling of wastes helps to protect the
environment. The user is obliged to transfer their used equipment to a
collection point where all electric and electronic components will be
recycled.

5
UFH8ZMP
II. Description of the device
UFH8ZMP wiring centre is intended for wireless control of the valves (see: Wireless
communication). The controller enables signifi cant energy saving due to precise
temperature management in particular rooms. Due to advanced software, the controller
fulfi ls a wide range of functions:
• controlling thermostatic actuators 230V
• controlling the pump ( 230V input)
• voltage-free contact intended for controlling e.g. the heating device
• possibility of connecting Internet modules which allow the user to adjust certain
functions and view certain parameters via the Internet
• controlling 8 temperature sensors (placed in separate heating zones
Controller dimensions
II.a) Principle of operation
Controller decides if a given zone needs to be heated on the basis of current temperature
value sent by the room sensor or the room regulator as well as the individual operation
algorithm of the zone.
If heating is necessary, controller opens the valve and activates the pump and the
additional contact which may be used e.g. for controlling the heating device.
Each zone should be assigned wired valve actuators.
.

6
User’s manual
III. Controller installation
The controller should be installed by a qualifi ed person.
WARNING
Risk of fatal electric shock from touching live connections. Before working on
the controller switch off the power supply and prevent it from being accidentally
switched on.
1. Cover (it should be removed to connect the devices to be controlled)
2. Display
3. Aerial – for wireless communication
4. Buttons
Controller may be installed as a free-standing device or as a panel mountable on a wall.
Controller may be installed as a free-standing device or as a panel mountable on a wall.
The controller may be installed on a DIN strip
123
4

7
UFH8ZMP
The controller may be installed on a DIN strip or by removing the front cover and using the
4 holes to screw to the wall.
III.a) First start-up
In order for the controller to operate correctly, the user must follow these steps when
starting the device for the fi rst time:
1. Connect UFH8ZMP with all the subordinate devices to be controlled
2. Switch on the power supply and check if the devices work.
3. Activate the Internet module.
4. Set current time and date.
5. Confi gure the temperature sensors settings / room regulators.
Step 1:Connect UFH8ZMP with all subordinate devices to be controlled
Remove the cover and connect the wires following the labels on the connectors and the
diagrams presented below.
Follow this order while connecting:
- all the necessary valve actuators (connectors 1..8)
- Internet module (using RS cable)
- pump
- an additional device
III. Controller installation
The controller should be installed by a qualifi ed person.
WARNING
Risk of fatal electric shock from touching live connections. Before working on
the controller switch off the power supply and prevent it from being accidentally
switched on.
1. Cover (it should be removed to connect the devices to be controlled)
2. Display
3. Aerial – for wireless communication
4. Buttons
Controller may be installed as a free-standing device or as a panel mountable on a wall.
The controller may be installed on a DIN strip

8
User’s manual
Thermostats that require a power supply can be wired into any of the 3 provided
connections. Two thermostats can be wired into the same connection allowing power to 6
thermostats. Thermostats can also be wired in a ‚daisy chain’ formation or powered by a
seperate electrical circuit, to allow power for upto 8 thermostats if required.
1 2 3 4 5 6 7 8 9
13
11
12
POWER SUPPLY 230V 50Hz
M
POWER SUPPLY 230V 50Hz
HEATING
DEVICE
M
10

9
UFH8ZMP
Pictorial diagram presenting wiring and communication with other devices in the system.
lub
heating
device
9
12 13
1 2 3 4 5 6 7 8
11
10
ETHERNET
RS
WIFI
21ºC
21ºC
23ºC
20ºC 20ºC
23ºC
23ºC
21ºC

10
User’s manual
KSTEP 2: Switch on the power supply and check if the devices work
After all the devices have been connected, switch on the power supply.
Use Manual operation function in order to check if particular devices work properly.
Use ▲ and ▼to select the device and press MENU – the device should switch on. Follow
this procedure to check all the devices.
STEP 3: Activate the Internet module
UFH8ZMP external controller is compatible with UFHINTMODP and UFHINTWIFIP Internet
modules.
UFHINTWIFIP uses WiFi wireless network whereas UFHINTMODP needs to be connected to
a router with RJ45 network cable.
Connection diagram for UFHINTMODP Internet module
ROUTER
Connection diagram for UFHINTWIFIP Internet module.
Internet modules should be connected as illustrated in the diagrams above. Next, activate
the module: Main menu/Fitter’s menu/Internet module/ON. Further steps are described in
detail in the instruction manual for the Internet module.
ROUTER

11
UFH8ZMP
NOTE
The user should enable the Internet module to connect with data servers listening
on TCP/2000 port. Most computer networks are protected by various software
(fi rewalls, anti-virus software etc.) which may block data exchange with the
above mentioned port. If any problems arise, contact technical support or your
computer network administrator.
STEP 5. Set current time and date
Set current time and date in the fi tter’s menu.
Step 5. Confi gure temperature sensors / room regulators
To enable UFH8ZMP external controller to control a given zone, it is necessary to provide
it with current temperature value. The easiest way is to use temperature sensor. If the
user wants to be able to change the pre-set temperature value directly from the zone, it is
advisable to use room regulators (an additional advantage of using room regulators is the
possibility of setting a weekly schedule of the pre-set temperature).
The user may also choose UFHTFTM room regulator which off ers additional
functionalities apart from sending the current temperature readings. It serves as a master
controller enabling the user to change the pre-set zone temperatures, adjust the weekly
schedules etc. Only one room regulator of this type may be installed in the heating system.
Regardless of the type of temperature sensor / room regulator chosen, it must be
registered in a particular zone in UFH8ZMP controller menu
How to register UFHSENSEWP room sensor:
In order to register, go to Sensor in the submenu of a
given zone (Zone / Registration / Sensor). After selecting
Registration press the communication button on the
selected temperature sensor.
If the process has been completed successfully, UFH8ZMP
external controller display shows an appropriate message.
Communication
button

12
User’s manual
How to register UFHBOOSTWP room regulator:
In order to register, go to Sensor in the submenu of a given zone
(Zone / Registration / Sensor). After selecting Registration press
the communication button on the selected room regulator.
If the registration process has been completed
successfully, the UFH8ZMP display shows an appropriate message
whereas the room sensor display shows “Scs”. In case of errors in
the registration process, the room sensor display shows “Err”.
How to register UFHTFT room regulators:
In order to register, go to Sensor in the submenu
of a given zone ( Zone/Registration/Sensor). After
selecting Registration go to the room regulator menu
and activate the registration process (Controller
settings / Registration).
If the process has been completed
successfully, SUFH8ZMP external controller display
and the room regulator display show an appropriate
message
NOTE
Only one sensor / room regulator may be assigned to each zone.
The following rules must be kept in mind:
- once registered, the sensor/regulator cannot be unregistered, but only switched off by
selecting Switched off in the submenu of a given zone,
- if the user attempts to assign a sensor/regulator to the zone to which other sensor/
regulator has already been assigned, the fi rst sensor becomes unregistered and it is
replaced by the second one.
- if the user attempts to assign a sensor/regulator which has already been assigned to a
diff erent zone, the sensor/regulator is unregistered from the fi rst zone and registered in
the new one.
It is possible to set individual pre-set temperature value and weekly schedule for each
room sensor / regulator assigned to a given zone. The settings may be confi gured both
in the controller menu (Main menu/Sensors) and via polypipe.emodul.eu (using Internet
module).

13
UFH8ZMP
IV. Wireless communication
It is possible to establish wireless communication between UFH8ZMP external controller
and certain devices:
Function Confi guration
UFHSENSEWP
– room
temperature
sensor
- sending current zone
temperature
The sensor must
be registered in a
given zone.
UFHBOOSTWP
– room
regulator
- sending current zone
temperature
- possibility of changing the
pre-set temperature directly
from the zone
The room
regulator must
be registered
in the external
controller.
UFHTFT
– room
regulator
- sending current zone
temperature
- possibility of adjusting the
pre-set temperature and the
schedule settings directly
from the zone
The room
regulator must
be registered
in the external
controller.
UFHTFTM –
master room
regulator
- sending current zone
temperature
- possibility of adjusting the
pre-set temperature and the
schedule settings directly
from the zone
- possibility of adjusting
settings for other zones
The room
regulator must
be registered
in the external
controller.

14
User’s manual
V. Main screen description and view
The user navigates in the menu structure using the buttons located next to the display
1. Display
2. ▲- „up” „plus” – it is used to view the menu options and increase the value while editing
parameters. During standard operation the button is used to switch between diff erent
zones parameters.
3. ▼- „down” „minus” - it is used to view the menu options and decrease the value while
editing parameters. During standard operation the button is used to switch between
diff erent zones parameters.
4. MENU button – it is used to enter the controller menu and confi rm the new settings
5. EXIT button – it is used to exit the menu and cancel the settings
1
2
3
4
5

15
UFH8ZMP
1. An icon indicating valve operation
2. An icon indicating that the additional contact is switched on
3. Current time
4. Time left until the manually set temperature in a given zone changes
5. Information about the type of current weekly schedule
6. Pre-set temperature in a given zone (backlit number in the zone bar – see: description
no. 12)
7. Sensor battery level in a given zone (backlit number in the zone bar – see: description
no. 12)
8. Sensor signal strength in a given zone (backlit number in the zone bar – see: description
no. 12)
9. Current temperature of sensor in a given zone (backlit number in the zone bar – see:
description no. 12)
10. Zone information:
The digit displayed indicates that the room sensor is connected and sends current
temperature information. If the zone temperature is too low, the digit fl ashes. In the event
of a zone alarm, an exclamation mark is displayed instead of the digit. In order to view the
operation parameters of a given zone, select its number using ▲or ▼.
123
10
9
4
8765

16
User’s manual
VI. Controller function
Due to multiple function fulfi lled by the controller, the menu is divided into Main menu and
Fitter’s menu.
VI.a) Block diagram of the menu

17
UFH8ZMP
VI.b) Manual operation
This function enables the user to activate particular devices (pump, voltage-free contact
and valve actuators) independently of the others it order to check if they operate properly.
In is advisable to check the devices using this procedure at the fi rst start-up.
VI.c) Zones
This submenu enables the user to confi gure operation parameters for particular zones.
When the pre-set temperature value in a zone is reached, the controller labels the zone as
suffi ciently heated and the status remains until the temperature drops below the pre-set
temperature by hysteresis value. When the temperature in all the zones is suffi cient, the
controller disables both the pump and the voltage-free contact.
Submenu of each zone:
• OFF/ON
After the room sensor has been connected and registered in a given zone. The sensor may
be deactivated by selecting OFF option.
• Pre-set temperature
The pre-set zone temperature depends on the weekly schedule settings. However, this
function enables the user to change this value separately.
After the value has been set, the user defi nes how long the temperature should apply.
When the time elapses, the pre-set temperature depends on the weekly schedule again.
If the user sets 00:00 as the time, the temperature applies for indefi nite period of time.
The main screen displays current pre-set temperature value and the time left (see: Main
screen description).

18
User’s manual
• Weekly control
The controller off ers two types of weekly schedules:
Own – local schedule
This weekly schedule is assigned to a given zone only. After the room sensor has been
detected by the external controller, the schedule is activated automatically in this zone and
may be adjusted by the user to individual needs.
1..5 schedules – global schedule
These schedules have universal settings for all zones and they cannot be edited in the
external controller (to introduce changes it is necessary to connect to the Internet via the
Internet module or UFHTFTM).
In order to assign a schedule to a given zone, choose Select option.
In order to adjust the global schedule as the current schedule in a given zone,
choose Edit option. After the schedule has been modifi ed and saved, it is overwritten as a
local schedule.
The type of weekly schedule assigned to a zone is displayed in the main screen (See: Main
screen description – screen area no. 9).
Edit
In order to start editing, select Edit option.
The user may program up to 3 time periods with pre-defi ned time limits (with the
accuracy of 15 minutes). Separate temperature value is assigned to each time period. The
next step involves setting the temperature value to apply outside the time periods (setback
temperarture).
The last step involves choosing days of the week when the settings should apply.
Use ▲to edit the next day and press ▼ to select/deselect.
• Calibration
Room sensor calibration should be performed while mounting or after it has been used
for a long time, if the external temperature displayed diff ers from the actual temperature.
Calibration setting range is from -10˚C to +10˚C with the accuracy of 0,1˚C.
• Hysteresis
This function is used to defi ne tolerance of the pre-set temperature in order to prevent
undesired oscillation in case of small temperature fl uctuation (within the range 0 ÷ 10⁰C)
with the accuracy of 0,1°C.
Example: if the pre-set temperature is 23⁰C and the hysteresis is 0,5⁰C, the zone
temperature is considered too low when it drops to 22,5⁰C.

19
UFH8ZMP
• Registration
A temperature sensor or room regulator should be registered in each zone. In order to
register the sensor, go to sensors option. In order to register the actuators, go to Register
valve option.
VI.d) Language
This option is used to select the language version.
VI.e) Display contrast
This option is used to adjust the display contrast to individual user’s needs.
VI.f) Fitter’s menu
The Fitter’s Menu is intended to be operated by people with appropriate qualifi cations and
is used primarily to adjust the controller’s additional functions.
Internet module
UFH8ZMP controller may cooperate with the Internet module which enables the user to
view and adjust certain parameters via the Internet. Such online control is possible only
after purchasing and connecting an additional module.
The Internet module may be connected to UFH8ZMP via RS cable. After it has been
connected, select Registration. The controller generates a code which the user should enter
on the Internet website. Detailed description of the procedure is available in the Internet
module instruction manual.
Internet module is a device enabling the user remote control of the regulator via the
Internet. The user controls the status of all valves on the home computer screen.
After switching the module on and selecting DHCP option, the controller automatically
downloads such parameters as IP address, IP mask, gateway address and DNS address
from the local network. If any problems arise when downloading the network parameters,
they may be set manually. The procedure of obtaining these parameters is described in
detail in the instruction manual of the Internet Module
Time
This option is used to set current time.
Date
This option is used to set current date
VI.g) Software version
When this option is selected, the display shows the logo of the CH boiler manufacturer and
the controller software version.

20
User’s manual
VII. Protections and alarm
In order to ensure safe and failure-free operation, the regulator has been equipped with a
range of safeguards. In case of an alarm, a sound signal is activated and the display shows
a message informing about the detected problem.
Temperature protection.
UFH8ZMP external controller is equipped with thermal protection which disconnects
UFH8ZMP from the power supply when the protection temperature has been exceeded.
WARNING
!!!This item must be connected in order to start the controller.!!!
Automatic sensor control
In the event of temperature sensor or external sensor damage, an alarm is activated and
the display shows an appropriate message, e.g.: „Sensor damaged”.
The alarm remains active until the fault is removed (the sensor battery or the sensor itself
is replaced) and alarm is deleted in the external controller.
How to delete the zone alarm in the external controller
Select the zone in which the alarm occurred (indicated by the exclamation mark instead of
the number). Press EXIT – two options appear on the screen:
-Reset
The external controller re-attempts to communicate with the sensor (it may take up to
several minutes). Until the communication is established, the valve remains in the alarm
mode (closed – zone temperature reached). If the communication attempt fails, the alarm
activates again.
-Deactivate
This option deactivates the zone altogether. It may be activated again by selecting Activate
in Main menu/Sensors/1..8 zones.
Fuse
The regulator has a WT 3,15A tube fuse-link (5x20mm) protecting the network.
WARNING
Higher amperage fuse should not be used as it may damage the controller.
Table of contents
Other Polypipe Thermostat manuals
Popular Thermostat manuals by other brands

NuTone
NuTone NTBZ48 Installation & operation guide

EWC Controls
EWC Controls EWT-725 installation manual

hager
hager WS310 systo User instructions

Carrier
Carrier 33CS Installation and operating instructions

Hot Yoga Heating
Hot Yoga Heating HYH-32-P installation manual

Honeywell
Honeywell FocusPRO TH6110D installation guide