
Supplied By www.heating spares.co Tel. 0161 620 6677
INTRODUCTION
The information given on this card will help you to obtain the
maximum comfort from your boiler with the minimum trouble and
cost. Your boiler is fully automatic in operation and requires very
little attention apart from setting the thermostat.
Regular skilled servicing is required to maintain the safe and
efficient operation of your boiler throughout its long working life.
Further information on this subject is given at a later stage.
ELECTRICITY SUPPLY
WARNING: THIS APPLIANCE MUST BE EARTHED
Connection shall be made to a 240V-50 Hz supply. The appliance
must be protected by a 3 amp fuse if a 13 amp (B51363) plug is
used or if any other type of plug is used by a 5 amp fuse in the
circuit.
TO CONNECT A PLUG
As the colour of the wires in the mains lead of the appliance may
not correspond with the coloured markings identifying the
terminals in your plug, proceed as follows:-
The wire which is coloured green-and-yellow must be connected to
the terminal in the plug which is marked with the letter E or by the
earth symbol or coloured green or green-and-yellow.
The wire which is coloured blue must be connected to the terminal
which is marked with the letter N or coloured black.
The wire which is coloured brown must be connected to the
terminal which is marked with the letter L or coloured red.
SAFETY
The boiler should have the following minimum clearances for
Safety and Maintenance, 610mm (2ft) at the front of the boiler,
5mm (3116in) each side, 100mm (4in) at the bottom, 50mm (2in)
at the top.
Flammable materials must not be stored in close proximity to the
boiler.
Ensure that the flue terminal outside the house, does not become
obstructed, particularly by foliage.
THE BOILER THERMOSTAT
The boiler thermostat enables you to control the temperature of
the water as it leaves the boiler and is also used for turning the
boiler on and off. The thermostat knob can be set to 0 (OFF),
1,2,3,4,5 or Max. The graduations 1 to Max. correspond
approximately to a temperature range of 55C to 82 C (130F -
180F).
During the summer months, when the boiler is only being used to
supply stored domestic hot water and there is no independent hot
water temperature control, the thermostat can be set to position 1
or 2 which will probably be hot enough for bathing or washing up
requirements. For washing clothes, a higher setting may be
necessary.
In winter weather, when central heating is required, the thermostat
knob can be turned up higher but it must be remembered that
unless the temperature of the water in the domestic hot water
cylinder is independently controlled, the stored hot water could be
at a temperature that could scald, i.e. about 82C (180°F).
OTHER CONTROLS
A Potterton Electronic Programmer or other type of clock may
have been fitted in your system, together with room and/or cylinder
thermostats. Full instructions on the use of these controls should
be supplied with them.
TO LIGHT
1. Ensure that the boiler thermostat knob is at ‘0’ (fully anti-
clockwise).
2. Switch ‘ON’ the main electricity supply.
3. Ensure the electronic programmer or other time control, if
fitted, is in an ‘ON’ period (refer to time control literature).
4. Ensure that any room and/or cylinder thermostats are at a
high temperature setting.
Proceed as follows:— Turn the boiler thermostat on and to the
required setting. After a short period, the boiler will light: the main
burner can be seen through the sight glass on the front of the
boiler. Set the time control and any thermostats, where fitted, to
their desired settings.
NOTE:- When the boiler is first lit, there may be a slight smell. This
will disappear with use.
TO SHUT THE BOILER OFF
Turn the boiler thermostat knob to ‘0’, or switch the external
programmer to the ‘OFF’ position. To relight the boiler, simply turn
the boiler thermostat ‘ON’ or switch tile programmer to the ‘ON’
position.
FOR LONGER SHUT DOWN PERIODS
Turn the boiler thermostat to ‘0’, isolate the electrical supply at the
isolating switch, or pull the plug out of its socket.
NOTE:
If the system is fitted with a low limit thermostat and protection of
the system is required during cold weather, all that is required is
for the programmer to be turned to the ‘OFF’ position. This will
allow the boiler to cycle if the temperature within the house
becomes too low.
IMPORTANT
Gas and electricity are required to operate your boiler. Its
performance will not be affected by normal variation in gas or
electricity supply, but a gas or electricity failure will put the boiler
out of operation. It will automatically re-start when the supply is
restored, provided that the time clock and/or thermostats are in an
‘ON’ position.
In the event of your boiler not working, there are several checks
you should carry out before calling in a service engineer, as this
could save you unnecessary expense.
1Check that the gas, electricity and water are all turned on at
the main supply.
2. Check that the time control, if fitted, is in an ‘ON’ period.